E Multirack Cabling Tables

InfiniBand cables connect multiple racks together, in addition to connecting the components within a rack. The cable lengths provided in these tables are for adjacent racks with the cables running underneath the racks. If the racks are apart or the cables run above the racks, then longer cables might be required. The cable lengths listed here are only guidelines. You should always verify the actual cable lengths required.

This appendix contains the following sections:

E.1 About Multirack Cabling

You can connect up to 18 full Recovery Appliance racks. The racks do not include spare cables or a third Sun Datacenter InfiniBand Switch 36, which functions as the spine switch. To extend a rack, order the cables and a Sun Datacenter InfiniBand Switch 36.

This section contains the following topics:

E.1.1 Cables Provided With a Spine Switch

The Sun Datacenter InfiniBand Switch 36 switches attach to standard Quad Small Form-factor Pluggable (QSFP) connectors at the ends of the InfiniBand cables.

Table E-1lists the spare cables provided with the Sun Datacenter InfiniBand Switch 36 spine switch.

Table E-1 InfiniBand Cables Provided as Spares

Cable Spare Interswitch Total

InfiniBand 2 meter cable

0

7

7

InfiniBand 3 meter cable

6

2

8

InfiniBand 5 meter cable

10

0

10

E.1.2 Optical Cables Required for Four or More Racks

Connecting four or more racks requires additional 10-meter optical QSFP-to-QSFP QDR InfiniBand cables. Each optical cable requires two QSFP SR transceivers. Table E-2 lists the cables needed to connect the racks.

Table E-2 Cable Requirements for Multirack Installations

Number of Racks 3 Meter Cables 5 Meter Cables 10 Meter Cables

2

16

16

0

3

18

30

0

4

16

40

8

5

20

42

18

6

24

46

26

7

28

44

40

8

16

52

60

E.1.3 Cabling Three Switches Within a Rack

In a single rack, the two leaf switches are interconnected using seven connections. In addition, each leaf switch has one connection to the spine switch. The leaf switches connect to the spine switch as shown in Figure E-1.

Figure E-1 In-Rack Connections Between Spine Switch and Leaf Switches

Description of Figure E-1 follows
Description of "Figure E-1 In-Rack Connections Between Spine Switch and Leaf Switches"

The servers connect to the leaf switches as shown in Figure E-2.

Figure E-2 In-Rack Connections Between the Servers and the Leaf Switches

Description of Figure E-2 follows
Description of "Figure E-2 In-Rack Connections Between the Servers and the Leaf Switches"

E.1.4 Cabling the Switches in Two Racks

When you connect up to eight racks, remove the seven interswitch connections between the leaf switches and the two connections between the leaf switches and the spine switch. From each leaf switch, distribute eight connections over the spine switches in all racks. In multirack environments, the leaf switches inside a rack are not directly connected.

Figure E-3 shows that each leaf switch in rack 1 connects to the following switches:

  • Four in-rack connections to the spine switch in rack 1

  • Four external connections to the spine switch in rack 2

The spine switch in rack 1 connects to the following switches:

  • Eight in-rack connections to both leaf switches in rack 1

  • Eight external connections to both leaf switches in rack 2

Figure E-3 Connecting Switches Across Two Racks

Description of Figure E-3 follows
Description of "Figure E-3 Connecting Switches Across Two Racks"

E.1.5 Cabling the Switches in Up to Eight Racks

As the number of racks increases from two to eight, the pattern continues, as shown in Figure E-4. Because not all of the racks are shown, not all of the cables are shown either.

Each leaf switch has eight interswitch connections distributed across all spine switches. Each spine switch has 16 interswitch connections distributed across all leaf switches. The leaf switches are not directly connected to other leaf switches, and the spine switches are not directly connected to the other spine switches.

Figure E-4 Connecting Switches Across Eight Racks

Description of Figure E-4 follows
Description of "Figure E-4 Connecting Switches Across Eight Racks"

E.1.6 Cabling Switches in Up to 18 Racks

When you connect racks 9 through 18, remove the interswitch connections between the leaf switches, and disconnect the spine switches from the InfiniBand fabric. Figure E-5 shows that the eight links from every leaf switch connect to the spine switches in racks 1 to 8.

The connections among racks 1 to 8 do not change you add the cables for racks 9 to 18.

Figure E-5 Connecting Switches Across 18 Racks

Description of Figure E-5 follows
Description of "Figure E-5 Connecting Switches Across 18 Racks"

Note:

Cable lengths are specified for racks 1 through 8. Cable lengths for racks 9 through 18 vary depending on the layout of the racks.

E.2 Key to Cabling Table Abbreviations

The following abbreviations are used in the tables:

Abbreviation Description

Rn

Rack n, where n is the number of the rack, such as R1.

IBn

Unit location in rack, where n is the number, such as IB3.

Pn

InfiniBand port n, where n is port number, such as P8A.

E.3 Two-Rack Cabling

Table E-3 shows the cable connections for the first spine switch (R1-U1) when two full racks are cabled together.

Table E-3 Leaf Switch Connections for Rack 1 in a Two-Rack System

Leaf Switch Connection Cable Length

R1 IB3 within Rack 1

R1-IB3-P8A to R1-U1-P3A

R1-IB3-P8B to R1-U1-P4A

R1-IB3-P9A to R1-U1-P5A

R1-IB3-P9B to R1-U1-P6A

3 meters

R1 IB3 to Rack 2

R1-IB3-P10A to R2-U1-P7A

R1-IB3-P10B to R2-U1-P8A

R1-IB3-P11A to R2-U1-P9A

R1-IB3-P11B to R2-U1-P10A

5 meters

R1 IB2 within Rack 1

R1-IB2-P8A to R1-U1-P3B

R1-IB2-P8B to R1-U1-P4B

R1-IB2-P9A to R1-U1-P5B

R1-IB2-P9B to R1-U1-P6B

3 meters

R1 IB2 to Rack 2

R1-IB2-P10A to R2-U1-P7B

R1-IB2-P10B to R2-U1-P8B

R1-IB2-P11A to R2-U1-P9B

R1-IB2-P11B to R2-U1-P10B

5 meters

Table E-4 shows the cable connections for the second spine switch (R2-U1) when two full racks are cabled together.

Table E-4 Leaf Switch Connections for Rack 2 in a Two-Rack System

Leaf Switch Connection Cable Length

R2 IB3 within Rack 2

R2-IB3-P8A to R2-U1-P3A

R2-IB3-P8B to R2-U1-P4A

R2-IB3-P9A to R2-U1-P5A

R2-IB3-P9B to R2-U1-P6A

3 meters

R2 IB3 to Rack 1

R2-IB3-P10A to R1-U1-P7A

R2-IB3-P10B to R1-U1-P8A

R2-IB3-P11A to R1-U1-P9A

R2-IB3-P11B to R1-U1-P10A

5 meters

R2 IB2 within Rack 2

R2-IB2-P8A to R2-U1-P3B

R2-IB2-P8B to R2-U1-P4B

R2-IB2-P9A to R2-U1-P5B

R2-IB2-P9B to R2-U1-P6B

3 meters

R2 IB2 to Rack 1

R2-IB2-P10A to R1-U1-P7B

R2-IB2-P10B to R1-U1-P8B

R2-IB2-P11A to R1-U1-P9B

R2-IB2-P11B to R1-U1-P10B

5 meters

E.4 Three-Rack Cabling

Table E-5 shows the cable connections for the first spine switch (R1-U1) when three full racks are cabled together.

Table E-5 Leaf Switch Connections for Rack 1 in a Three-Rack System

Leaf Switch Connection Cable Length

R1 IB3 within Rack 1

R1-IB3-P8A to R1-U1-P3A

R1-IB3-P8B to R1-U1-P4A

R1-IB3-P9A to R1-U1-P5A

3 meters

R1 IB3 to Rack 2

R1-IB3-P9B to R2-U1-P6A

R1-IB3-P10A to R2-U1-P7A

R1-IB3-P10B to R2-U1-P8A

5 meters

R1 IB3 to Rack 3

R1-IB3-P11A to R3-U1-P9A

R1-IB3-P11B to R3-U1-P10A

5 meters

R1 IB2 within Rack 1

R1-IB2-P8A to R1-U1-P3B

R1-IB2-P8B to R1-U1-P4B

R1-IB2-P9A to R1-U1-P5B

3 meters

R1 IB2 to Rack 2

R1-IB2-P9B to R2-U1-P6B

R1-IB2-P10A to R2-U1-P7B

R1-IB2-P10B to R2-U1-P8B

5 meters

R1 IB2 to Rack 3

R1-IB2-P11A to R3-U1-P9B

R1-IB2-P11B to R3-U1-P10B

5 meters

Table E-6 shows the cable connections for the second spine switch (R2-U1) when three full racks are cabled together.

Table E-6 Leaf Switch Connections for Rack 2 in a Three-Rack System

Leaf Switch Connection Cable Length

R2 IB3 within Rack 2

R2-IB3-P8A to R2-U1-P3A

R2-IB3-P8B to R2-U1-P4A

R2-IB3-P9A to R2-U1-P5A

3 meters

R2 IB3 to Rack 1

R2-IB3-P11A to R1-U1-P9A

R2-IB3-P11B to R1-U1-P10A

5 meters

R2 IB3 to Rack 3

R2-IB3-P9B to R3-U1-P6A

R2-IB3-P10A to R3-U1-P7A

R2-IB3-P10B to R3-U1-P8A

5 meters

R2 IB2 within Rack 2

R2-IB2-P8A to R2-U1-P3B

R2-IB2-P8B to R2-U1-P4B

R2-IB2-P9A to R2-U1-P5B

3 meters

R2 IB2 to Rack 1

R2-IB2-P11A to R1-U1-P9B

R2-IB2-P11B to R1-U1-P10B

5 meters

R2 IB2 to Rack 3

R2-IB2-P9B to R3-U1-P6B

R2-IB2-P10A to R3-U1-P7B

R2-IB2-P10B to R3-U1-P8B

5 meters

Table E-7 shows the cable connections for the third spine switch (R3-U1) when three full racks are cabled together.

