B Data Center Environmental Requirements
This topic describes the environmental requirements of the data center where Oracle Cloud at Customer is being installed.
Table B-1 Power, Cooling, Weight, and Dimensions Requirements for all Oracle Cloud at Customer Configurations
| Requirement | Specification | Unit | 1x Control Plane | 1x Compute Model | 1x Block Storage Model | 1x Object Storage Model | 1x Base Rack | Oracle Advanced Support Gateway |
|---|---|---|---|---|---|---|---|---|
| Power | Maximum | kW | 9.66 | 0.72 | 3.43 | 2.51 | 1.43 | 0.72 |
| kVA | 9.85 | 0.73 | 3.50 | 2.56 | 1.46 | 0.73 | ||
| Typical | kW | 6.76 | 0.50 | 2.40 | 1.76 | 1.00 | 0.50 | |
| kVA | 6.90 | 0.52 | 2.45 | 1.80 | 1.02 | 0.52 | ||
| Cooling | Maximum | BTU/hour | 32963 | 2455 | 11717 | 8576 | 4883 | 2455 |
| kJ/hour | 34776 | 2591 | 12362 | 9048 | 5152 | 2591 | ||
| Typical | BTU/hour | 23075 | 1719 | 8202 | 6004 | 3419 | 1719 | |
| kJ/hour | 24345 | 1814 | 8654 | 6335 | 3608 | 1814 | ||
| Airflow | Maximum | CFM | 1527 | 114 | 543 | 398 | 227 | 114 |
| Typical | CFM | 1069 | 80 | 381 | 279 | 159 | 80 | |
| Weight | Installed | kg | 500.8 | 18.1 | 150 | 120 | 224.1 | 18.1 |
| lbs | 1105 | 40 | 331 | 265 | 495 | 40 | ||
| Shipping | kg | 567 | 290.3 | |||||
| lbs | 1251 | 641 | ||||||
| Dimensions | Installed | mm | 600 (width) x 1200 (depth) x 1998 (height) | 1 RU | 12 RU | 8 RU | 600 x 1200 x 1998 | 1 RU |
| inches | 23.62 x 47.24 x 78.66 | 23.62 x 47.24 x 78.66 | ||||||
| Shipping | mm | 1219 x 1575 x 2159 | 1219 x 1575 x 2159 | |||||
| inches | 48 x 62 x 85 | 48 x 62 x 85 |