U.S . |
Metric |
---|---|---|
Height |
68.3 in |
173 cm |
Width |
30 in |
77 cm |
Depth |
39 in |
99 cm |
Weight |
835 lb, approx |
375 kg, approx |
Power cord |
15 ft |
4.6 m |
Table A-2 Enterprise 6500/5500 Clearance and Service Access
|
U.S. |
Metric |
---|---|---|
Front |
4 ft |
122 cm |
Rear |
3 ft |
92 cm |
Left |
1 ft* |
31 cm |
Right |
1 ft * |
31 cm |
* Access only. There are no side clearance requirements during operation. |
Table A-3 Enterprise 6500/5500 Shipping Specifications
|
U.S. |
Metric |
---|---|---|
Height |
75.3 in |
188 cm |
Width |
39 in |
99 cm |
Depth |
44.5 in |
113 cm |
Weight |
910 lb, approx |
415 kg, approx |
Table A-4 Enterprise 4500 Physical Specifications
|
U.S. |
Metric |
---|---|---|
Height |
13.5 in |
34 cm |
Width |
19.7 in |
50 cm |
Depth |
22 in |
56 cm |
Weight |
150 lb, approx |
68 kg, approx |
Power cord |
6 ft |
1.8 m |
Table A-5 Enterprise 4500 Clearance and Service Access
|
U.S. |
Metric |
---|---|---|
Front |
18 in |
47 cm |
Rear |
18 in |
47 cm |
Left |
6 in* |
16 cm* |
Right |
6 in* |
16 cm* |
*Although 6 in (16 cm) clearance is sufficient to prevent blocking the in and out airflow of a single system, to avoid exhaust air recirculation, a minimum space of 36 in (92 cm) is recommended between systems sitting side by side. |
Table A-6 Enterprise 4500 Shipping Specifications
|
U.S. |
Metric |
---|---|---|
Height |
19.0 in |
48 cm |
Width |
23.8 in |
60 cm |
Depth |
26.8 in |
68 cm |
Weight |
160 lb, approx |
72 kg, approx |
Parameter |
|
Value |
---|---|---|
Input current |
Voltage range |
200-240 Vac |
|
Current, maximum |
24A |
|
Current frequency range |
47-63 Hz |
Input power rating |
Total continuous power |
3500W (with 3 drive trays) |
Volt-Ampere rating |
|
3700 VA |
BTU rating |
|
12,000 BTU |
Power factor |
|
0.92 - 0.96 |
Plug type |
U.S. |
NEMA L6-30P for 200-240 Vac |
|
International |
32A, single phase IEC 309, connected for 220-240 Vac |
Table A-8 Enterprise 4500 Electrical Specifications
Parameter |
|
Value |
---|---|---|
Input current |
Voltage range |
100-120 Vac or 200-240 Vac |
|
Current, maximum |
12A |
|
Current frequency range |
47-63 Hz |
Input power rating |
Total continuous power |
1370W |
Volt-Ampere rating |
|
1440 VA |
BTU rating |
|
4680 BTU |
Power factor |
|
0.92 - 0.96 |
Plug type |
U.S. |
NEMA 5-15P |
|
International |
10A, single phase IEC 320, connected for 220-240 Vac |
|
Operating |
Nonoperating |
---|---|---|
Temperature |
41F to 95F (5C to 35C)* |
-4F to 140F (-20C to 60C) |
Humidity |
20% to 80% RH noncondensing, 27C max wb |
93% RH |
Altitude |
9,843 ft (3 km) |
39,370 ft (12 km) |
*Maximum operating temperature is 95F (35C) when using tape media. |
Table A-10 Enterprise 4500 Temperature, Humidity, and Altitude Limits
|
Operating |
Nonoperating |
---|---|---|
Temperature |
41F to 104F (5C to 40C)* |
-4F to 140F (-20C to 60C) |
Humidity |
20% to 80% RH noncondensing, 27C max wb |
93% RH |
Altitude |
9,843 ft (3 km) |
39,370 ft (12 km) |
*Maximum operating temperature is 95F (35C) when using tape media. |