Table E-7 Leaf Switch Connections for Rack 3 in a Three-Rack System

Leaf Switch Connection Cable Length

R3 IB3 within Rack 3

R3-IB3-P8A to R3-U1-P3A

R3-IB3-P8B to R3-U1-P4A

R3-IB3-P9A to R3-U1-P5A

3 meters

R3 IB3 to Rack 1

R3-IB3-P9B to R1-U1-P6A

R3-IB3-P10A to R1-U1-P7A

R3-IB3-P10B to R1-U1-P8A

5 meters

R3 IB3 to Rack 2

R3-IB3-P11A to R2-U1-P9A

R3-IB3-P11B to R2-U1-P10A

5 meters

R3 IB2 within Rack 3

R3-IB2-P8A to R3-U1-P3B

R3-IB2-P8B to R3-U1-P4B

R3-IB2-P9A to R3-U1-P5B

3 meters

R3 IB2 to Rack 1

R3-IB2-P9B to R1-U1-P6B

R3-IB2-P10A to R1-U1-P7B

R3-IB2-P10B to R1-U1-P8B

5 meters

R3 IB2 to Rack 2

R3-IB2-P11A to R2-U1-P9B

R3-IB2-P11B to R2-U1-P10B

5 meters

E.5 Four-Rack Cabling

Table E-8 shows the cable connections for the first spine switch (R1-U1) when four full racks are cabled together.

Table E-8 Leaf Switch Connections for Rack 1 in a Four-Rack System

Leaf Switch Connection Cable Length

R1 IB3 within Rack 1

R1-IB3-P8A to R1-U1-P3A

R1-IB3-P8B to R1-U1-P4A

3 meters

R1 IB3 to Rack 2

R1-IB3-P9A to R2-U1-P5A

R1-IB3-P9B to R2-U1-P6A

5 meters

R1 IB3 to Rack 3

R1-IB3-P10A to R3-U1-P7A

R1-IB3-P10B to R3-U1-P8A

5 meters

R1 IB3 to Rack 4

R1-IB3-P11A to R4-U1-P9A

R1-IB3-P11B to R4-U1-P10A

10 meters

R1 IB2 within Rack 1

R1-IB2-P8A to R1-U1-P3B

R1-IB2-P8B to R1-U1-P4B

3 meters

R1 IB2 to Rack 2

R1-IB2-P9A to R2-U1-P5B

R1-IB2-P9B to R2-U1-P6B

5 meters

R1 IB2 to Rack 3

R1-IB2-P10A to R3-U1-P7B

R1-IB2-P10B to R3-U1-P8B

5 meters

R1 IB2 to Rack 4

R1-IB2-P11A to R4-U1-P9B

R1-IB2-P11B to R4-U1-P10B

10 meters

Table E-9 shows the cable connections for the second spine switch (R2-U1) when four full racks are cabled together.

Table E-9 Leaf Switch Connections for Rack 2 in a Four-Rack System

Leaf Switch Connection Cable Length

R2 IB3 within Rack 2

R2-IB3-P8A to R2-U1-P3A

R2-IB3-P8B to R2-U1-P4A

3 meters

R2 IB3 to Rack 1

R2-IB3-P11A to R1-U1-P9A

R2-IB3-P11B to R1-U1-P10A

5 meters

R2 IB3 to Rack 3

R2-IB3-P9A to R3-U1-P5A

R2-IB3-P9B to R3-U1-P6A

5 meters

R2 IB3 to Rack 4

R2-IB3-P10A to R4-U1-P7A

R2-IB3-P10B to R4-U1-P8A

5 meters

R2 IB2 within Rack 2

R2-IB2-P8A to R2-U1-P3B

R2-IB2-P8B to R2-U1-P4B

3 meters

R2 IB2 to Rack 1

R2-IB2-P11A to R1-U1-P9B

R2-IB2-P11B to R1-U1-P10B

5 meters

R2 IB2 to Rack 3

R2-IB2-P9A to R3-U1-P5B

R2-IB2-P9B to R3-U1-P6B

5 meters

R2 IB2 to Rack 4

R2-IB2-P10A to R4-U1-P7B

R2-IB2-P10B to R4-U1-P8B

5 meters

Table E-10 shows the cable connections for the third spine switch (R3-U1) when four full racks are cabled together.

Table E-10 Leaf Switch Connections for Rack 3 in a Four-Rack System

Leaf Switch Connection Cable Length

R3 IB3 within Rack 3

R3-IB3-P8A to R3-U1-P3A

R3-IB3-P8B to R3-U1-P4A

3 meters

R3 IB3 to Rack 1

R3-IB3-P10A to R1-U1-P7A

R3-IB3-P10B to R1-U1-P8A

5 meters

R3 IB3 to Rack 2

R3-IB3-P11A to R2-U1-P9A

R3-IB3-P11B to R2-U1-P10A

5 meters

R3 IB3 to Rack 4

R3-IB3-P9A to R4-U1-P5A

R3-IB3-P9B to R4-U1-P6A

5 meters

R3 IB2 within Rack 3

R3-IB2-P8A to R3-U1-P3B

R3-IB2-P8B to R3-U1-P4B

3 meters

R3 IB2 to Rack 1

R3-IB2-P10A to R1-U1-P7B

R3-IB2-P10B to R1-U1-P8B

5 meters

R3 IB2 to Rack 2

R3-IB2-P11A to R2-U1-P9B

R3-IB2-P11B to R2-U1-P10B

5 meters

R3 IB2 to Rack 4

R3-IB2-P9A to R4-U1-P5B

R3-IB2-P9B to R4-U1-P6B

5 meters

Table E-11 shows the cable connections for the fourth spine switch (R4-U1) when four full racks are cabled together.

Table E-11 Leaf Switch Connections for Rack 4 in a Four-Rack System

Leaf Switch Connection Cable Length

R4 IB3 within Rack 4

R4-IB3-P8A to R4-U1-P3A

R4-IB3-P8B to R4-U1-P4A

3 meters

R4 IB3 to Rack 1

R4-IB3-P9A to R1-U1-P5A

R4-IB3-P9B to R1-U1-P6A

10 meters

R4 IB3 to Rack 2

R4-IB3-P10A to R2-U1-P7A

R4-IB3-P10B to R2-U1-P8A

5 meters

R4 IB3 to Rack 3

R4-IB3-P11A to R3-U1-P9A

R4-IB3-P11B to R3-U1-P10A

5 meters

R4 IB2 within Rack 4

R4-IB2-P8A to R4-U1-P3B

R4-IB2-P8B to R4-U1-P4B

3 meters

R4 IB2 to Rack 1

R4-IB2-P9A to R1-U1-P5B

R4-IB2-P9B to R1-U1-P6B

10 meters

R4 IB2 to Rack 2

R4-IB2-P10A to R2-U1-P7B

R4-IB2-P10B to R2-U1-P8B

5 meters

R4 IB2 to Rack 3

R4-IB2-P11A to R3-U1-P9B

R4-IB2-P11B to R3-U1-P10B

5 meters

E.6 Five-Rack Cabling

Table E-12 shows the cable connections for the first spine switch (R1-U1) when five full racks are cabled together.

Table E-12 Leaf Switch Connections for Rack 1 in a Five-Rack System

Leaf Switch Connection Cable Length

R1 IB3 within Rack 1

R1-IB3-P8A to R1-U1-P3A

R1-IB3-P8B to R1-U1-P4A

3 meters

R1 IB3 to Rack 2

R1-IB3-P9A to R2-U1-P5A

R1-IB3-P9B to R2-U1-P6A

5 meters

R1 IB3 to Rack 3

R1-IB3-P10A to R3-U1-P7A

R1-IB3-P10B to R3-U1-P8A

5 meters

R1 IB3 to Rack 4

R1-IB3-P11A to R4-U1-P9A

10 meters

R1 IB3 to Rack 5

R1-IB3-P11B to R5-U1-P10A

10 meters

R1 IB2 within Rack 1

R1-IB2-P8A to R1-U1-P3B

R1-IB2-P8B to R1-U1-P4B

3 meters

R1 IB2 to Rack 2

R1-IB2-P9A to R2-U1-P5B

R1-IB2-P9B to R2-U1-P6B

5 meters

R1 IB2 to Rack 3

R1-IB2-P10A to R3-U1-P7B

R1-IB2-P10B to R3-U1-P8B

5 meters

R1 IB2 to Rack 4

R1-IB2-P11A to R4-U1-P9B

10 meters

R1 IB2 to Rack 5

R1-IB2-P11B to R5-U1-P10B

10 meters

Table E-13 shows the cable connections for the second spine switch (R2-U1) when five full racks are cabled together.

