Sun Storage J4200/J4400 Specifications
|
This chapter describes the physical, environmental, and electrical requirements for the Sun Storage J4200/J4400 arrays. Where information for both arrays is the same, a single table is used. This chapter contains the following sections:
Dimension and Weight Specifications
The floor space at the installation site must be strong enough to support the combined weight of the cabinet, controller trays, expansion trays, and associated equipment. The site also requires sufficient space for installation, operation, and servicing the arrays and sufficient ventilation to provide a free flow of air to the unit.
The total weight of an expansion tray depends on the number of drives installed.
TABLE 3-1 provides the physical dimensions and weight of the J4200 and the J4400 arrays.
TABLE 3-1 Dimensions and Weight (with rails)
Height
|
Width
|
Depth
|
Weight (Fully Populated)
|
J4200
|
|
|
|
3.44 in.
|
17.52 in.
|
24.05 in.
|
59.61 lb.
|
8.74 cm
|
44.5 cm
|
61.1 cm
|
27.04 kg
|
J4400
|
|
|
|
6.88 in.
|
17.5 in.
|
23.4 in.
|
103.20 lbs
|
17.48 cm
|
44.5 cm
|
59.4 cm
|
46.81 kg
|
Environmental Requirements
This section describes the environmental conditions that are prerequisite to installing the unit, and heat conditions that are generated by normal operation of the unit.
J4200 Temperature lists the temperature specifications in which the J4200 array is designed to operate, and J4400 Temperature lists the temperature specifications in which the J4400 array is designed to operate.
TABLE 3-2 J4200 Temperature
Parameter
|
Specification
|
Operating range
|
35˚ F to 95˚ F (0˚ C to 35˚ C)
|
Maximum rate of change
|
18˚ F (10˚ C) per hour
|
Storage range
|
-40˚ F to 149˚ F (-40˚ C to 65˚ C)
|
Maximum rate of change
|
27˚ F (15˚ C) per hour
|
Transit range
|
-40˚ F to 149˚ F (-40˚ C to 65˚ C)
|
Maximum rate of change
|
27˚ F (15˚ C) per hour
|
Heat output1
|
352.8 Watts (1204 BTU/hour)
|
TABLE 3-3 J4400 Temperature
Operating range
|
35˚ F to 95˚ F (0˚ C to 35˚ C)
|
Maximum rate of change
|
18˚ F (10˚ C) per hour
|
Storage range
|
-40˚ F to 149˚ F (-40˚ C to 65˚ C)
|
Maximum rate of change
|
27˚ F (15˚ C) per hour
|
Transit range
|
-40˚ F to 149˚ F (-40˚ C to 65˚ C)
|
Maximum rate of change
|
27˚ F (15˚ C) per hour
|
Heat output2
|
662 Watts (2123 BTU/hour)
|
1 Based on a configuration of two power supplies, two SIMs, two fan modules, and 12 drives.
2 Based on a configuration of two power supplies, two SIMs, and 24 drives.
Humidity
Table shows the operating temperature, relative humidity, altitude, shock, vibration, and heat output ranges of the array trays.
J4200/J4400 Relative Humidity (noncondensing) lists the relative humidity of the J4200/J4400 array.
TABLE 3-4 J4200/J4400 Relative Humidity (noncondensing)
Parameter
|
Specification
|
Operating range
|
20% to 80%
|
Nonoperating range
|
20% to 95%
|
Storage range
|
20% to 95%
|
Transit range
|
20% to 95%
|
Maximum dew point
|
26˚ C (79˚ F)
|
Maximum gradient
|
10% per hour
|
Altitude
J4200/J4400 Altitude lists the altitude specifications for the J4200/J4400 array.
TABLE 3-5 J4200/J4400 Altitude
Environment
|
Specification
|
Operating
|
0 to 9,843 feet (3,000 meters)
|
Non-operating
|
0 to 39,370 feet (12,000 meters)
|
Vibration and Shock
J4200 Shock and Vibration lists the vibration and shock specifications for the J4200 array, and J4400 Shock and Vibration lists the vibration and shock specifications for the J4400 array.
