6.6.9.3 PDU Thresholds for Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
The following tables list the threshold values for Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers:
-
Table 6-65 Threshold Values for Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers with Single-phase, Low-voltage PDU
-
Table 6-66 Threshold Values for Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers with Three-phase, Low-voltage PDU
-
Table 6-67 Threshold Values for Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers with Single-phase, High-voltage PDU
-
Table 6-68 Threshold Values for Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers with Three-phase, High-voltage PDU
Table 6-65 lists the threshold values for Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers using a single-phase, low-voltage PDU.
Table 6-65 Threshold Values for Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers with Single-phase, Low-voltage PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A |
Module 1, phase 1 |
0 |
10 |
13 |
A |
Module 1, phase 2 |
0 |
6 |
8 |
A |
Module 1, phase 3 |
0 |
0 |
0 |
B |
Module 1, phase 1 |
0 |
0 |
0 |
B |
Module 1, phase 2 |
0 |
6 |
8 |
B |
Module 1, phase 3 |
0 |
10 |
13 |
Table 6-66 lists the threshold values for Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers using a three-phase, low-voltage PDU.
Table 6-66 Threshold Values for Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers with Three-phase, Low-voltage PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A and B |
Module 1, phase 1 |
0 |
12 |
15 |
A and B |
Module 1, phase 2 |
0 |
11 |
14 |
A and B |
Module 1, phase 3 |
0 |
5 |
7 |
Table 6-67 lists the threshold values for Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers using a single-phase, high-voltage PDU.
Table 6-67 Threshold Values for Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers with Single-phase, High-voltage PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A |
Module 1, phase 1 |
0 |
9 |
12 |
A |
Module 1, phase 2 |
0 |
5 |
7 |
A |
Module 1, phase 3 |
0 |
0 |
0 |
B |
Module 1, phase 1 |
0 |
0 |
0 |
B |
Module 1, phase 2 |
0 |
5 |
7 |
B |
Module 1, phase 3 |
0 |
9 |
12 |
Table 6-68 lists the threshold values for Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers using a three-phase, high-voltage PDU.
Table 6-68 Threshold Values for Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers with Three-phase, High-voltage PDU
PDU | Module/Phase | Info Low Threshold | Pre Warning Threshold | Alarm Threshold |
---|---|---|---|---|
A and B |
Module 1, phase 1 |
0 |
9 |
12 |
A and B |
Module 1, phase 2 |
0 |
3 |
4 |
A and B |
Module 1, phase 3 |
0 |
4 |
5 |