B Data Center Environmental Requirements

This topic describes the environmental requirements of the data center where Oracle Cloud at Customer is being installed.

Table B-1 Power, Cooling, Weight, and Dimensions Requirements for all Oracle Cloud at Customer Configurations

Requirement Specification Unit 1x Control Plane 1x Compute Model 1x Block Storage Model 1x Object Storage Model 1x Base Rack Oracle Advanced Support Gateway
Power Maximum kW 9.66 0.72 3.43 2.51 1.43 0.72
kVA 9.85 0.73 3.50 2.56 1.46 0.73
Typical kW 6.76 0.50 2.40 1.76 1.00 0.50
kVA 6.90 0.52 2.45 1.80 1.02 0.52
Cooling Maximum BTU/hour 32963 2455 11717 8576 4883 2455
kJ/hour 34776 2591 12362 9048 5152 2591
Typical BTU/hour 23075 1719 8202 6004 3419 1719
kJ/hour 24345 1814 8654 6335 3608 1814
Airflow Maximum CFM 1527 114 543 398 227 114
Typical CFM 1069 80 381 279 159 80
Weight Installed kg 500.8 18.1 150 120 224.1 18.1
lbs 1105 40 331 265 495 40
Shipping kg 567       290.3  
lbs 1251       641  
Dimensions Installed mm 600 (width) x 1200 (depth) x 1998 (height) 1 RU 12 RU 8 RU 600 x 1200 x 1998 1 RU
inches 23.62 x 47.24 x 78.66       23.62 x 47.24 x 78.66  
Shipping mm 1219 x 1575 x 2159       1219 x 1575 x 2159  
inches 48 x 62 x 85       48 x 62 x 85  

Note:

Individual configurations might differ from the specification described on the table. Contact Oracle for more information about ventilation requirements for your specific configuration.

Note:

See Physical Requirements for more information about requirements.