Table E-13 Leaf Switch Connections for Rack 2 in a Five-Rack System

Leaf Switch Connection Cable Length

R2 IB3 within Rack 2

R2-IB3-P8A to R2-U1-P3A

R2-IB3-P8B to R2-U1-P4A

3 meters

R2 IB3 to Rack 1

R2-IB3-P11B to R1-U1-P10A

5 meters

R2 IB3 to Rack 3

R2-IB3-P9A to R3-U1-P5A

R2-IB3-P9B to R3-U1-P6A

5 meters

R2 IB3 to Rack 4

R2-IB3-P10A to R4-U1-P7A

R2-IB3-P10B to R4-U1-P8A

5 meters

R2 IB3 to Rack 5

R2-IB3-P11A to R5-U1-P9A

10 meters

R2 IB2 within Rack 2

R2-IB2-P8A to R2-U1-P3B

R2-IB2-P8B to R2-U1-P4B

3 meters

R2 IB2 to Rack 1

R2-IB2-P11B to R1-U1-P10B

5 meters

R2 IB2 to Rack 3

R2-IB2-P9A to R3-U1-P5B

R2-IB2-P9B to R3-U1-P6B

5 meters

R2 IB2 to Rack 4

R2-IB2-P10A to R4-U1-P7B

R2-IB2-P10B to R4-U1-P8B

5 meters

R2 IB2 to Rack 5

R2-IB2-P11A to R5-U1-P9B

10 meters

Table E-14 shows the cable connections for the third spine switch (R3-U1) when five full racks are cabled together.

Table E-14 Leaf Switch Connections for Rack 3 in a Five-Rack System

Leaf Switch Connection Cable Length

R3 IB3 within Rack 3

R3-IB3-P8A to R3-U1-P3A

R3-IB3-P8B to R3-U1-P4A

3 meters

R3 IB3 to Rack 1

R3-IB3-P11A to R1-U1-P9A

5 meters

R3 IB3 to Rack 2

R3-IB3-P11B to R2-U1-P10A

5 meters

R3 IB3 to Rack 4

R3-IB3-P9A to R4-U1-P5A

R3-IB3-P9B to R4-U1-P6A

5 meters

R3 IB3 to Rack 5

R3-IB3-P10A to R5-U1-P7A

R3-IB3-P10B to R5-U1-P8A

5 meters

R3 IB2 within Rack 3

R3-IB2-P8A to R3-U1-P3B

R3-IB2-P8B to R3-U1-P4B

3 meters

R3 IB2 to Rack 1

R3-IB2-P11A to R1-U1-P9B

5 meters

R3 IB2 to Rack 2

R3-IB2-P11B to R2-U1-P10B

5 meters

R3 IB2 to Rack 4

R3-IB2-P9A to R4-U1-P5B

R3-IB2-P9B to R4-U1-P6B

5 meters

R3 IB2 to Rack 5

R3-IB2-P10A to R5-U1-P7B

R3-IB2-P10B to R5-U1-P8B

5 meters

Table E-15 shows the cable connections for the fourth spine switch (R4-U1) when five full racks are cabled together.

Table E-15 Leaf Switch Connections for Rack 4 in a Five-Rack System

Leaf Switch Connection Cable Length

R4 IB3 within Rack 4

R4-IB3-P8A to R4-U1-P3A

R4-IB3-P8B to R4-U1-P4A

3 meters

R4 IB3 to Rack 1

R4-IB3-P10A to R1-U1-P7A

R4-IB3-P10B to R1-U1-P8A

10 meters

R4 IB3 to Rack 2

R4-IB3-P11A to R2-U1-P9A

5 meters

R4 IB3 to Rack 3

R4-IB3-P11B to R3-U1-P10A

5 meters

R4 IB3 to Rack 5

R4-IB3-P9A to R5-U1-P5A

R4-IB3-P9B to R5-U1-P6A

5 meters

R4 IB2 within Rack 4

R4-IB2-P8A to R4-U1-P3B

R4-IB2-P8B to R4-U1-P4B

3 meters

R4 IB2 to Rack 1

R4-IB2-P10A to R1-U1-P7B

R4-IB2-P10B to R1-U1-P8B

10 meters

R4 IB2 to Rack 2

R4-IB2-P11A to R2-U1-P9B

5 meters

R4 IB2 to Rack 3

R4-IB2-P11B to R3-U1-P10B

5 meters

R4 IB2 to Rack 5

R4-IB2-P9A to R5-U1-P5B

R4-IB2-P9B to R5-U1-P6B

5 meters

Table E-16 shows the cable connections for the fifth spine switch (R5-U1) when five full racks are cabled together.

Table E-16 Leaf Switch Connections for Rack 5 in a Five-Rack System

Leaf Switch Connection Cable Length

R5 IB3 within Rack 5

R5-IB3-P8A to R5-U1-P3A

R5-IB3-P8B to R5-U1-P4A

3 meters

R5 IB3 to Rack 1

R5-IB3-P9A to R1-U1-P5A

R5-IB3-P9B to R1-U1-P6A

10 meters

R5 IB3 to Rack 2

R5-IB3-P10A to R2-U1-P7A

R5-IB3-P10B to R2-U1-P8A

10 meters

R5 IB3 to Rack 3

R5-IB3-P11A to R3-U1-P9A

5 meters

R5 IB3 to Rack 4

R5-IB3-P11B to R4-U1-P10A

5 meters

R5 IB2 within Rack 5

R5-IB2-P8A to R5-U1-P3B

R5-IB2-P8B to R5-U1-P4B

3 meters

R5 IB2 to Rack 1

R5-IB2-P9A to R1-U1-P5B

R5-IB2-P9B to R1-U1-P6B

10 meters

R5 IB2 to Rack 2

R5-IB2-P10A to R2-U1-P7B

R5-IB3-P10B to R2-U1-P8B

10 meters

R5 IB2 to Rack 3

R5-IB2-P11A to R3-U1-P9B

5 meters

R5 IB2 to Rack 4

R5-IB2-P11B to R4-U1-P10B

5 meters

E.7 Six-Rack Cabling

Table E-17 shows the cable connections for the first spine switch (R1-U1) when six full racks are cabled together.

Table E-17 Leaf Switch Connections for Rack 1 in a Six-Rack System

Leaf Switch Connection Cable Length

R1 IB3 within Rack 1

R1-IB3-P8A to R1-U1-P3A

R1-IB3-P8B to R1-U1-P4A

3 meters

R1 IB3 to Rack 2

R1-IB3-P9A to R2-U1-P5A

R1-IB3-P9B to R2-U1-P6A

5 meters

R1 IB3 to Rack 3

R1-IB3-P10A to R3-U1-P7A

5 meters

R1 IB3 to Rack 4

R1-IB3-P10B to R4-U1-P8A

10 meters

R1 IB3 to Rack 5

R1-IB3-P11A to R5-U1-P9A

10 meters

R1 IB3 to Rack 6

R1-IB3-P11B to R6-U1-P10A

10 meters

R1 IB2 within Rack 1

R1-IB2-P8A to R1-U1-P3B

R1-IB2-P8B to R1-U1-P4B

3 meters

R1 IB2 to Rack 2

R1-IB2-P9A to R2-U1-P5B

R1-IB2-P9B to R2-U1-P6B

5 meters

R1 IB2 to Rack 3

R1-IB2-P10A to R3-U1-P7B

5 meters

R1 IB2 to Rack 4

R1-IB2-P10B to R4-U1-P8B

10 meters

R1 IB2 to Rack 5

R1-IB2-P11A to R5-U1-P9B

10 meters

R1 IB2 to Rack 6

R1-IB2-P11B to R6-U1-P10B

10 meters

Table E-18 shows the cable connections for the second spine switch (R2-U1) when six full racks are cabled together.

Table E-18 Leaf Switch Connections for Rack 2 in a Six-Rack System

Leaf Switch Connection Cable Length

R2 IB3 within Rack 2

R2-IB3-P8A to R2-U1-P3A

R2-IB3-P8B to R2-U1-P4A

3 meters

R2 IB3 to Rack 1

R2-IB3-P11B to R1-U1-P10A

5 meters

R2 IB3 to Rack 3

R2-IB3-P9A to R3-U1-P5A

R2-IB3-P9B to R3-U1-P6A

5 meters

R2 IB3 to Rack 4

R2-IB3-P10A to R4-U1-P7A

5 meters

R2 IB3 to Rack 5

R2-IB3-P10B to R5-U1-P8A

10 meters

R2 IB3 to Rack 6

R2-IB3-P11Ato R6-U1-P9A

10 meters

R2 IB2 within Rack 2

R2-IB2-P8A to R2-U1-P3B

R2-IB2-P8B to R2-U1-P4B

3 meters

R2 IB2 to Rack 1

R2-IB2-P11B to R1-U1-P10B

5 meters

R2 IB2 to Rack 3

R2-IB2-P9A to R3-U1-P5B

R2-IB2-P9B to R3-U1-P6B

5 meters

R2 IB2 to Rack 4

R2-IB2-P10A to R4-U1-P7B

5 meters

R2 IB2 to Rack 5

R2-IB2-P10B to R5-U1-P8B

10 meters

R2 IB2 to Rack 6

R2-IB2-P11Ato R6-U1-P9B

10 meters

Table E-19 shows the cable connections for the third spine switch (R3-U1) when six full racks are cabled together.

Table E-19 Leaf Switch Connections for Rack 3 in a Six-Rack System

Leaf Switch Connection Cable Length

R3 IB3 within Rack 3

R3-IB3-P8A to R3-U1-P3A

R3-IB3-P8B to R3-U1-P4A

3 meters

R3 IB3 to Rack 1

R3-IB3-P11A to R1-U1-P9A

5 meters

R3 IB3 to Rack 2

R3-IB3-P11B to R2-U1-P10A

5 meters

R3 IB3 to Rack 4

R3-IB3-P9A to R4-U1-P5A

R3-IB3-P9B to R4-U1-P6A

5 meters

R3 IB3 to Rack 5

R3-IB3-P10A to R5-U1-P7A

5 meters

R3 IB3 to Rack 6

R3-IB3-P10B to R6-U1-P8A

10 meters

R3 IB2 within Rack 3

R3-IB2-P8A to R3-U1-P3B

R3-IB2-P8B to R3-U1-P4B

3 meters

R3 IB2 to Rack 1

R3-IB2-P11A to R1-U1-P9B

5 meters

R3 IB2 to Rack 2

R3-IB2-P11B to R2-U1-P10B

5 meters

R3 IB2 to Rack 4

R3-IB2-P9A to R4-U1-P5B

R3-IB2-P9B to R4-U1-P6B

5 meters

R3 IB2 to Rack 5

R3-IB2-P10A to R5-U1-P7B

5 meters

R3 IB2 to Rack 6

R3-IB2-P10B to R6-U1-P8B

10 meters

Table E-20 shows the cable connections for the fourth spine switch (R4-U1) when six full racks are cabled together.

