32324 - Breaker panel feed error

Alarm Group:
PLAT
Description:
This alarm indicates that the server is not receiving information from the breaker panel relays.
Severity:
Major
Instance:
May include AlarmLocation, AlarmId, AlarmState, AlarmSeverity, and bindVarNamesValueStr
HA Score:
Normal
Auto Clear Seconds:
0 (zero)
OID:
tpdBrkPnlFeedError
Alarm ID:
TKSPLATMA25

Recovery:

  1. Verify that the same alarm is displayed by multiple servers:
    • If this alarm is displayed by only one server, the problem is most likely to be with the cable or the server itself. Look for other alarms that indicate a problem with the server and perform the recovery procedures for those alarms first.
    • If this alarm is displayed by multiple servers, go to the next step.
  2. Verify that the cables that connect the servers to the breaker panel are not damaged and are securely fastened to both the Alarm Interface ports on the breaker panel and to the serial ports on both servers.
  3. If the problem has not been resolved, it is recommended to contact unresolvable-reference.htm#GUID-DD0927BD-FD0B-4CEB-86E9-98A33C12D4E0 to request that the breaker panel be replaced.