6.6.3.1 PDU Thresholds for Oracle Exadata Database Machine X3-2 Full Rack

The following tables list the threshold values for Oracle Exadata Database Machine X3-2 Full Rack:

  • Table 6-13 Threshold Values for Oracle Exadata Database Machine X3-2 Full Rack with Single-phase, Low-voltage PDU

  • Table 6-14 Threshold Values for Oracle Exadata Database Machine X3-2 Full Rack with Three-phase, Low-voltage PDU

  • Table 6-15 Threshold Values for Oracle Exadata Database Machine X3-2 Full Rack with Single-phase, High-voltage PDU

  • Table 6-16

    Threshold Values for Oracle Exadata Database Machine X3-2 Full Rack with Three-phase, High-voltage PDU

Table 6-13 lists the threshold values for Oracle Exadata Database Machine X3-2 Full Rack using a single-phase, low-voltage PDU.

Table 6-13 Threshold Values for Oracle Exadata Database Machine X3-2 Full Rack with Single-phase, Low-voltage PDU

PDU Module/Phase Info Low Threshold Pre Warning Threshold Alarm Threshold

A

Module 1, phase 1

0

20

24

A

Module 1, phase 2

0

14

18

A

Module 1, phase 3

0

19

24

B

Module 1, phase 1

0

19

24

B

Module 1, phase 2

0

14

18

B

Module 1, phase 3

0

20

24

Table 6-14 lists the threshold values for Oracle Exadata Database Machine X3-2 Full Rack using a three-phase, low-voltage PDU.

Table 6-14 Threshold Values for Oracle Exadata Database Machine X3-2 Full Rack with Three-phase, Low-voltage PDU

PDU Module/Phase Info Low Threshold Pre Warning Threshold Alarm Threshold

A and B

Module 1, phase 1

0

30

38

A and B

Module 1, phase 2

0

32

40

A and B

Module 1, phase 3

0

30

38

Table 6-15 lists the threshold values for Oracle Exadata Database Machine X3-2 Full Rack using a single-phase, high-voltage PDU.

Table 6-15 Threshold Values for Oracle Exadata Database Machine X3-2 Full Rack with Single-phase, High-voltage PDU

PDU Module/Phase Info Low Threshold Pre Warning Threshold Alarm Threshold

A

Module 1, phase 1

0

18

23

A

Module 1, phase 2

0

13

17

A

Module 1, phase 3

0

18

22

B

Module 1, phase 1

0

18

22

B

Module 1, phase 2

0

13

17

B

Module 1, phase 3

0

18

23

Table 6-16 lists the threshold values for Oracle Exadata Database Machine X3-2 Full Rack using a three-phase, high-voltage PDU.

Table 6-16 Threshold Values for Oracle Exadata Database Machine X3-2 Full Rack with Three-phase, High-voltage PDU

PDU Module/Phase Info Low Threshold Pre Warning Threshold Alarm Threshold

A and B

Module 1, phase 1

0

17

21

A and B

Module 1, phase 2

0

17

21

A and B

Module 1, phase 3

0

15

19