Table E-20 Leaf Switch Connections for Rack 4 in a Six-Rack System

Leaf Switch Connection Cable Length

R4 IB3 within Rack 4

R4-IB3-P8A to R4-U1-P3A

R4-IB3-P8B to R4-U1-P4A

3 meters

R4 IB3 to Rack 1

R4-IB3-P10B to R1-U1-P8A

10 meters

R4 IB3 to Rack 2

R4-IB3-P11A to R2-U1-P9A

5 meters

R4 IB3 to Rack 3

R4-IB3-P11B to R3-U1-P10A

5 meters

R4 IB3 to Rack 5

R4-IB3-P9A to R5-U1-P5A

R4-IB3-P9B to R5-U1-P6A

5 meters

R4 IB3 to Rack 6

R4-IB3-P10A to R6-U1-P7A

5 meters

R4 IB2 within Rack 4

R4-IB2-P8A to R4-U1-P3B

R4-IB2-P8B to R4-U1-P4B

3 meters

R4 IB2 to Rack 1

R4-IB2-P10B to R1-U1-P8B

10 meters

R4 IB2 to Rack 2

R4-IB2-P11A to R2-U1-P9B

5 meters

R4 IB2 to Rack 3

R4-IB2-P11B to R3-U1-P10B

5 meters

R4 IB2 to Rack 5

R4-IB2-P9A to R5-U1-P5B

R4-IB2-P9B to R5-U1-P6B

5 meters

R4 IB2 to Rack 6

R4-IB2-P10A to R6-U1-P7B

5 meters

Table E-21 shows the cable connections for the fifth spine switch (R5-U1) when six full racks are cabled together.

Table E-21 Leaf Switch Connections for Rack 5 in a Six-Rack System

Leaf Switch Connection Cable Length

R5 IB3 within Rack 5

R5-IB3-P8A to R5-U1-P3A

R5-IB3-P8B to R5-U1-P4A

3 meters

R5 IB3 to Rack 1

R5-IB3-P10A to R1-U1-P7A

10 meters

R5 IB3 to Rack 2

R5-IB3-P10B to R2-U1-P8A

10 meters

R5 IB3 to Rack 3

R5-IB3-P11A to R3-U1-P9A

5 meters

R5 IB3 to Rack 4

R5-IB3-P11B to R4-U1-P10A

5 meters

R5 IB3 to Rack 6

R5-IB3-P9A to R6-U1-P5A

R5-IB3-P9B to R6-U1-P6A

5 meters

R5 IB2 within Rack 5

R5-IB2-P8A to R5-U1-P3B

R5-IB2-P8B to R5-U1-P4B

3 meters

R5 IB2 to Rack 1

R5-IB2-P10A to R1-U1-P7B

10 meters

R5 IB2 to Rack 2

R5-IB3-P10B to R2-U1-P8B

10 meters

R5 IB2 to Rack 3

R5-IB2-P11A to R3-U1-P9B

5 meters

R5 IB2 to Rack 4

R5-IB2-P11B to R4-U1-P10B

5 meters

R5 IB2 to Rack 6

R5-IB2-P9A to R6-U1-P5B

R5-IB2-P9B to R6-U1-P6B

5 meters

Table E-22 shows the cable connections for the sixth spine switch (R6-U1) when six full racks are cabled together.

Table E-22 Leaf Switch Connections for Rack 6 in a Six-Rack System

Leaf Switch Connection Cable Length

R6 IB3 within Rack 6

R6-IB3-P8A to R6-U1-P3A

R6-IB3-P8B to R6-U1-P4A

3 meters

R6 IB3 to Rack 1

R6-IB3-P9A to R1-U1-P5A

R6-IB3-P9B to R1-U1-P6A

10 meters

R6 IB3 to Rack 2

R6-IB3-P10A to R2-U1-P7A

10 meters

R6 IB3 to Rack 3

R6-IB3-P10B to R3-U1-P8A

10 meters

R6 IB3 to Rack 4

R6-IB3-P11A to R4-U1-P9A

5 meters

R6 IB3 to Rack 5

R6-IB3-P11B to R5-U1-P10A

5 meters

R6 IB2 within Rack 6

R6-IB2-P8A to R6-U1-P3B

R6-IB2-P8B to R6-U1-P4B

3 meters

R6 IB2 to Rack 1

R6-IB2-P9A to R1-U1-P5B

R6-IB2-P9B to R1-U1-P6B

10 meters

R6 IB2 to Rack 2

R6-IB3-P10A to R2-U1-P7B

10 meters

R6 IB2 to Rack 3

R6-IB2-P10B to R3-U1-P8B

10 meters

R6 IB2 to Rack 4

R6-IB2-P11A to R4-U1-P9B

5 meters

R6 IB2 to Rack 5

R6-IB2-P11B to R5-U1-P10B

5 meters

E.8 Seven-Rack Cabling

Table E-23 shows the cable connections for the first spine switch (R1-U1) when seven racks are cabled together.

Table E-23 Leaf Switch Connections for Rack 1 in a Seven-Rack System

Leaf Switch Connection Cable Length

R1 IB3 within Rack 1

R1-IB3-P8A to R1-U1-P3A

R1-IB3-P8B to R1-U1-P4A

3 meters

R1 IB3 to Rack 2

R1-IB3-P9A to R2-U1-P5A

5 meters

R1 IB3 to Rack 3

R1-IB3-P9B to R3-U1-P6A

5 meters

R1 IB3 to Rack 4

R1-IB3-P10A to R4-U1-P7A

10 meters

R1 IB3 to Rack 5

R1-IB3-P10B to R5-U1-P8A

10 meters

R1 IB3 to Rack 6

R1-IB3-P11A to R6-U1-P9A

10 meters

R1 IB3 to Rack 7

R1-IB3-P11B to R7-U1-P10A

10 meters

R1 IB2 within Rack 1

R1-IB2-P8A to R1-U1-P3B

R1-IB2-P8B to R1-U1-P4B

3 meters

R1 IB2 to Rack 2

R1-IB2-P9A to R2-U1-P5B

5 meters

R1 IB2 to Rack 3

R1-IB2-P9B to R3-U1-P6B

5 meters

R1 IB2 to Rack 4

R1-IB2-P10A to R4-U1-P7B

10 meters

R1 IB2 to Rack 5

R1-IB2-P10B to R5-U1-P8B

10 meters

R1 IB2 to Rack 6

R1-IB2-P11A to R6-U1-P9B

10 meters

R1 IB2 to Rack 7

R1-IB2-P11B to R7-U1-P10B

10 meters

Table E-24 shows the cable connections for the second spine switch (R2-U1) when seven full racks are cabled together.

Table E-24 Leaf Switch Connections for Rack 2 in a Seven-Rack System

Leaf Switch Connection Cable Length

R2 IB3 within Rack 2

R2-IB3-P8A to R2-U1-P3A

R2-IB3-P8B to R2-U1-P4A

3 meters

R2 IB3 to Rack 1

R2-IB3-P11B to R1-U1-P10A

5 meters

R2 IB3 to Rack 3

R2-IB3-P9A to R3-U1-P5A

5 meters

R2 IB3 to Rack 4

R2-IB3-P9B to R4-U1-P6A

5 meters

R2 IB3 to Rack 5

R2-IB3-P10A to R5-U1-P7A

10 meters

R2 IB3 to Rack 6

R2-IB3-P10B to R6-U1-P8A

10 meters

R2 IB3 to Rack 7

R2-IB3-P11A to R7-U1-P9A

10 meters

R2 IB2 within Rack 2

R2-IB2-P8A to R2-U1-P3B

R2-IB2-P8B to R2-U1-P4B

3 meters

R2 IB2 to Rack 1

R2-IB2-P11B to R1-U1-P10B

5 meters

R2 IB2 to Rack 3

R2-IB2-P9A to R3-U1-P5B

5 meters

R2 IB2 to Rack 4

R2-IB2-P9B to R4-U1-P6B

5 meters

R2 IB2 to Rack 5

R2-IB2-P10A to R5-U1-P7B

10 meters

R2 IB2 to Rack 6

R2-IB2-P10Bto R6-U1-P8B

10 meters

R2 IB2 to Rack 7

R2-IB2-P11A to R7-U1-P9B

10 meters

Table E-25 shows the cable connections for the third spine switch (R3-U1) when seven full racks are cabled together.

