Electrical Specifications

Description
Value
Operating Input Range
100 to 120 VAC; 200 to 240 VAC; 50-60 Hz
Max Operating Input Current per cord at 100VAC
8.6 A
Max Operating Input Current per cord at 200VAC
4.1 A
Max operating input power at 100VAC
851 W
Max operating input power at 200VAC
819 W
Maximum heat dissipation
2904 BTU/hr
3064 KJ/hr
Maximum standby power
23.4 W
Maximum server configuration specification under nominal temperature and voltage conditions
(SPARC S7-2, Two 4.267GHz S7 Processors, 16 64GB DDR4 DIMMS, 4 SAS + 4 NVMe-SFF drives , 1 Internal HBA card, 3 PCIe cards)
Idle AC input power
412 W
Peak AC input power running MGRID
749 W
Minimum server configuration specification under nominal temperature and voltage conditions
(SPARC S7-2-1S, One 4.267GHz S7 Processors, 4 16GB DDR4 DIMMS, 0 drives, 1 Internal HBA card, 0 PCIe cards)
Idle AC input power
190 W
Peak AC input power running MGRID
352 W

For information on power specifications, use the power calculator at:

http://www.oracle.com/us/products/servers-storage/sun-power-calculators