1.7.1.2 Low-Voltage 22 kVA Single Phase PDU for North America, South America, Japan and Taiwan

Note:

The following specifications are for a single PDU. Every Oracle Exadata Rack configuration contains two PDUs.

Table 1-27 Specifications for each Low-Voltage 22 kVA Single Phase PDU for North America, South America, Japan and Taiwan

Specification Value
Number of Inputs 3
Source Voltage 200-240V
Frequency 50/60 Hz
Max Line Current 36.8A
Phase Current N/A
Nominal Power Rating 22kVA
Recommended Circuit Breaker 50A
Outlets 42 x C13, 6 x C19
Outlet Groups 6
Max Group Current 20A
Output Voltage 200-240V
Data Center Receptacle 1ph 2W + ground 30A NEMA L6-30