A Temperature and Humidity Requirements
This topic describes the environmental requirements of the data center where an Oracle Cloud at Customer is being installed.
Table A-1 Oracle Cloud at Customer Temperature and Humidity Requirements
Condition | Operating Requirement | Non-operating Requirement | Optimal Requirement |
---|---|---|---|
Temperature |
5 to 32 degrees Celsius (59 to 89.6 degrees Fahrenheit) |
-40 to 70 degrees Celsius (-40 to 158 degrees Fahrenheit). |
For optimal rack cooling, data center temperatures from 21 to 23 degrees Celsius (70 to 74 degrees Fahrenheit). |
Relative humidity |
10 to 90 percent relative humidity, non-condensing |
Up to 93 percent relative humidity. |
For optimal data center rack cooling, 45 to 50 percent, non-condensing. |
Altitude |
3048 meters (10000 feet) maximum |
12000 meters (40000 feet). |
Ambient temperature is reduced by 1 degree Celsius per 300 m above 900 m altitude above sea level. |