Electrical Power

Learn about the electrical power specifications and requirements for Exadata Cloud at Customer.

Exadata Cloud at Customer can operate effectively over a wide range of voltages and frequencies. However, it must have a reliable power source. Damage may occur if the ranges are exceeded. Electrical disturbances such as the following may damage an Exadata Cloud at Customer:

  • Fluctuations caused by brownouts

  • Wide and rapid variations in input voltage levels or in input power frequency

  • Electrical storms

  • Faults in the distribution system, such as defective wiring

To protect the system, dedicated power distribution system and power-conditioning equipment should be used. Lightning arresters or power cables should be used to protect from electrical storms.

Each rack has two pre-installed Power Distribution Units (PDUs). The PDUs accept different power sources. You must select the type of PDU that meets the requirements for your data center.

Available PDUs

The following list outlines the available PDUs for Exadata Cloud at Customer depending on your region:

  • Americas, Japan, and Taiwan

    • Low-Voltage 15kVA Single-Phase

    • Low-Voltage 15kVA Three-Phase

    • Low-Voltage 22kVA Single-Phase

    • Low-Voltage 24kVA Three-Phase

  • Europe, the Middle East and Africa (EMEA), and Asia Pacific (APAC), except for Japan and Taiwan

    • High-Voltage 15kVA Three-Phase

    • High-Voltage 22kVA Single-Phase

    • High-Voltage 24kVA Three-Phase

Low-voltage PDU electrical specifications

The following table lists the low-voltage PDU specifications. The listed specifications are for each PDU. Each rack contains two PDUs.

Specification 15 kVA, 1 phase 15 kVA, 3 phase 22 kVA, 1 phase 24 kVA, 3 phase
Voltage 200 - 240 VAC 200 - 208 VAC 3ph 200 - 240 VAC 200 - 208 VAC 3ph
Frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Current 24A maximum per input 40A maximum per phase 36.8 A maximum per input 34.6 A maximum per phase
Power Rating 15 kVA 14.4 kVA 22 kVA 25 kVA
Output Current 72A (3 x 24A) 69A (3 x 23A) 110.4 A (3 x 36.8 A) 120A (6 x 20A)
Outlets 42 x C13; 6 x C19 42 x C13; 6 x C19 42 x C13; 6 x C19 42 x C13; 6 x C19
Number of Inputs 3 x 30A, 1 phase 1 x 60A, 3 phase 3 x 50 A, 1 phase 2 x 60A, 3 phase
Data Center Receptacle NEMA L6-30 IEC309 60A 4 PIN 250VAC 3ph IP67 Hubbell CS8264C IEC309 60A 4 PIN 250VAC 3ph IP67

High-voltage PDU electrical specifications

The following table lists the high-voltage PDU specifications. The listed specifications are for each PDU. Each rack contains two PDUs.

Specification 15 kVA, 3 phase 22 kVA, 1 phase 24 kVA, 3 phase
Voltage 220/380 - 240/415 VAC 3ph 220 - 240 VAC 220/380 - 240/415 VAC 3ph
Frequency 50/60 Hz 50/60 Hz 50/60 Hz
Current 25A maximum per phase 32A maximum per input 18A maximum per phase
Power Rating 14.4 kVA 22 kVA 25 kVA
Output Current 62.7A (3 x 20.9A) 96A (3 x 32A) 109A (6 x 18.1A)
Outlets 42 x C13; 6 x C19 42 x C13; 6 x C19 42 x C13; 6 x C19
Number of Inputs 1 x 25A, 3 phase 3 x 32A, 1 phase 2 x 25A, 3 phase
Data Center Receptacle IEC309 32A 5 PIN 230/400V 3ph IP44 IEC309 32A 3 PIN 250 VAC IP44 IEC309 32A 5 PIN 230/400V 3ph IP44