C Power Distribution Units Specification
This topic describes the specification of the available PDUs depending on your region and Oracle Cloud at Customer configuration.
Note:
15kVA are available for Control Plane and certain smaller configurations only. For more details, contact the sales team.Table C-1 PDU specifications for low voltage
| Specification | Low Voltage 15 kVA, 1–phase | Low Voltage 15 kVA, 3–phase | Low Voltage 22 kVA, 1–phase | Low Voltage 24 kVA, 3–phase |
|---|---|---|---|---|
|
Typical Region |
North America, South America, Japan and Taiwan. |
North America, South America, Japan and Taiwan. |
North America, South America, Japan and Taiwan. |
North America, South America, Japan and Taiwan. |
|
Phase |
1 ph |
3 ph |
1 ph |
3 ph |
|
Marketing Part Number |
6442 A |
6440 A |
7100873 |
XSR-24K-IEC309-4P / 6444A |
|
Voltage |
200 - 240 VAC |
200 - 208 VAC 3ph |
200-240 VAC 1ph |
200-208 VAC 3 ph |
|
Frequency |
50/60 Hz |
50/60 Hz |
50/60 Hz |
50/60 Hz |
|
Current |
24 A maximum per input |
40 A maximum per phase |
36.8 A maximum per input |
34.6 A maximum per phase |
|
Power Rating |
15 kVA |
14.4 kVA |
22 kVA |
25 kVA |
|
Output Current |
72 A (3 x 24 A) |
69 A (3 x 23 A) |
110.4 A (3 x 36.8 A) |
120 A (6 × 20 A) |
|
Outlets |
42 x C13 6 x C19 |
42 x C13 6 x C19 |
42 x C13, 6 x C19 |
42 x C13, 6 x C19 |
|
Outlet Groups |
6 |
6 |
6 |
6 |
|
Group Protection |
20 A (UL489 2-pole circuit breaker) |
20 A (UL489 2-pole circuit breaker) |
20 A (UL489 2-pole circuit breaker) |
20 A (UL489 2-pole circuit breaker) |
|
Data Center Receptacle |
NEMA L6-30 |
IEC309 60 A 4 PIN 250VAC 3ph IP67 |
Hubbell CS8265C |
IEC309-3P4W-IP67 60 A 250 VAC 3 ph (Hubbell equivalent is HBL460R9W) |
|
Number of PDUs per Rack |
2 |
2 |
2 |
2 |
|
Number of Outlets per PDU |
3 |
1 |
3 |
2 |
|
Number of Outlets Per Rack |
6 |
2 |
6 |
4 |
Table C-2 PDU specifications for high voltage
| Specification | High Voltage 15 kVA, 3–phase | High Voltage 22 kVA, 1–phase | High Voltage 24 kVA, 3–phase |
|---|---|---|---|
|
Typical Region |
Europe, Middle East, Africa (EMEA), and Asia Pacific (APAC), except Japan and Taiwan. |
Europe, Middle East, Africa (EMEA), and Asia Pacific (APAC), except Japan and Taiwan. |
Europe, Middle East, Africa (EMEA), and Asia Pacific (APAC), except Japan and Taiwan. |
|
Phase |
3 ph |
1 ph |
3 ph |
|
Marketing Part Number |
6441 A |
7100874 |
XSR-24K-IEC309-5P |
|
Voltage |
220/380 – 240/415 VAC 3ph |
220-240 VAC 1 ph |
220/380-240/415 VAC 3 ph |
|
Frequency |
50/60 Hz |
50/60 Hz |
50/60 Hz |
|
Current |
25 A maximum per phase |
32 A maximum per input |
18.1 A maximum per phase |
|
Power Rating |
14.4 kVA |
22 kVA |
25 kVA |
|
Output Current |
62.7 A (3 x 20.9 A) |
96 A (3 x 32 A) |
108.6 A (6 × 18.1 A) |
|
Outlets |
42 x C13 6 x C19 |
42 x C13, 6 x C19 |
42 x C13, 6 x C19 |
|
Outlet Groups |
6 |
6 |
6 |
|
Group Protection |
20 A (UL489 1-pole circuit breaker) |
20 A (UL489 1-pole circuit breaker) |
20 A (UL489 1-pole circuit breaker) |
|
Data Center Receptacle |
IEC309 32 A 5 PIN 230/400V 3ph IP44 |
IEC309-2P3W-IP44 32 A 250 VAC (Hubbell equivalent is HBL332R6W) |
IEC309-4P5W-IP44 32 A 400 VAC 3 ph (Hubbell equivalent is HBL532R6W) |
|
Number of PDUs per Rack |
2 |
2 |
2 |
|
Number of Outlets per PDU |
1 |
3 |
2 |
|
Number of Outlets Per Rack |
2 |
6 |
4 |
Note:
Take note of the number of outlets required per rack. Oracle Cloud at Customer requires all power whips to be connected during installation due to the balanced power configuration of the racks. The customer is required to provide power receptacles for all the outlets that are available for the PDUs.