TABLE 3-6 J4200 Shock and Vibration
Condition
|
Parameter
|
Specification
|
Vibration
|
Operating
|
0.25 G (peak), 3 to 200 Hz sweep @ 1/2 octave per minute, bottom side tested only
|
Nonoperating (unpacked)
|
10 Hz to 250 Hz, 1.54 GRMS random vibration, 15 minutes, 3 axes
|
Transit and storage (packed)
|
2 Hz to 200 Hz, 0.8 GRMS random vibration, 30 minutes, 6 axes
|
Shock
|
Operating (no damage)
|
31-G +/-5%, with pulse duration of 2.6 ms or less half-sine, bottom side tested only
|
Nonoperating
|
71-G +/-5%, with pulse duration of 2.0 ms or less half-sine, all six sides tested
|
Transit (packed)
|
Height 24.015 in. (610 mm), six sides, two corners, six edges
|
TABLE 3-7 J4400 Shock and Vibration
Condition
|
Parameter
|
Specification
|
Vibration
|
Operating
|
0.25 G (peak), 3 to 200 Hz sweep @ 1/2 octave per minute, bottom side tested only
|
Nonoperating (unpacked)
|
10 Hz to 250 Hz, 1.54 GRMS random vibration, 15 minutes, 3 axes
|
Transit and storage (packed)
|
2 Hz to 200 Hz, 0.8 GRMS random vibration, 30 minutes, 6 axes
|
Shock
|
Operating (no damage)
|
31-G +/-5%, with pulse duration of 2.6 ms or less half-sine, bottom side tested only
|
Nonoperating
|
71-G +/-5%, with pulse duration of 2.0 ms or less half-sine, all six sides tested
|
Transit (packed)
|
Height 17.992 in. (457 mm), six sides, two corners, six edges
|
Table shows the non-operating temperature, relative humidity, altitude, shock, vibration, and heat output ranges of the array trays.
Electrical Requirements
This section provides information regarding site power and wiring, module AC power requirements, and power cord routing instructions.
Site Wiring and Power
The tray uses wide-ranging redundant power supplies that automatically accommodate voltages to the AC power source. The power supplies operate within the range of 100 VAC to 240 VAC, at a minimum frequency of 47 Hz and a maximum frequency of 63 Hz. The power supplies meet standard voltage requirements for both domestic (inside USA) and international (outside USA) operation. They use standard industrial wiring with line-to-neutral or line-to-line power connections.
Power Input
The AC power sources must provide the correct voltage, current, and frequency specified on the tray model and serial number label. The tray can run without interruption within the limits shown in TABLE 3-8 and TABLE 3-9.
TABLE 3-8 J4200 Tray AC Power Requirements
Condition
|
Specification
|
AC power
|
9 A maximum operating (100 VAC to 127 VAC range), 47 to 63 Hz
4.5 A maximum operating (200 VAC to 240 VAC range), 47 to 63 Hz
|
Maximum operating current
|
1.51 A maximum operating @ 240 VAC (198 VAC to 264 VAC range), 50 to 60 Hz
|
.
TABLE 3-9 J4400 Tray AC Power Requirements
Condition
|
Specification
|
AC power
|
10 A maximum operating @ (100 VAC to 127 VAC range), 47 to 63 Hz
|
Maximum operating current
|
27.4 A maximum operating @ 240 VAC (198 VAC to 264 VAC range), 50 to 60 Hz
|
Table shows the voltage,current, and fr4equency of the tray..Power Cords and Receptacles
All trays are shipped with two AC power cords that are appropriate for use in a typical outlet in the destination country.
Each power cord connects one of the power supplies in a tray to an independent external power source, such as those provided in the supported Sun cabinet, a wall receptacle, or uninterruptible power supply (UPS).
Sun Storage J4200/J4400 Site Preparation Guide
|
820-3219-10
|
|
Copyright © 2008, Sun Microsystems, Inc. All Rights Reserved.