1.2.4 General Environmental Requirements for Oracle Exadata Database Machine X4-2

The environmental requirements for Oracle Exadata Database Machine X4-2 depend on the size of the system. Table 1-3 shows the general environmental requirements for Oracle Exadata Database Machine X4-2. The other sections in this chapter provide detailed information.

Table 1-3 Environmental Requirements for Oracle Exadata Database Machine X4-2

Environmental Component Oracle Exadata Database Machine X4-2 Full Rack Oracle Exadata Database Machine X4-2 Half Rack Oracle Exadata Database Machine X4-2 Quarter Rack Oracle Exadata Database Machine X4-2 Eighth Rack

Weight

See Also: "Flooring Requirements"

852.8 kg (1880 lbs)

525.3 kg (1158 lbs)

365.6 kg (806 lbs)

365.6 kg (806 lbs)

Acoustic levels

93 db(A)

89 db(A)

85 db(A)

85 db(A)

Power

See Also: "Electrical Power Requirements"

  • High performance drives

    Maximum: 12.4 kVA

    Typical: 8.7 kVA (varies based on application load)

  • High capacity drives

    Maximum: 11.4 kVA

    Typical: 8.1 kVA (varies based on application load)

  • High performance drives

    Maximum: 6.8 kVA

    Typical: 4.8 kVA (varies based on application load)

  • High capacity drives

    Maximum: 6.3 kVA

    Typical: 4.4 kVA (varies based on application load)

  • High performance drives

    Maximum: 3.4 kVA

    Typical: 2.5 kVA (varies based on application load)

  • High capacity drives

    Maximum: 3.2 kVA

    Typical: 2.3 kVA (varies based on application load)

  • High performance drives

    Maximum: 3.1 kVA

    Typical: 2.2 kVA (varies based on application load)

  • High capacity drives

    Maximum: 2.9 kVA

    Typical: 2.1 kVA (varies based on application load)

Cooling

See Also: "Temperature and Humidity Requirements", and "Ventilation and Cooling Requirements"

  • High performance drives

    Maximum: 41,300 BTU/hour (43,600 kJ/hour)

    Typical: 29,000 BTU/hour (30,600 kJ/hour)

  • High capacity drives

    Maximum: 38,300 BTU/hour (40,400 kJ/hour)

    Typical: 27,000 BTU/hour (28,500 kJ/hour)

  • High performance drives

    Maximum: 22,500 BTU/hour (23,750 kJ/hour)

    Typical: 16,000 BTU/hour (16,900 kJ/hour)

  • High capacity drives

    Maximum: 21,200 BTU/hour (22,400 kJ/hour)

    Typical: 14,700 BTU/hour (15,500 kJ/hour)

  • High performance drives

    Maximum: 11,300 BTU/hour (11,900 kJ/hour)

    Typical: 8,200 BTU/hour (8,700 kJ/hour)

  • High capacity drives

    Maximum: 10,600 BTU/hour (11,200 kJ/hour)

    Typical: 7,500 BTU/hour (7,900 kJ/hour)

  • High performance drives

    Maximum: 10,200 BTU/hour (10,700 kJ/hour)

    Typical: 7,100 BTU/hour (7,500 kJ/hour)

  • High capacity drives

    Maximum: 9,500 BTU/hour (10,000 kJ/hour)

    Typical: 6,600 BTU/hour (7,000 kJ/hour)

Air flow front-to-back (subject to actual data center environment)

See Also: "Temperature and Humidity Requirements", and "Ventilation and Cooling Requirements"

  • High performance drives

    Maximum: Approximately 1,900 CFM

    Typical: Approximately 1,350 CFM

  • High capacity drives

    Maximum: Approximately 1,780 CFM

    Typical: Approximately 1,250 CFM

  • High performance drives

    Maximum: Approximately 1,050 CFM

    Typical: Approximately 750 CFM

  • High capacity drives

    Maximum: Approximately 980 CFM

    Typical: Approximately 680 CFM

  • High performance drives

    Maximum: Approximately 520 CFM

    Typical: Approximately 365 CFM

  • High capacity drives

    Maximum: Approximately 490 CFM

    Typical: Approximately 350 CFM

  • High performance drives

    Maximum: Approximately 470 CFM

    Typical: Approximately 325 CFM

  • High capacity drives

    Maximum: Approximately 440 CFM

    Typical: Approximately 310 CFM

IP Addresses

See Also: "Network Connection and IP Address Requirements for Oracle Exadata Database Machine"

68 for Ethernet network, assuming single cluster

Up to 36 for InfiniBand network

38 for Ethernet network, assuming single cluster

Up to 18 for InfiniBand network

22 for Ethernet network, assuming single cluster

Up to 8 for InfiniBand network

22 for Ethernet network, assuming single cluster

Up to 8 for InfiniBand network

Network drops

See Also: "Network Connection and IP Address Requirements for Oracle Exadata Database Machine"

Minimum of 11 network drops

Minimum of 7 network drops

Minimum of 5 network drops

Minimum of 5 network drops

External connectivity

See Also: "Network Connection and IP Address Requirements for Oracle Exadata Database Machine"

18 x 1 GbE/10 GbE Ethernet ports

16 x 10 GbE Ethernet ports

At least 12 InfiniBand ports

12 x 1 GbE/10 GbE Ethernet ports

8 x 10 GbE Ethernet ports

At least 12 InfiniBand ports

6 x 1 GbE/10 GbE Ethernet ports

4 x 10 GbE Ethernet ports

At least 12 InfiniBand ports

6 x 1 GbE/10 GbE Ethernet ports

4 x 10 GbE Ethernet ports

At least 12 InfiniBand ports