Environmental Specifications

For the Acme Packet 6300/6350 to function properly, Acme Packet recommends that you follow the environmental guidelines in the following table.

Table 7-7 Acme Packet 6300/6350 Environmental Specifications

Specification Description
Temperature The Acme Packet 6300/6350 System is required to operate within the temperature range of:

* +0° C to +40° C, 32° F to 104° F (operating)

* -20° C to +65° C, -4° F to 149° F (storage)

Relative Humidity Operating conditions of 10% to 85% humidity under non-condensing operating conditions
Maximum Altitude The Acme Packet 6300/6350 System is required to operate below the maximum altitude of 10,000 feet.
Air Flow 300 CFM
Power Dissipation 250W typical 350W maximum (base system with 2x10 G NIU)

Additional 150W for second 2 x 10GbE NIU

Additional 275W for each fully populated transcode carrier card