6.8 Eight-Rack Cabling with InfiniBand Network Fabric

Note the following when cabling eight racks together with InfiniBand Network Fabric:

  • The spine switch is in U1 (also referred to as IB1) for all racks.

  • In the following tables, the leaf switches are referred to as IB2 and IB3. Use the rack unit that is appropriate for your system.

  • In Oracle Exadata Database Machine X2-2 racks and Oracle Exadata Storage Expansion Racks with Exadata Storage Server with Sun Fire X4270 M2 Servers, the leaf switches are in U20 and U24, also referred to as IB2 and IB3, respectively.

  • In Oracle Exadata Database Machine X2-8 and later racks, the leaf switches are in U21 and U23, also referred to as IB2 and IB3, respectively.

  • In Oracle Exadata Database Machine X4-2 and later racks, or Oracle Exadata Database Machine X3-2 Full Racks and Oracle Exadata Storage Expansion Rack X3-2 racks, the leaf switches are in U20 and U22, also referred to as IB2 and IB3, respectively.

  • The cable lengths shown in the tables assume the racks are adjacent to each other. If the racks are not adjacent or use overhead cabling trays, then they may require longer cables lengths. Up to 100 meters is supported.

  • Only optical cables are supported for lengths greater than 5 meters.

Table 6-28 shows the cable connections for the first spine switch (R1-U1) when cabling eight racks together:

Table 6-28 Leaf Switch Connections for the First Rack in a Eight-Rack System

Leaf Switch Connection Cable Length

R1 IB3 within Rack 1

R1-IB3-P8A to R1-U1-P3A

3 meters

R1 IB3 to Rack 2

R1-IB3-P8B to R2-U1-P4A

5 meters

R1 IB3 to Rack 3

R1-IB3-P9A to R3-U1-P5A

5 meters

R1 IB3 to Rack 4

R1-IB3-P9B to R4-U1-P6A

10 meters

R1 IB3 to Rack 5

R1-IB3-P10A to R5-U1-P7A

10 meters

R1 IB3 to Rack 6

R1-IB3-P10B to R6-U1-P8A

10 meters

R1 IB3 to Rack 7

R1-IB3-P11A to R7-U1-P9A

10 meters

R1 IB3 to Rack 8

R1-IB3-P11B to R8-U1-P10A

10 meters

R1 IB2 within Rack 1

R1-IB2-P8A to R1-U1-P3B

3 meters

R1 IB2 to Rack 2

R1-IB2-P8B to R2-U1-P4B

5 meters

R1 IB2 to Rack 3

R1-IB2-P9A to R3-U1-P5B

5 meters

R1 IB2 to Rack 4

R1-IB2-P9B to R4-U1-P6B

10 meters

R1 IB2 to Rack 5

R1-IB2-P10A to R5-U1-P7B

10 meters

R1 IB2 to Rack 6

R1-IB2-P10B to R6-U1-P8B

10 meters

R1 IB2 to Rack 7

R1-IB2-P11A to R7-U1-P9B

10 meters

R1 IB2 to Rack 8

R1-IB2-P11B to R8-U1-P10B

10 meters

Table 6-29 shows the cable connections for the second spine switch (R2-U1) when cabling eight full racks together:

Table 6-29 Leaf Switch Connections for the Second Rack in a Eight-Rack System

Leaf Switch Connection Cable Length

R2 IB3 within Rack 2

R2-IB3-P8A to R2-U1-P3A

3 meters

R2 IB3 to Rack 1

R2-IB3-P11B to R1-U1-P10A

5 meters

R2 IB3 to Rack 3

R2-IB3-P8B to R3-U1-P4A

5 meters

R2 IB3 to Rack 4

R2-IB3-P9A to R4-U1-P5A

5 meters

R2 IB3 to Rack 5

R2-IB3-P9B to R5-U1-P6A

10 meters

R2 IB3 to Rack 6

R2-IB3-P10A to R6-U1-P7A

10 meters

R2 IB3 to Rack 7

R2-IB3-P10B to R7-U1-P8A

10 meters

R2 IB3 to Rack 8

R2-IB3-P11A to R8-U1-P9A

10 meters

R2 IB2 within Rack 2

R2-IB2-P8A to R2-U1-P3B

3 meters

R2 IB2 to Rack 1

R2-IB2-P11B to R1-U1-P10B

5 meters

R2 IB2 to Rack 3

R2-IB2-P8B to R3-U1-P4B

5 meters

R2 IB2 to Rack 4

R2-IB2-P9A to R4-U1-P5B

5 meters

R2 IB2 to Rack 5

R2-IB2-P9B to R5-U1-P6B

10 meters

R2 IB2 to Rack 6

R2-IB2-P10A to R6-U1-P7B

10 meters

R2 IB2 to Rack 7

R2-IB2-P10B to R7-U1-P8B

10 meters

R2 IB2 to Rack 8

R2-IB2-P11A to R8-U1-P9B

10 meters

Table 6-30 shows the cable connections for the third spine switch (R3-U1) when cabling eight full racks together:

