Space
All Oracle Cloud at Customer models use the same rack, and have the same space requirements.
The space requirements are as follows:
Table 2-1 Oracle Cloud at Customer Space Requirements
Description | Measurement |
---|---|
Height |
1998 mm |
78.66 inches | |
Minimum ceiling height for the cabinet (measured from true or raised floor) |
2914 mm (rack height of 2000 mm + 914 mm for maintenance access) |
114 inches (rack height of 78 inches + 36 inches for maintenance access) | |
Width |
600 mm with side panels |
23.62 inches | |
Required space to remove the side panels |
675. 64 mm |
26.6 inches | |
Depth from front door handle to rear door handle |
1200 mm |
47.24 inches | |
Depth with doors removed |
1112 mm |
43.78 inches | |
Top, front, and rear maintenance access requirement |
914 mm |
36 inches |
Note:
For non-raised floor installations, the installation site AC power receptacle must be routed to the top of the rack and within 2000 mm (78.74 inches) of the top of the rack.