1.2.7 General Environmental Requirements for Oracle Exadata Database Machine X3-2

The environmental requirements for Oracle Exadata Database Machine X3-2 depend on the size of the system. Table 1-6 shows the general environmental requirements for Oracle Exadata Database Machine X3-2. The other sections in this chapter provide detailed information.

Table 1-6 Environmental Requirements for Oracle Exadata Database Machine X3-2

Environmental Component Oracle Exadata Database Machine X3-2 Full Rack Oracle Exadata Database Machine X3-2 Half Rack Oracle Exadata Database Machine X3-2 Quarter Rack Oracle Exadata Database Machine Eighth Rack

Weight

See Also: "Flooring Requirements"

871.4 kg (1921 lbs)

543.9 kg (1199 lbs)

368.8 kg (813 lbs)

368.8 kg (813 lbs)

Acoustic levels

87 db(A)

84 db(A)

81 db(A)

81 db(A)

Power

See Also: "Electrical Power Requirements"

  • High performance drives

    Maximum: 12.1 kVA

    Typical: 8.6 kVA (varies based on application load)

  • High capacity drives

    Maximum: 11.1 kVA

    Typical: 7.8 kVA (varies based on application load)

  • High performance drives

    Maximum: 6.6 kVA

    Typical: 4.7 kVA (varies based on application load)

  • High capacity drives

    Maximum: 6.1 kVA

    Typical: 4.3 kVA (varies based on application load)

  • High performance drives

    Maximum: 3.3 kVA

    Typical: 2.4 kVA (varies based on application load)

  • High capacity drives

    Maximum: 3.1 kVA

    Typical: 2.2 kVA (varies based on application load)

  • High performance drives

    Maximum: 3.0 kVA

    Typical: 2.1 kVA (varies based on application load)

  • High capacity drives

    Maximum: 2.8 kVA

    Typical: 2.0 kVA (varies based on application load)

Cooling

See Also: "Temperature and Humidity Requirements", and "Ventilation and Cooling Requirements"

  • High performance drives

    Maximum: 40,600 BTU/hour (42,800 kJ/hour)

    Typical: 28,700 BTU/hour (30,300 kJ/hour)

  • High capacity drives

    Maximum: 37,200 BTU/hour (39,250 kJ/hour)

    Typical: 26,000 BTU/hour (27,400 kJ/hour)

  • High performance drives

    Maximum: 22,200 BTU/hour (23,400 kJ/hour)

    Typical: 15,700 BTU/hour (16,600 kJ/hour)

  • High capacity drives

    Maximum: 20,500 BTU/hour (21,600 kJ/hour)

    Typical: 14,300 BTU/hour (15,100 kJ/hour)

  • High performance drives

    Maximum: 10,900 BTU/hour (11,500 kJ/hour)

    Typical: 7,850 BTU/hour (8,300 kJ/hour)

  • High capacity drives

    Maximum: 10,200 BTU/hour (10,800 kJ/hour)

    Typical: 7,200 BTU/hour (7,600 kJ/hour)

  • High performance drives

    Maximum: 9,900 BTU/hour (10,500 kJ/hour)

    Typical: 6,800 BTU/hour (7,200 kJ/hour)

  • High capacity drives

    Maximum: 9,200 BTU/hour (9,700 kJ/hour)

    Typical: 6,500 BTU/hour (6,850 kJ/hour)

Air flow front-to-back (subject to actual data center environment)

See Also: "Temperature and Humidity Requirements", and "Ventilation and Cooling Requirements"

  • High performance drives

    Maximum: Approximately 1,900 CFM

    Typical: Approximately 1,350 CFM

  • High capacity drives

    Maximum: Approximately 1,700 CFM

    Typical: Approximately 1,200 CFM

  • High performance drives

    Maximum: Approximately 1,050 CFM

    Typical: Approximately 750 CFM

  • High capacity drives

    Maximum: Approximately 950 CFM

    Typical: Approximately 670 CFM

  • High performance drives

    Maximum: Approximately 500 CFM

    Typical: Approximately 375 CFM

  • High capacity drives

    Maximum: Approximately 470 CFM

    Typical: Approximately 330 CFM

  • High performance drives

    Maximum: Approximately 460 CFM

    Typical: Approximately 325 CFM

  • High capacity drives

    Maximum: Approximately 425 CFM

    Typical: Approximately 300 CFM

IP Addresses

See Also: "Network Connection and IP Address Requirements for Oracle Exadata Database Machine"

69 for Ethernet network, assuming single cluster

22 for InfiniBand network

39 for Ethernet network, assuming single cluster (39 IP addresses are needed for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers))

11 for InfiniBand network

22 for Ethernet network, assuming single cluster

5 for InfiniBand network

22 for Ethernet network, assuming single cluster

5 for InfiniBand network

Network drops

See Also: "Network Connection and IP Address Requirements for Oracle Exadata Database Machine"

Minimum of 11 network drops

Minimum of 7 network drops

Minimum of 5 network drops

Minimum of 5 network drops

External connectivity

See Also: "Network Connection and IP Address Requirements for Oracle Exadata Database Machine"

24 x 1 GbE/10 GbE Ethernet ports

16 x 10 GbE Ethernet ports

At least 12 InfiniBand ports

12 x 1 GbE/10 GbE Ethernet ports

8 x 10 GbE Ethernet ports

At least 12 InfiniBand ports

6 x 1 GbE/10 GbE Ethernet ports

4 x 10 GbE Ethernet ports

At least 12 InfiniBand ports

6 x 1 GbE/10 GbE Ethernet ports

4 x 10 GbE Ethernet ports

At least 12 InfiniBand ports