Table E-25 Leaf Switch Connections for Rack 3 in a Seven-Rack System

Leaf Switch Connection Cable Length

R3 IB3 within Rack 3

R3-IB3-P8A to R3-U1-P3A

R3-IB3-P8B to R3-U1-P4A

3 meters

R3 IB3 to Rack 1

R3-IB3-P11A to R1-U1-P9A

5 meters

R3 IB3 to Rack 2

R3-IB3-P11B to R2-U1-P10A

5 meters

R3 IB3 to Rack 4

R3-IB3-P9A to R4-U1-P5A

5 meters

R3 IB3 to Rack 5

R3-IB3-P9B to R5-U1-P6A

5 meters

R3 IB3 to Rack 6

R3-IB3-P10A to R6-U1-P7A

10 meters

R3 IB3 to Rack 7

R3-IB3-P10B to R7-U1-P8A

10 meters

R3 IB2 within Rack 3

R3-IB2-P8A to R3-U1-P3B

R3-IB2-P8B to R3-U1-P4B

3 meters

R3 IB2 to Rack 1

R3-IB2-P11A to R1-U1-P9B

5 meters

R3 IB2 to Rack 2

R3-IB2-P11B to R2-U1-P10B

5 meters

R3 IB2 to Rack 4

R3-IB2-P9A to R4-U1-P5B

5 meters

R3 IB2 to Rack 5

R3-IB2-P9B to R5-U1-P6B

5 meters

R3 IB2 to Rack 6

R3-IB2-P10A to R6-U1-P7B

10 meters

R3 IB2 to Rack 7

R3-IB2-P10B to R7-U1-P8B

10 meters

Table E-26 shows the cable connections for the fourth spine switch (R4-U1) when seven full racks are cabled together.

Table E-26 Leaf Switch Connections for Rack 4 in a Seven-Rack System

Leaf Switch Connection Cable Length

R4 IB3 within Rack 4

R4-IB3-P8A to R4-U1-P3A

R4-IB3-P8B to R4-U1-P4A

3 meters

R4 IB3 to Rack 1

R4-IB3-P10B to R1-U1-P8A

10 meters

R4 IB3 to Rack 2

R4-IB3-P11A to R2-U1-P9A

5 meters

R4 IB3 to Rack 3

R4-IB3-P11B to R3-U1-P10A

5 meters

R4 IB3 to Rack 5

R4-IB3-P9A to R5-U1-P5A

5 meters

R4 IB3 to Rack 6

R4-IB3-P9B to R6-U1-P6A

5 meters

R4 IB3 to Rack 7

R4-IB3-P10A to R7-U1-P7A

10 meters

R4 IB2 within Rack 4

R4-IB2-P8A to R4-U1-P3B

R4-IB2-P8B to R4-U1-P4B

3 meters

R4 IB2 to Rack 1

R4-IB2-P10B to R1-U1-P8B

10 meters

R4 IB2 to Rack 2

R4-IB2-P11A to R2-U1-P9B

5 meters

R4 IB2 to Rack 3

R4-IB2-P11B to R3-U1-P10B

5 meters

R4 IB2 to Rack 5

R4-IB2-P9A to R5-U1-P5B

5 meters

R4 IB2 to Rack 6

R4-IB2-P9B to R6-U1-P6B

5 meters

R4 IB2 to Rack 7

R4-IB2-P10A to R7-U1-P7B

10 meters

Table E-27 shows the cable connections for the fifth spine switch (R5-U1) when seven full racks are cabled together.

Table E-27 Leaf Switch Connections for Rack 5 in a Seven-Rack System

Leaf Switch Connection Cable Length

R5 IB3 within Rack 5

R5-IB3-P8A to R5-U1-P3A

R5-IB3-P8B to R5-U1-P4A

3 meters

R5 IB3 to Rack 1

R5-IB3-P10A to R1-U1-P7A

10 meters

R5 IB3 to Rack 2

R5-IB3-P10B to R2-U1-P8A

10 meters

R5 IB3 to Rack 3

R5-IB3-P11A to R3-U1-P9A

5 meters

R5 IB3 to Rack 4

R5-IB3-P11B to R4-U1-P10A

5 meters

R5 IB3 to Rack 6

R5-IB3-P9A to R6-U1-P5A

5 meters

R5 IB3 to Rack 7

R5-IB3-P9B to R7-U1-P6A

5 meters

R5 IB2 within Rack 5

R5-IB2-P8A to R5-U1-P3B

R5-IB2-P8B to R5-U1-P4B

3 meters

R5 IB2 to Rack 1

R5-IB2-P10A to R1-U1-P7B

10 meters

R5 IB2 to Rack 2

R5-IB3-P10B to R2-U1-P8B

10 meters

R5 IB2 to Rack 3

R5-IB2-P11A to R3-U1-P9B

5 meters

R5 IB2 to Rack 4

R5-IB2-P11B to R4-U1-P10B

5 meters

R5 IB2 to Rack 6

R5-IB2-P9A to R6-U1-P5B

5 meters

R5 IB2 to Rack 7

R5-IB2-P9B to R7-U1-P6B

5 meters

Table E-28 shows the cable connections for the sixth spine switch (R6-U1) when seven full racks are cabled together.

Table E-28 Leaf Switch Connections for Rack 6 in a Seven-Rack System

Leaf Switch Connection Cable Length

R6 IB3 within Rack 6

R6-IB3-P8A to R6-U1-P3A

R6-IB3-P8B to R6-U1-P4A

3 meters

R6 IB3 to Rack 1

R6-IB3-P9B to R1-U1-P6A

10 meters

R6 IB3 to Rack 2

R6-IB3-P10A to R2-U1-P7A

10 meters

R6 IB3 to Rack 3

R6-IB3-P10B to R3-U1-P8A

10 meters

R6 IB3 to Rack 4

R6-IB3-P11A to R4-U1-P9A

5 meters

R6 IB3 to Rack 5

R6-IB3-P11B to R5-U1-P10A

5 meters

R6 IB3 to Rack 7

R6-IB3-P9A to R7-U1-P5A

5 meters

R6 IB2 within Rack 6

R6-IB2-P8A to R6-U1-P3B

R6-IB2-P8B to R6-U1-P4B

3 meters

R6 IB2 to Rack 1

R6-IB2-P9B to R1-U1-P6B

10 meters

R6 IB2 to Rack 2

R6-IB3-P10A to R2-U1-P7B

10 meters

R6 IB2 to Rack 3

R6-IB2-P10B to R3-U1-P8B

10 meters

R6 IB2 to Rack 4

R6-IB2-P11A to R4-U1-P9B

5 meters

R6 IB2 to Rack 5

R6-IB2-P11B to R5-U1-P10B

5 meters

R6 IB2 to Rack 7

R6-IB3-P9A to R7-U1-P5B

5 meters

Table E-29 shows the cable connections for the seventh spine switch (R7-U1) when seven full racks are cabled together.

Table E-29 Leaf Switch Connections for Rack 7 in a Seven-Rack System

Leaf Switch Connection Cable Length

R7 IB3 within Rack 7

R7-IB3-P8A to R7-U1-P3A

R7-IB3-P8B to R7-U1-P4A

3 meters

R7 IB3 to Rack 1

R7-IB3-P9A to R1-U1-P5A

10 meters

R7 IB3 to Rack 2

R7-IB3-P9B to R2-U1-P6A

10 meters

R7 IB3 to Rack 3

R7-IB3-P10A to R3-U1-P7A

10 meters

R7 IB3 to Rack 4

R7-IB3-P10B to R4-U1-P8A

10 meters

R7 IB3 to Rack 5

R7-IB3-P11A to R5-U1-P9A

5 meters

R7 IB3 to Rack 6

R7-IB3-P11B to R6-U1-P10A

5 meters

R7 IB2 within Rack 7

R7-IB2-P8A to R7-U1-P3B

R7-IB2-P8B to R7-U1-P4B

3 meters

R7 IB2 to Rack 1

R7-IB2-P9A to R1-U1-P5B

10 meters

R7 IB2 to Rack 2

R7-IB3-P9B to R2-U1-P6B

10 meters

R7 IB2 to Rack 3

R7-IB2-P10A to R3-U1-P7B

10 meters

R7 IB2 to Rack 4

R7-IB2-P10B to R4-U1-P8B

10 meters

R7 IB2 to Rack 5

R7-IB2-P11A to R5-U1-P9B

5 meters

R7 IB2 to Rack 6

R7-IB3-P11B to R6-U1-P10B

5 meters

E.9 Eight-Rack Cabling

Table E-30 shows the cable connections for the first spine switch (R1-U1) when eight full racks are cabled together.

Table E-30 Leaf Switch Connections for Rack 1 in an Eight-Rack System

Leaf Switch Connection Cable Length

R1 IB3 within Rack 1

R1-IB3-P8A to R1-U1-P3A

3 meters

R1 IB3 to Rack 2

R1-IB3-P8B to R2-U1-P4A

5 meters

R1 IB3 to Rack 3

R1-IB3-P9A to R3-U1-P5A

5 meters

R1 IB3 to Rack 4

R1-IB3-P9B to R4-U1-P6A

10 meters

R1 IB3 to Rack 5

R1-IB3-P10A to R5-U1-P7A

10 meters

R1 IB3 to Rack 6

R1-IB3-P10B to R6-U1-P8A

10 meters

R1 IB3 to Rack 7

R1-IB3-P11A to R7-U1-P9A

10 meters

R1 IB3 to Rack 8

R1-IB3-P11B to R8-U1-P10A

10 meters

R1 IB2 within Rack 1

R1-IB2-P8A to R1-U1-P3B

3 meters

R1 IB2 to Rack 2

R1-IB2-P8B to R2-U1-P4B

5 meters

R1 IB2 to Rack 3

R1-IB2-P9A to R3-U1-P5B

5 meters

R1 IB2 to Rack 4

R1-IB2-P9B to R4-U1-P6B

10 meters

R1 IB2 to Rack 5

R1-IB2-P10A to R5-U1-P7B

10 meters

R1 IB2 to Rack 6

R1-IB2-P10B to R6-U1-P8B

10 meters

R1 IB2 to Rack 7

R1-IB2-P11A to R7-U1-P9B

10 meters

R1 IB2 to Rack 8

R1-IB2-P11B to R8-U1-P10B

10 meters

Table E-31 shows the cable connections for the second spine switch (R2-U1) when eight full racks are cabled together.

