Electrical Power
Learn about the electrical power specifications and requirements for Exadata Cloud at Customer.
Exadata Cloud at Customer can operate effectively over a wide range of voltages and frequencies. However, it must have a reliable power source. Damage may occur if the ranges are exceeded. Electrical disturbances such as the following may damage an Exadata Cloud at Customer:
-
Fluctuations caused by brownouts
-
Wide and rapid variations in input voltage levels or in input power frequency
-
Electrical storms
-
Faults in the distribution system, such as defective wiring
To protect the system, dedicated power distribution system and power-conditioning equipment should be used. Lightning arresters or power cables should be used to protect from electrical storms.
Each rack has two pre-installed Power Distribution Units (PDUs). The PDUs accept different power sources. You must select the type of PDU that meets the requirements for your data center.
Available PDUs
The following list outlines the available PDUs for Exadata Cloud at Customer depending on your region:
-
Americas, Japan, and Taiwan
-
Low-Voltage 15kVA Single-Phase
-
Low-Voltage 15kVA Three-Phase
-
Low-Voltage 22kVA Single-Phase
-
Low-Voltage 24kVA Three-Phase
-
-
Europe, the Middle East and Africa (EMEA), and Asia Pacific (APAC), except for Japan and Taiwan
-
High-Voltage 15kVA Three-Phase
-
High-Voltage 22kVA Single-Phase
-
High-Voltage 24kVA Three-Phase
-
Low-voltage PDU electrical specifications
The following table lists the low-voltage PDU specifications. The listed specifications are for each PDU. Each rack contains two PDUs.
Specification | 15 kVA, 1 phase | 15 kVA, 3 phase | 22 kVA, 1 phase | 24 kVA, 3 phase |
---|---|---|---|---|
Voltage | 200 - 240 VAC | 200 - 208 VAC 3ph | 200 - 240 VAC | 200 - 208 VAC 3ph |
Frequency | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz |
Current | 24A maximum per input | 40A maximum per phase | 36.8 A maximum per input | 34.6 A maximum per phase |
Power Rating | 15 kVA | 14.4 kVA | 22 kVA | 25 kVA |
Output Current | 72A (3 x 24A) | 69A (3 x 23A) | 110.4 A (3 x 36.8 A) | 120A (6 x 20A) |
Outlets | 42 x C13; 6 x C19 | 42 x C13; 6 x C19 | 42 x C13; 6 x C19 | 42 x C13; 6 x C19 |
Number of Inputs | 3 x 30A, 1 phase | 1 x 60A, 3 phase | 3 x 50 A, 1 phase | 2 x 60A, 3 phase |
Data Center Receptacle | NEMA L6-30 | IEC309 60A 4 PIN 250VAC 3ph IP67 | Hubbell CS8264C | IEC309 60A 4 PIN 250VAC 3ph IP67 |
High-voltage PDU electrical specifications
The following table lists the high-voltage PDU specifications. The listed specifications are for each PDU. Each rack contains two PDUs.
Specification | 15 kVA, 3 phase | 22 kVA, 1 phase | 24 kVA, 3 phase |
---|---|---|---|
Voltage | 220/380 - 240/415 VAC 3ph | 220 - 240 VAC | 220/380 - 240/415 VAC 3ph |
Frequency | 50/60 Hz | 50/60 Hz | 50/60 Hz |
Current | 25A maximum per phase | 32A maximum per input | 18A maximum per phase |
Power Rating | 14.4 kVA | 22 kVA | 25 kVA |
Output Current | 62.7A (3 x 20.9A) | 96A (3 x 32A) | 109A (6 x 18.1A) |
Outlets | 42 x C13; 6 x C19 | 42 x C13; 6 x C19 | 42 x C13; 6 x C19 |
Number of Inputs | 1 x 25A, 3 phase | 3 x 32A, 1 phase | 2 x 25A, 3 phase |
Data Center Receptacle | IEC309 32A 5 PIN 230/400V 3ph IP44 | IEC309 32A 3 PIN 250 VAC IP44 | IEC309 32A 5 PIN 230/400V 3ph IP44 |