Single-Phase PDU Cabling

The following table lists the specifications for single-phase power distribution units (PDUs) in various countries:

Table 1 Single-phase PDUs
Single-phase PDUs North America, South America, Japan, and Taiwan EMEA
Rack location Vertical rack-mounted PDUs that occupy no rack unit (RU) space. Vertical rack-mounted PDUs that occupy no rack unit (RU) space.
Inlet circuits Each PDU has two 30A (de-rated to 24A) inlet circuits. The inlet plug style is NEMA L6-30. Each PDU has two 25A inlet circuits. The inlet plug style is IEC309.
AC voltage Each PDU supports AC voltage levels 200 – 240VAC at 50/60Hz. Each PDU supports AC voltage levels from 200 – 240VAC at 50/60Hz.
Power Each PDU can supply 10KW of power when both power cables are connected. Each PDU can supply 10KW of power when both power cables are connected.
Outlet groups All PDUs have 42 outlets arranged in six groups of seven outlets. All PDUs have 42 outlets arranged in six groups of seven outlets.
Receptacles All 42 outlets are IEC60320 C13 style receptacles. The C13 receptacle can supply 10A.
Note: If two outlets are configured to draw 10A each, the remaining five outlets in the group cannot be used.
All 42 outlets are IEC60320 C13 style receptacles. The C13 receptacle can supply 10A.
Note: If two outlets are configured to draw 10A each, the remaining five outlets in the group cannot be used.
Circuit breaker Each group of seven outlets have a 20A rated circuit breaker that can be re-set. Each group of seven outlets have a 20A rated circuit breaker that can be re-set.
The following figure shows the outlet groups for single-phase PDUs.

Figure 1: Single phase PDU outlet groups

 Single phase PDU outlet groups 
Legend
1 AC inlet circuit P1 supplies groups 0,1, and 2
2 AC inlet circuit P2 supplies groups 3,4, and 5
3 Current is monitored across both AC inlet circuits
4 Group of seven outlets has its own 20 A circuit breaker that can be re-set