2.2 Flooring Requirements

Oracle recommends that the Oracle Virtual Compute Appliance be installed on raised flooring. The site floor and the raised flooring must be able to support the total weight of the system as specified in Section 2.1, “Space Requirements”.

Table 2.3 lists the floor load requirements.

Table 2.3 Floor Load Requirements

Description

Requirement

Maximum allowable weight of installed rack equipment

952.54 kg (2100 lbs)

Maximum allowable weight of installed power distribution units

52.16 kg (115 lbs)

Maximum dynamic load (maximum allowable weight of installed equipment including power distribution units)

1004.71 kg (2215 lbs)