Table E-31 Leaf Switch Connections for Rack 2 in an Eight-Rack System

Leaf Switch Connection Cable Length

R2 IB3 within Rack 2

R2-IB3-P8A to R2-U1-P3A

3 meters

R2 IB3 to Rack 1

R2-IB3-P11B to R1-U1-P10A

5 meters

R2 IB3 to Rack 3

R2-IB3-P8B to R3-U1-P4A

5 meters

R2 IB3 to Rack 4

R2-IB3-P9A to R4-U1-P5A

5 meters

R2 IB3 to Rack 5

R2-IB3-P9B to R5-U1-P6A

10 meters

R2 IB3 to Rack 6

R2-IB3-P10A to R6-U1-P7A

10 meters

R2 IB3 to Rack 7

R2-IB3-P10B to R7-U1-P8A

10 meters

R2 IB3 to Rack 8

R2-IB3-P11A to R8-U1-P9A

10 meters

R2 IB2 within Rack 2

R2-IB2-P8A to R2-U1-P3B

3 meters

R2 IB2 to Rack 1

R2-IB2-P11B to R1-U1-P10B

5 meters

R2 IB2 to Rack 3

R2-IB2-P8B to R3-U1-P4B

5 meters

R2 IB2 to Rack 4

R2-IB2-P9A to R4-U1-P5B

5 meters

R2 IB2 to Rack 5

R2-IB2-P9B to R5-U1-P6B

10 meters

R2 IB2 to Rack 6

R2-IB2-P10A to R6-U1-P7B

10 meters

R2 IB2 to Rack 7

R2-IB2-P10B to R7-U1-P8B

10 meters

R2 IB2 to Rack 8

R2-IB2-P11A to R8-U1-P9B

10 meters

Table E-32 shows the cable connections for the third spine switch (R3-U1) when eight full racks are cabled together.

Table E-32 Leaf Switch Connections for Rack 3 in an Eight-Rack System

Leaf Switch Connection Cable Length

R3 IB3 within Rack 3

R3-IB3-P8A to R3-U1-P3A

3 meters

R3 IB3 to Rack 1

R3-IB3-P11A to R1-U1-P9A

5 meters

R3 IB3 to Rack 2

R3-IB3-P11B to R2-U1-P10A

5 meters

R3 IB3 to Rack 4

R3-IB3-P8B to R4-U1-P4A

5 meters

R3 IB3 to Rack 5

R3-IB3-P9A to R5-U1-P5A

5 meters

R3 IB3 to Rack 6

R3-IB3-P9B to R6-U1-P6A

10 meters

R3 IB3 to Rack 7

R3-IB3-P10A to R7-U1-P7A

10 meters

R3 IB3 to Rack 8

R3-IB3-P10B to R8-U1-P8A

10 meters

R3 IB2 within Rack 3

R3-IB2-P8A to R3-U1-P3B

3 meters

R3 IB2 to Rack 1

R3-IB2-P11A to R1-U1-P9B

5 meters

R3 IB2 to Rack 2

R3-IB2-P11B to R2-U1-P10B

5 meters

R3 IB2 to Rack 4

R3-IB2-P8B to R4-U1-P4B

5 meters

R3 IB2 to Rack 5

R3-IB2-P9A to R5-U1-P5B

5 meters

R3 IB2 to Rack 6

R3-IB2-P9B to R6-U1-P6B

10 meters

R3 IB2 to Rack 7

R3-IB2-P10A to R7-U1-P7B

10 meters

R3 IB2 to Rack 8

R3-IB2-P10B to R8-U1-P8B

10 meters

Table E-33 shows the cable connections for the fourth spine switch (R4-U1) when eight full racks are cabled together.

Table E-33 Leaf Switch Connections for Rack 4 in an Eight-Rack System

Leaf Switch Connection Cable Length

R4 IB3 within Rack 4

R4-IB3-P8A to R4-U1-P3A

3 meters

R4 IB3 to Rack 1

R4-IB3-P10B to R1-U1-P8A

10 meters

R4 IB3 to Rack 2

R4-IB3-P11A to R2-U1-P9A

5 meters

R4 IB3 to Rack 3

R4-IB3-P11B to R3-U1-P10A

5 meters

R4 IB3 to Rack 5

R4-IB3-P8B to R5-U1-P4A

5 meters

R4 IB3 to Rack 6

R4-IB3-P9A to R6-U1-P5A

5 meters

R4 IB3 to Rack 7

R4-IB3-P9B to R7-U1-P6A

10 meters

R4 IB3 to Rack 8

R4-IB3-P10A to R8-U1-P7A

10 meters

R4 IB2 within Rack 4

R4-IB2-P8A to R4-U1-P3B

3 meters

R4 IB2 to Rack 1

R4-IB2-P10B to R1-U1-P8B

10 meters

R4 IB2 to Rack 2

R4-IB2-P11A to R2-U1-P9B

5 meters

R4 IB2 to Rack 3

R4-IB2-P11B to R3-U1-P10B

5 meters

R4 IB2 to Rack 5

R4-IB2-P8B to R5-U1-P4B

5 meters

R4 IB2 to Rack 6

R4-IB2-P9A to R6-U1-P5B

5 meters

R4 IB2 to Rack 7

R4-IB2-P9B to R7-U1-P6B

10 meters

R4 IB2 to Rack 8

R4-IB2-P10A to R8-U1-P7B

10 meters

Table E-34 shows the cable connections for the fifth spine switch (R5-U1) when eight full racks are cabled together.

Table E-34 Leaf Switch Connections for Rack 5 in a Eight-Rack System

Leaf Switch Connection Cable Length

R5 IB3 within Rack 5

R5-IB3-P8A to R5-U1-P3A

3 meters

R5 IB3 to Rack 1

R5-IB3-P10A to R1-U1-P7A

10 meters

R5 IB3 to Rack 2

R5-IB3-P10B to R2-U1-P8A

10 meters

R5 IB3 to Rack 3

R5-IB3-P11A to R3-U1-P9A

5 meters

R5 IB3 to Rack 4

R5-IB3-P11B to R4-U1-P10A

5 meters

R5 IB3 to Rack 6

R5-IB3-P8B to R6-U1-P4A

5 meters

R5 IB3 to Rack 7

R5-IB3-P9A to R7-U1-P5A

5 meters

R5 IB3 to Rack 8

R5-IB3-P9B to R8-U1-P6A

10 meters

R5 IB2 within Rack 5

R5-IB2-P8A to R5-U1-P3B

3 meters

R5 IB2 to Rack 1

R5-IB2-P10A to R1-U1-P7B

10 meters

R5 IB2 to Rack 2

R5-IB3-P10B to R2-U1-P8B

10 meters

R5 IB2 to Rack 3

R5-IB2-P11A to R3-U1-P9B

5 meters

R5 IB2 to Rack 4

R5-IB2-P11B to R4-U1-P10B

5 meters

R5 IB2 to Rack 6

R5-IB2-P8B to R6-U1-P4B

5 meters

R5 IB2 to Rack 7

R5-IB2-P9A to R7-U1-P5B

5 meters

R5 IB2 to Rack 8

R5-IB2-P9B to R8-U1-P6B

10 meters

Table E-35 shows the cable connections for the sixth spine switch (R6-U1) when eight full racks are cabled together.

Table E-35 Leaf Switch Connections for Rack 6 in a Eight-Rack System

Leaf Switch Connection Cable Length

R6 IB3 within Rack 6

R6-IB3-P8A to R6-U1-P3A

3 meters

R6 IB3 to Rack 1

R6-IB3-P9B to R1-U1-P6A

10 meters

R6 IB3 to Rack 2

R6-IB3-P10A to R2-U1-P7A

10 meters

R6 IB3 to Rack 3

R6-IB3-P10B to R3-U1-P8A

10 meters

R6 IB3 to Rack 4

R6-IB3-P11A to R4-U1-P9A

5 meters

R6 IB3 to Rack 5

R6-IB3-P11B to R5-U1-P10A

5 meters

R6 IB3 to Rack 7

R6-IB3-P8B to R7-U1-P4A

5 meters

R6 IB3 to Rack 8

R6-IB3-P9A to R8-U1-P5A

5 meters

R6 IB2 within Rack 6

R6-IB2-P8A to R6-U1-P3B

3 meters

R6 IB2 to Rack 1

R6-IB2-P9B to R1-U1-P6B

10 meters

R6 IB2 to Rack 2

R6-IB3-P10A to R2-U1-P7B

10 meters

R6 IB2 to Rack 3

R6-IB2-P10B to R3-U1-P8B

10 meters

R6 IB2 to Rack 4

R6-IB2-P11A to R4-U1-P9B

5 meters

R6 IB2 to Rack 5

R6-IB2-P11B to R5-U1-P10B

5 meters

R6 IB2 to Rack 7

R6-IB3-P8B to R7-U1-P4B

5 meters

R6 IB2 to Rack 8

R6-IB2-P9A to R8-U1-P5B

5 meters

Table E-36 shows the cable connections for the seventh spine switch (R7-U1) when eight full racks are cabled together.

