Sun Fire V490 Server Administration Guide
|
|
This appendix provides the following specifications for the Sun Fire V490 Server server:
Physical Specifications
The dimensions and weight of the system are as follows.
Measurement
|
U.S
|
Metric
|
Height
|
8.75 in
|
222 mm
|
Width
|
17.5 in
|
446 mm
|
Depth
|
24 in
|
610 mm
|
Weight
Minimum
Maximum
|
79 lbs
97 lbs
|
35.83 kg
44 kg
|
Power Cord
|
8.2 ft
|
2.5 m
|
Electrical Specifications
The following table provides the electrical specifications for the system.
Note - All electrical specifications apply to a fully configured system.
|
Parameter
|
Value
|
Input
|
Nominal Frequencies
|
50 or 60 Hz
|
Nominal Voltage Range
|
Auto Ranging 200-240 VAC
|
Maximum Current AC RMS
|
8A @ 200-240 VAC
|
Maximum AC Power Consumption
|
1600 W
|
Maximum Heat Dissipation
|
5459 BTU/hr
|
Environmental Specifications
The operating and non-operating environmental specifications for the system are as follows.
Parameter
|
Value
|
Operating
|
Temperature
|
5°∞ C to 35°C (41°F to 95°F)--IEC 60068-2-1&2
|
Humidity
|
20% to 80% RH noncondensing; 27°C (81°F) wet bulb--
IEC 60068-2-3&56
|
Altitude
|
0 to 3000 meters (0 to 10,000 feet)--IEC 60068-2-13
|
Vibration
|
.0001 (z-axis only) G2/Hz, 5-150 Hz, -12db/octave slope, 150-500 Hz-- IEC 60068-2-13
|
Shock
|
3g peak, 11 milliseconds half-sine pulse--IEC 60068-2-27
|
Declared Acoustics
|
72 DbA
|
Non-Operating
|
Temperature
|
-20°C to 60°C (-4°F to 140°F)--IEC 60068-2-1&2
|
Humidity
|
95% RH noncondensing--IEC 60068-2-3&56
|
Altitude
|
0 to 12,000 meters (0 to 40,000 feet)--IEC 60068-2-13
|
Vibration
|
.001 (z-axis only) G2/Hz, 5-150 Hz, -12db/octave slope, 150-500 Hz-- IEC 60068-2-13
|
Shock
|
10g peak, 11 milliseconds half-sine pulse--IEC 60068-2-27
|
Handling Drops
|
25 mm (10 in)
|
Threshold Impact
|
1 meter/second
|
Agency Compliance Specifications
The system complies with the following specifications.
Category
|
Relevant Standards
|
Safety
|
UL 60950, CB Scheme IEC 60950, CSA C22.2 No. 60950-00 from UL,
TUV EN 60950
|
RFI/EMI
|
47 CFR 15B Class A
EN55022 Class A
VCCI Class A
ICES-003
AS/NZ 3548
CNS 13438
|
Immunity
|
EN55024
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-11
|
Clearance and Service Access Specifications
Minimum clearances needed for servicing the system are as follows.
Blockage
|
Required Clearance
|
Front blockage only
|
36 in (92 cm)
|
Rear blockage only
|
36 in (92 cm)
|
Front and rear blockage
Front clearance
Rear clearance
|
36 in (92 cm)
36 in (92 cm)
36 in (92 cm)
|
Sun Fire V490 Server Administration Guide
|