Flooring

Learn about the flooring requirements for Exadata Cloud at Customer.

Oracle recommends that the Exadata Cloud at Customer system be installed on raised flooring. The site floor and the raised flooring must be able to support the total weight of Exadata Cloud at Customer.

The following table lists the floor load requirements.

Description Kilograms (kg) Pounds (lbs)
Maximum allowable weight of installed rack equipment 952.5 kg 2100 lbs
Maximum allowable weight of installed power distribution units 52.16 kg 115 lbs
Maximum dynamic load (maximum allowable weight of installed equipment including PDUs) 1004.66 kg 2215 lbs

Note:

Open tiles are typically required for electrical access.