Table E-36 Leaf Switch Connections for Rack 7 in a Eight-Rack System

Leaf Switch Connection Cable Length

R7 IB3 within Rack 7

R7-IB3-P8A to R7-U1-P3A

3 meters

R7 IB3 to Rack 1

R7-IB3-P9A to R1-U1-P5A

10 meters

R7 IB3 to Rack 2

R7-IB3-P9B to R2-U1-P6A

10 meters

R7 IB3 to Rack 3

R7-IB3-P10A to R3-U1-P7A

10 meters

R7 IB3 to Rack 4

R7-IB3-P10B to R4-U1-P8A

10 meters

R7 IB3 to Rack 5

R7-IB3-P11A to R5-U1-P9A

5 meters

R7 IB3 to Rack 6

R7-IB3-P11B to R6-U1-P10A

5 meters

R7 IB3 to Rack 8

R7-IB3-P8B to R8-U1-P4A

5 meters

R7 IB2 within Rack 7

R7-IB2-P8A to R7-U1-P3B

3 meters

R7 IB2 to Rack 1

R7-IB2-P9A to R1-U1-P5B

10 meters

R7 IB2 to Rack 2

R7-IB3-P9B to R2-U1-P6B

10 meters

R7 IB2 to Rack 3

R7-IB2-P10A to R3-U1-P7B

10 meters

R7 IB2 to Rack 4

R7-IB2-P10B to R4-U1-P8B

10 meters

R7 IB2 to Rack 5

R7-IB2-P11A to R5-U1-P9B

5 meters

R7 IB2 to Rack 6

R7-IB3-P11B to R6-U1-P10B

5 meters

R7 IB2 to Rack 8

R7-IB3-P8B to R8-U1-P4B

5 meters

Table E-37 shows the cable connections for the eighth spine switch (R8-U1) when eight full racks are cabled together.

Table E-37 Leaf Switch Connections for Rack 8 in a Eight-Rack System

Leaf Switch Connection Cable Length

R8 IB3 within Rack 8

R8-IB3-P8A to R8-U1-P3A

3 meters

R8 IB3 to Rack 1

R8-IB3-P8B to R1-U1-P4A

10 meters

R8 IB3 to Rack 2

R8-IB3-P9A to R2-U1-P5A

10 meters

R8 IB3 to Rack 3

R8-IB3-P9B to R3-U1-P6A

10 meters

R8 IB3 to Rack 4

R8-IB3-P10A to R4-U1-P7A

10 meters

R8 IB3 to Rack 5

R8-IB3-P10B to R5-U1-P8A

10 meters

R8 IB3 to Rack 6

R8-IB3-P11A to R6-U1-P9A

5 meters

R8 IB3 to Rack 7

R8-IB3-P11B to R7-U1-P10A

5 meters

R8 IB2 within Rack 8

R8-IB2-P8A to R8-U1-P3B

3 meters

R8 IB2 to Rack 1

R8-IB2-P8B to R1-U1-P4B

10 meters

R8 IB2 to Rack 2

R8-IB3-P9A to R2-U1-P5B

10 meters

R8 IB2 to Rack 3

R8-IB2-P9B to R3-U1-P6B

10 meters

R8 IB2 to Rack 4

R8-IB2-P10A to R4-U1-P7B

10 meters

R8 IB2 to Rack 5

R8-IB2-P10B to R5-U1-P8B

10 meters

R8 IB2 to Rack 6

R8-IB3-P11A to R6-U1-P9B

5 meters

R8 IB2 to Rack 7

R8-IB3-P11B to R7-U1-P10B

5 meters

E.10 Nine-Rack Cabling

Table E-38 shows the cable connections for the switches when nine full racks are cabled together. The cabling among racks 1 through 8 does not change.

Table E-38 Leaf Switch Connections for Rack 9

Leaf Switch Connection

R9 IB3 to Rack 1

R9-IB3-P8B to R1-U1-P11A

R9 IB3 to Rack 2

R9-IB3-P9A to R2-U1-P11A

R9 IB3 to Rack 3

R9-IB3-P9B to R3-U1-P11A

R9 IB3 to Rack 4

R9-IB3-P10A to R4-U1-P11A

R9 IB3 to Rack 5

R9-IB3-P10B to R5-U1-P11A

R9 IB3 to Rack 6

R9-IB3-P11A to R6-U1-P11A

R9 IB3 to Rack 7

R9-IB3-P11B to R7-U1-P11A

R9 IB3 to Rack 8

R9-IB3-P9A to R8-U1-P11A

R9 IB2 to Rack 1

R9-IB2-P8B to R1-U1-P11B

R9 IB2 to Rack 2

R9-IB2-P9A to R2-U1-P11B

R9 IB2 to Rack 3

R9-IB2-P9B to R3-U1-P11B

R9 IB2 to Rack 4

R9-IB2-P10A to R4-U1-P11B

R9 IB2 to Rack 5

R9-IB2-P10B to R5-U1-P11B

R9 IB2 to Rack 6

R9-IB2-P11A to R6-U1-P11B

R9 IB2 to Rack 7

R9-IB2-P11B to R7-U1-P11B

R9 IB2 to Rack 8

R9-IB2-P8A to R8-U1-P11B

E.11 10-Rack Cabling

Table E-39 shows the cable connections for the switches when 10 full racks are cabled together. The cabling among racks 1 through 8 does not change.

Table E-39 Leaf Switch Connections for Rack 10

Leaf Switch Connection

R10 IB3 to Rack 1

R10-IB3-P8B to R1-U1-P12A

R10 IB3 to Rack 2

R10-IB3-P9A to R2-U1-P12A

R10 IB3 to Rack 3

R10-IB3-P9B to R3-U1-P12A

R10 IB3 to Rack 4

R10-IB3-P10A to R4-U1-P12A

R10 IB3 to Rack 5

R10-IB3-P10B to R5-U1-P12A

R10 IB3 to Rack 6

R10-IB3-P12A to R6-U1-P12A

R10 IB3 to Rack 7

R10-IB3-P12B to R7-U1-P12A

R10 IB3 to Rack 8

R10-IB3-P8A to R8-U1-P12A

R10 IB2 to Rack 1

R10-IB2-P8B to R1-U1-P12B

R10 IB2 to Rack 2

R10-IB2-P9A to R2-U1-P12B

R10 IB2 to Rack 3

R10-IB2-P9B to R3-U1-P12B

R10 IB2 to Rack 4

R10-IB2-P10A to R4-U1-P12B

R10 IB2 to Rack 5

R10-IB2-P10B to R5-U1-P12B

R10 IB2 to Rack 6

R10-IB2-P12A to R6-U1-P12B

R10 IB2 to Rack 7

R10-IB2-P12B to R7-U1-P12B

R10 IB2 to Rack 8

R10-IB2-P8A to R8-U1-P12B

E.12 11-Rack Cabling

Table E-40 shows the cable connections for the switches when 11 full racks are cabled together. The cabling among racks 1 through 8 does not change.

Table E-40 Leaf Switch Connections for Rack 11

Leaf Switch Connection

R11 IB3 to Rack 1

R11-IB3-P8B to R1-U1-P13A

R11 IB3 to Rack 2

R11-IB3-P9A to R2-U1-P13A

R11 IB3 to Rack 3

R11-IB3-P9B to R3-U1-P13A

R11 IB3 to Rack 4

R11-IB3-P10A to R4-U1-P13A

R11 IB3 to Rack 5

R11-IB3-P10B to R5-U1-P13A

R11 IB3 to Rack 6

R11-IB3-P13A to R6-U1-P13A

R11 IB3 to Rack 7

R11-IB3-P13B to R7-U1-P13A

R11 IB3 to Rack 8

R11-IB3-P8A to R8-U1-P13A

R11 IB2 to Rack 1

R11-IB2-P8B to R1-U1-P13B

R11 IB2 to Rack 2

R11-IB2-P9A to R2-U1-P13B

R11 IB2 to Rack 3

R11-IB2-P9B to R3-U1-P13B

R11 IB2 to Rack 4

R11-IB2-P10A to R4-U1-P13B

R11 IB2 to Rack 5

R11-IB2-P10B to R5-U1-P13B

R11 IB2 to Rack 6

R11-IB2-P13A to R6-U1-P13B

R11 IB2 to Rack 7

R11-IB2-P13B to R7-U1-P13B

R11 IB2 to Rack 8

R11-IB2-P8A to R8-U1-P13B

E.13 12-Rack Cabling

Table E-41 shows the cable connections for the switches when cabling twelve full racks together. The cabling between racks 1 through 8 does not change.

Table E-41 Leaf Switch Connections for Rack 12

Leaf Switch Connection

R12 IB3 to Rack 1

R12-IB3-P8B to R1-U1-P14A

R12 IB3 to Rack 2

R12-IB3-P9A to R2-U1-P14A

R12 IB3 to Rack 3

R12-IB3-P9B to R3-U1-P14A

R12 IB3 to Rack 4

R12-IB3-P10A to R4-U1-P14A

R12 IB3 to Rack 5

R12-IB3-P10B to R5-U1-P14A

R12 IB3 to Rack 6

R12-IB3-P14A to R6-U1-P14A

R12 IB3 to Rack 7

R12-IB3-P14B to R7-U1-P14A

R12 IB3 to Rack 8

R12-IB3-P8A to R8-U1-P14A

R12 IB2 to Rack 1

R12-IB2-P8B to R1-U1-P14B

R12 IB2 to Rack 2

R12-IB2-P9A to R2-U1-P14B

R12 IB2 to Rack 3

R12-IB2-P9B to R3-U1-P14B

R12 IB2 to Rack 4

R12-IB2-P10A to R4-U1-P14B

R12 IB2 to Rack 5

R12-IB2-P10B to R5-U1-P14B

R12 IB2 to Rack 6

R12-IB2-P14A to R6-U1-P14B

R12 IB2 to Rack 7

R12-IB2-P14B to R7-U1-P14B

R12 IB2 to Rack 8

R12-IB2-P8A to R8-U1-P14B

E.14 13-Rack Cabling

Table E-42 shows the cable connections for the switches when 13 full racks are cabled together. The cabling among racks 1 through 8 does not change.

