1.2.7 General Environmental Requirements for Oracle Exadata Database Machine X3-2
The environmental requirements for Oracle Exadata Database Machine X3-2 depend on the size of the system. Table 1-6 shows the general environmental requirements for Oracle Exadata Database Machine X3-2. The other sections in this chapter provide detailed information.
Table 1-6 Environmental Requirements for Oracle Exadata Database Machine X3-2
Environmental Component | Oracle Exadata Database Machine X3-2 Full Rack | Oracle Exadata Database Machine X3-2 Half Rack | Oracle Exadata Database Machine X3-2 Quarter Rack | Oracle Exadata Database Machine Eighth Rack |
---|---|---|---|---|
Weight See Also: "Flooring Requirements" |
871.4 kg (1921 lbs) |
543.9 kg (1199 lbs) |
368.8 kg (813 lbs) |
368.8 kg (813 lbs) |
Acoustic levels |
87 db(A) |
84 db(A) |
81 db(A) |
81 db(A) |
Power See Also: "Electrical Power Requirements" |
|
|
|
|
Cooling See Also: "Temperature and Humidity Requirements", and "Ventilation and Cooling Requirements" |
|
|
|
|
Air flow front-to-back (subject to actual data center environment) See Also: "Temperature and Humidity Requirements", and "Ventilation and Cooling Requirements" |
|
|
|
|
See Also: "Network Connection and IP Address Requirements for Oracle Exadata Database Machine" |
69 for Ethernet network, assuming single cluster 22 for InfiniBand network |
39 for Ethernet network, assuming single cluster (39 IP addresses are needed for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers)) 11 for InfiniBand network |
22 for Ethernet network, assuming single cluster 5 for InfiniBand network |
22 for Ethernet network, assuming single cluster 5 for InfiniBand network |
Network drops See Also: "Network Connection and IP Address Requirements for Oracle Exadata Database Machine" |
Minimum of 11 network drops |
Minimum of 7 network drops |
Minimum of 5 network drops |
Minimum of 5 network drops |
External connectivity See Also: "Network Connection and IP Address Requirements for Oracle Exadata Database Machine" |
24 x 1 GbE/10 GbE Ethernet ports 16 x 10 GbE Ethernet ports At least 12 InfiniBand ports |
12 x 1 GbE/10 GbE Ethernet ports 8 x 10 GbE Ethernet ports At least 12 InfiniBand ports |
6 x 1 GbE/10 GbE Ethernet ports 4 x 10 GbE Ethernet ports At least 12 InfiniBand ports |
6 x 1 GbE/10 GbE Ethernet ports 4 x 10 GbE Ethernet ports At least 12 InfiniBand ports |
Parent topic: General Environmental Requirements