1.  Site Planning for the Sun Blade 6048 Modular System

Customer Obligations

System Configuration

Preparing the Site Before the System Arrives

Load-Bearing and Handling Precautions

Power and Electrical Requirements

Power Budgeting

Cooling Requirements

Temperature and Humidity Requirements

Airflow Requirements

Clearance for Service and Aisle Requirements

Route to the Data Center

Facility Safety

Secure Installation Requirements

Placement of an Oracle Product

Hazardous Conditions Precaution

System Specifications

Shipping Crate Physical Specifications

Chassis and Components Dimensions and Weights

AC Power Requirements

Environmental Specifications

Thermal Design Specifications

Acoustic Noise Emissions

Regulatory Compliance

Site Planning Checklist

A.  Conversion Information

Index

System Specifications

This section describes the following system specifications:

Shipping Crate Physical Specifications

The standard Sun Blade 6048 modular system is shipped with the following components installed:

The chassis shipping crate physical specifications are as follows.

Table 1-2 Standard Shipping Crate Physical Specifications 

Dimension or Weight
Specification
Shipping crate height
87.5 inches (222.3 cm)
Shipping crate width
48 inches (121.9 cm)
Shipping crate length
62 inches (157.5 cm)
Chassis, packaging, and pallet weight
Approximately 2500 lb (1134 kg)

Chassis and Components Dimensions and Weights

The unpacked chassis and component dimensions and weights are as follows.

Table 1-3 Chassis and Component Physical Specifications

Dimension or Weight
Specification
Chassis height
81.7 inches (2075 mm)
Chassis depth
40.35 inches (1025 mm)
Chassis width
23.78 inches (604 mm)
Chassis weight
Fully configured system: 2300 lb (1045 kg) Empty chassis: 1300 lb (590 kg) Subassembly weights:
  • I/O chassis with midplane: 26 lb (11.79 kg)

  • Power supply module: 30 lb (13.6 kg)

  • Server Module: 23 lb (10.43 kg)

  • Front fan module: 1.95 lb (0.88 kg)

  • Rear fan module: 2.31 lb (1.04 kg)

  • Network Express Module: 3.85 lb (1.75 kg)

  • PCI Express Module: 0.78 lb (0.35 kg)

  • Chassis Monitoring Module: 1.25 lb (0.57 kg)

  • Front Indicator Module: 0.75 lb (0.34 kg)

AC Power Requirements

The AC power requirements of the system are as follows.

Table 1-4 AC Power Requirements 

Function
Specification
Voltage
200 to 240 VAC
Frequency
50/60 Hz
Current
16A per input, total six AC inputs (three per power supply module).
Number of AC inputs
6 per shelf; 24 total for the whole system
AC input connection
  • Americas Domestic – NEMA L6-20P to IEC320-C19M (4m, Oracle PN X5044A-Z)
  • International – IEC309 to IEC320-C19 (4m, Oracle PN X5045A-Z)

  • Installed in rack with modular power system – IEC320-C319 to IEC320-C20 (1.5m, Oracle PN X5046A-Z; 2.0m, X5047A-Z)

Environmental Specifications

The environmental specifications of the system are as follows.

Table 1-5 Environmental Specifications 

Specification
Operating
Nonoperating
Temperature
5 to 32 oC (41 to 90 oF) noncondensing
-40 to 65 oC (-40 to 149 oF) noncondensing
Optimum ambient temperature
23 oC (73.4 oF)
Relative humidity
10 to 90% RH, noncondensing, 27 oC max wet bulb
5 to 93% RH, noncondensing, 38 oC max wet bulb
Optimum ambient relative humidity
45 to 50% RH, noncondensing
Altitude
0 to 10,000 feet (3048 m) maximum ambient temperature is derated by 1 oC per 300 m (984 ft) above 900 m (2953 ft)
0 to 39,370 feet (12,000 m)

Thermal Design Specifications

The thermal design specifications of the system are as follows.

Table 1-6  Thermal Design Specifications

Parameter
Specification
Per shelf volumetric airflow
844 CFM typical, 1460 CFM maximum possible
Maximum possible per shelf heat dissipation/HVAC load
32,000 BTU/h
Maximum possible temperature rise through chassis
19.6 oC (35 oF)

Acoustic Noise Emissions

Declared noise emissions are in accordance with ISO 9295/9296 standards.

Data center personnel should take necessary precautions to reduce exposure to the high noise levels. Acoustic noise emission levels are as follows:

Table 1-7 Acoustic Noise Emission Specifications Per Rack

Function
Specification
Operating/idling acoustic noise (LwAd, 1B=10 dB)
9.2 B at or below 23 °C, 10.1 B at max ambient