1.7.1.3 Low-Voltage 15 kVA Three Phase PDU for North America, South America, Japan and Taiwan

Note:

The following specifications are for a single PDU. Every Oracle Exadata Rack configuration contains two PDUs.

Table 1-28 Specifications for each Low-Voltage 15 kVA Three Phase PDU for North America, South America, Japan and Taiwan

Specification Value
Number of Inputs 1
Source Voltage 200-220V
Frequency 50/60 Hz
Max Line Current 40A
Phase Current 23A
Nominal Power Rating 15kVA
Recommended Circuit Breaker 50A
Outlets 42 x C13, 6 x C19
Outlet Groups 6
Max Group Current 20A
Output Voltage 200-240V
Data Center Receptacle 3ph 3W + ground 60A IEC60309