1.7.1.4 Low-Voltage 24 kVA Three Phase PDU for North America, South America, Japan and Taiwan

Note:

The following specifications are for a single PDU. Every Oracle Exadata Rack configuration contains two PDUs.

Table 1-29 Specifications for each Low-Voltage 24 kVA Three Phase PDU for North America, South America, Japan and Taiwan

Specification Value
Number of Inputs 2
Source Voltage 200-220V
Frequency 50/60 Hz
Max Line Current 34.6A
Phase Current 20A
Nominal Power Rating 24kVA
Recommended Circuit Breaker 50A
Outlets 42 x C13, 6 x C19
Outlet Groups 6
Max Group Current 20A
Output Voltage 200-240V
Data Center Receptacle 3ph 3W + ground 60A IEC60309