3.2 Reviewing Rack Compatibility

Verify that your rack is compatible with the slide-rail and cable management arm (CMA) options. The optional slide-rails are compatible with a wide range of equipment racks that meet the standards listed in.

Table 3-1 Rack Compatibility for Oracle Exalytics In-Memory Machine

Item Requirement

Structure

Four-post rack (mounting at both front and rear). Two-post racks are not compatible.

Rack horizontal opening and unit vertical pitch

Conforms to ANSI/EIA 310-D-1992 or IEC 60927 standards. Only M6 tapped or 9.5 mm square are supported.

Distance between front and rear mounting planes

Minimum 610 mm and maximum 915 mm

(24 inches to 36 inches).

Clearance depth in front of front mounting plane

Distance to front cabinet door is at least 25.4 mm

(1 inch).

Clearance depth behind front mounting plane

Distance to rear cabinet door is at least 900 mm (35.5 inches) with the cable management arm, or 770 mm (30.4 inches) without the cable management arm.

Clearance width between front and rear mounting planes

Distance between structural supports and cable troughs is at least 456 mm (18 inches).

Machine dimensions

Depth: (not including PSU handle): 732 mm (28.82 inches)

Width: (not including ears): 436.5 mm (17.19 inches)

Height: 129.85 mm (5.11 inches)