Table E-42 Leaf Switch Connections for Rack 13

Leaf Switch Connection

R13 IB3 to Rack 1

R13-IB3-P8B to R1-U1-P15A

R13 IB3 to Rack 2

R13-IB3-P9A to R2-U1-P15A

R13 IB3 to Rack 3

R13-IB3-P9B to R3-U1-P15A

R13 IB3 to Rack 4

R13-IB3-P10A to R4-U1-P15A

R13 IB3 to Rack 5

R13-IB3-P10B to R5-U1-P15A

R13 IB3 to Rack 6

R13-IB3-P15A to R6-U1-P15A

R13 IB3 to Rack 7

R13-IB3-P15B to R7-U1-P15A

R13 IB3 to Rack 8

R13-IB3-P8A to R8-U1-P15A

R13 IB2 to Rack 1

R13-IB2-P8B to R1-U1-P15B

R13 IB2 to Rack 2

R13-IB2-P9A to R2-U1-P15B

R13 IB2 to Rack 3

R13-IB2-P9B to R3-U1-P15B

R13 IB2 to Rack 4

R13-IB2-P10A to R4-U1-P15B

R13 IB2 to Rack 5

R13-IB2-P10B to R5-U1-P15B

R13 IB2 to Rack 6

R13-IB2-P15A to R6-U1-P15B

R13 IB2 to Rack 7

R13-IB2-P15B to R7-U1-P15B

R13 IB2 to Rack 8

R13-IB2-P8A to R8-U1-P15B

E.15 14-Rack Cabling

Table E-43 shows the cable connections for the switches when cabling 14 racks together. The cabling among racks 1 through 8 does not change.

Table E-43 Leaf Switch Connections for Rack 14

Leaf Switch Connection

R14 IB3 to Rack 1

R14-IB3-P8B to R1-U1-P16A

R14 IB3 to Rack 2

R14-IB3-P9A to R2-U1-P16A

R14 IB3 to Rack 3

R14-IB3-P9B to R3-U1-P16A

R14 IB3 to Rack 4

R14-IB3-P10A to R4-U1-P16A

R14 IB3 to Rack 5

R14-IB3-P10B to R5-U1-P16A

R14 IB3 to Rack 6

R14-IB3-P16A to R6-U1-P16A

R14 IB3 to Rack 7

R14-IB3-P16B to R7-U1-P16A

R14 IB3 to Rack 8

R14-IB3-P8A to R8-U1-P16A

R14 IB2 to Rack 1

R14-IB2-P8B to R1-U1-P16B

R14 IB2 to Rack 2

R14-IB2-P9A to R2-U1-P16B

R14 IB2 to Rack 3

R14-IB2-P9B to R3-U1-P16B

R14 IB2 to Rack 4

R14-IB2-P10A to R4-U1-P16B

R14 IB2 to Rack 5

R14-IB2-P10B to R5-U1-P16B

R14 IB2 to Rack 6

R14-IB2-P16A to R6-U1-P16B

R14 IB2 to Rack 7

R14-IB2-P16B to R7-U1-P16B

R14 IB2 to Rack 8

R14-IB2-P8A to R8-U1-P16B

E.16 15-Rack Cabling

Table E-44 shows the cable connections for the switches when 15 racks are cabled together. The cabling among racks 1 through 8 does not change.

Table E-44 Leaf Switch Connections for Rack 15

Leaf Switch Connection

R15 IB3 to Rack 1

R15-IB3-P8B to R1-U1-P17A

R15 IB3 to Rack 2

R15-IB3-P9A to R2-U1-P17A

R15 IB3 to Rack 3

R15-IB3-P9B to R3-U1-P17A

R15 IB3 to Rack 4

R15-IB3-P10A to R4-U1-P17A

R15 IB3 to Rack 5

R15-IB3-P10B to R5-U1-P17A

R15 IB3 to Rack 6

R15-IB3-P17A to R6-U1-P17A

R15 IB3 to Rack 7

R15-IB3-P17B to R7-U1-P17A

R15 IB3 to Rack 8

R15-IB3-P8A to R8-U1-P17A

R15 IB2 to Rack 1

R15-IB2-P8B to R1-U1-P17B

R15 IB2 to Rack 2

R15-IB2-P9A to R2-U1-P17B

R15 IB2 to Rack 3

R15-IB2-P9B to R3-U1-P17B

R15 IB2 to Rack 4

R15-IB2-P10A to R4-U1-P17B

R15 IB2 to Rack 5

R15-IB2-P10B to R5-U1-P17B

R15 IB2 to Rack 6

R15-IB2-P17A to R6-U1-P17B

R15 IB2 to Rack 7

R15-IB2-P17B to R7-U1-P17B

R15 IB2 to Rack 8

R15-IB2-P8A to R8-U1-P17B

E.17 16-Rack Cabling

Table E-45 shows the cable connections for the switches when 16 full racks are cabled together. The cabling among racks 1 through 8 does not change.

Table E-45 Leaf Switch Connections for Rack 16

Leaf Switch Connection

R16 IB3 to Rack 1

R16-IB3-P8B to R1-U1-P0A

R16 IB3 to Rack 2

R16-IB3-P9A to R2-U1-P0A

R16 IB3 to Rack 3

R16-IB3-P9B to R3-U1-P0A

R16 IB3 to Rack 4

R16-IB3-P10A to R4-U1-P0A

R16 IB3 to Rack 5

R16-IB3-P10B to R5-U1-P0A

R16 IB3 to Rack 6

R16-IB3-P0A to R6-U1-P0A

R16 IB3 to Rack 7

R16-IB3-P0B to R7-U1-P0A

R16 IB3 to Rack 8

R16-IB3-P8A to R8-U1-P0A

R16 IB2 to Rack 1

R16-IB2-P8B to R1-U1-P0B

R16 IB2 to Rack 2

R16-IB2-P9A to R2-U1-P0B

R16 IB2 to Rack 3

R16-IB2-P9B to R3-U1-P0B

R16 IB2 to Rack 4

R16-IB2-P10A to R4-U1-P0B

R16 IB2 to Rack 5

R16-IB2-P10B to R5-U1-P0B

R16 IB2 to Rack 6

R16-IB2-P0A to R6-U1-P0B

R16 IB2 to Rack 7

R16-IB2-P0B to R7-U1-P0B

R16 IB2 to Rack 8

R16-IB2-P8A to R8-U1-P0B

E.18 17-Rack Cabling

Table E-46 shows the cable connections for the switches when 17 racks are cabled together. The cabling among racks 1 through 8 does not change.

Table E-46 Leaf Switch Connections for Rack 17

Leaf Switch Connection

R17 IB3 to Rack 1

R17-IB3-P8B to R1-U1-P1A

R17 IB3 to Rack 2

R17-IB3-P9A to R2-U1-P1A

R17 IB3 to Rack 3

R17-IB3-P9B to R3-U1-P1A

R17 IB3 to Rack 4

R17-IB3-P10A to R4-U1-P1A

R17 IB3 to Rack 5

R17-IB3-P10B to R5-U1-P1A

R17 IB3 to Rack 6

R17-IB3-P1A to R6-U1-P1A

R17 IB3 to Rack 7

R17-IB3-P1B to R7-U1-P1A

R17 IB3 to Rack 8

R17-IB3-P8A to R8-U1-P1A

R17 IB2 to Rack 1

R17-IB2-P8B to R1-U1-P1B

R17 IB2 to Rack 2

R17-IB2-P9A to R2-U1-P1B

R17 IB2 to Rack 3

R17-IB2-P9B to R3-U1-P1B

R17 IB2 to Rack 4

R17-IB2-P10A to R4-U1-P1B

R17 IB2 to Rack 5

R17-IB2-P10B to R5-U1-P1B

R17 IB2 to Rack 6

R17-IB2-P1A to R6-U1-P1B

R17 IB2 to Rack 7

R17-IB2-P1B to R7-U1-P1B

R17 IB2 to Rack 8

R17-IB2-P8A to R8-U1-P1B

E.19 18-Rack Cabling

Table E-47 shows the cable connections for the switches when 18 racks are cabled together. The cabling among racks 1 through 8 does not change.

Table E-47 Leaf Switch Connections for Rack 18

Leaf Switch Connection

R18 IB3 to Rack 1

R18-IB3-P8B to R1-U1-P2A

R18 IB3 to Rack 2

R18-IB3-P9A to R2-U1-P2A

R18 IB3 to Rack 3

R18-IB3-P9B to R3-U1-P2A

R18 IB3 to Rack 4

R18-IB3-P10A to R4-U1-P2A

R18 IB3 to Rack 5

R18-IB3-P10B to R5-U1-P2A

R18 IB3 to Rack 6

R18-IB3-P2A to R6-U1-P2A

R18 IB3 to Rack 7

R18-IB3-P2B to R7-U1-P2A

R18 IB3 to Rack 8

R18-IB3-P8A to R8-U1-P2A

R18 IB2 to Rack 1

R18-IB2-P8B to R1-U1-P2B

R18 IB2 to Rack 2

R18-IB2-P9A to R2-U1-P2B

R18 IB2 to Rack 3

R18-IB2-P9B to R3-U1-P2B

R18 IB2 to Rack 4

R18-IB2-P10A to R4-U1-P2B

R18 IB2 to Rack 5

R18-IB2-P10B to R5-U1-P2B

R18 IB2 to Rack 6

R18-IB2-P2A to R6-U1-P2B

R18 IB2 to Rack 7

R18-IB2-P2B to R7-U1-P2B

R18 IB2 to Rack 8

R18-IB2-P8A to R8-U1-P2B