Table 6-30 Leaf Switch Connections for the Third Rack in a Eight-Rack System

Leaf Switch Connection Cable Length

R3 IB3 within Rack 3

R3-IB3-P8A to R3-U1-P3A

3 meters

R3 IB3 to Rack 1

R3-IB3-P11A to R1-U1-P9A

5 meters

R3 IB3 to Rack 2

R3-IB3-P11B to R2-U1-P10A

5 meters

R3 IB3 to Rack 4

R3-IB3-P8B to R4-U1-P4A

5 meters

R3 IB3 to Rack 5

R3-IB3-P9A to R5-U1-P5A

5 meters

R3 IB3 to Rack 6

R3-IB3-P9B to R6-U1-P6A

10 meters

R3 IB3 to Rack 7

R3-IB3-P10A to R7-U1-P7A

10 meters

R3 IB3 to Rack 8

R3-IB3-P10B to R8-U1-P8A

10 meters

R3 IB2 within Rack 3

R3-IB2-P8A to R3-U1-P3B

3 meters

R3 IB2 to Rack 1

R3-IB2-P11A to R1-U1-P9B

5 meters

R3 IB2 to Rack 2

R3-IB2-P11B to R2-U1-P10B

5 meters

R3 IB2 to Rack 4

R3-IB2-P8B to R4-U1-P4B

5 meters

R3 IB2 to Rack 5

R3-IB2-P9A to R5-U1-P5B

5 meters

R3 IB2 to Rack 6

R3-IB2-P9B to R6-U1-P6B

10 meters

R3 IB2 to Rack 7

R3-IB2-P10A to R7-U1-P7B

10 meters

R3 IB2 to Rack 8

R3-IB2-P10B to R8-U1-P8B

10 meters

Table 6-31 shows the cable connections for the fourth spine switch (R4-U1) when cabling eight full racks together:

Table 6-31 Leaf Switch Connections for the Fourth Rack in a Eight-Rack System

Leaf Switch Connection Cable Length

R4 IB3 within Rack 4

R4-IB3-P8A to R4-U1-P3A

3 meters

R4 IB3 to Rack 1

R4-IB3-P10B to R1-U1-P8A

10 meters

R4 IB3 to Rack 2

R4-IB3-P11A to R2-U1-P9A

5 meters

R4 IB3 to Rack 3

R4-IB3-P11B to R3-U1-P10A

5 meters

R4 IB3 to Rack 5

R4-IB3-P8B to R5-U1-P4A

5 meters

R4 IB3 to Rack 6

R4-IB3-P9A to R6-U1-P5A

5 meters

R4 IB3 to Rack 7

R4-IB3-P9B to R7-U1-P6A

10 meters

R4 IB3 to Rack 8

R4-IB3-P10A to R8-U1-P7A

10 meters

R4 IB2 within Rack 4

R4-IB2-P8A to R4-U1-P3B

3 meters

R4 IB2 to Rack 1

R4-IB2-P10B to R1-U1-P8B

10 meters

R4 IB2 to Rack 2

R4-IB2-P11A to R2-U1-P9B

5 meters

R4 IB2 to Rack 3

R4-IB2-P11B to R3-U1-P10B

5 meters

R4 IB2 to Rack 5

R4-IB2-P8B to R5-U1-P4B

5 meters

R4 IB2 to Rack 6

R4-IB2-P9A to R6-U1-P5B

5 meters

R4 IB2 to Rack 7

R4-IB2-P9B to R7-U1-P6B

10 meters

R4 IB2 to Rack 8

R4-IB2-P10A to R8-U1-P7B

10 meters

Table 6-32 shows the cable connections for the fifth spine switch (R5-U1) when cabling eight full racks together:

Table 6-32 Leaf Switch Connections for the Fifth Rack in a Eight-Rack System

Leaf Switch Connection Cable Length

R5 IB3 within Rack 5

R5-IB3-P8A to R5-U1-P3A

3 meters

R5 IB3 to Rack 1

R5-IB3-P10A to R1-U1-P7A

10 meters

R5 IB3 to Rack 2

R5-IB3-P10B to R2-U1-P8A

10 meters

R5 IB3 to Rack 3

R5-IB3-P11A to R3-U1-P9A

5 meters

R5 IB3 to Rack 4

R5-IB3-P11B to R4-U1-P10A

5 meters

R5 IB3 to Rack 6

R5-IB3-P8B to R6-U1-P4A

5 meters

R5 IB3 to Rack 7

R5-IB3-P9A to R7-U1-P5A

5 meters

R5 IB3 to Rack 8

R5-IB3-P9B to R8-U1-P6A

10 meters

R5 IB2 within Rack 5

R5-IB2-P8A to R5-U1-P3B

3 meters

R5 IB2 to Rack 1

R5-IB2-P10A to R1-U1-P7B

10 meters

R5 IB2 to Rack 2

R5-IB2-P10B to R2-U1-P8B

10 meters

R5 IB2 to Rack 3

R5-IB2-P11A to R3-U1-P9B

5 meters

R5 IB2 to Rack 4

R5-IB2-P11B to R4-U1-P10B

5 meters

R5 IB2 to Rack 6

R5-IB2-P8B to R6-U1-P4B

5 meters

R5 IB2 to Rack 7

R5-IB2-P9A to R7-U1-P5B

5 meters

R5 IB2 to Rack 8

R5-IB2-P9B to R8-U1-P6B

10 meters

Table 6-33 shows the cable connections for the sixth spine switch (R6-U1) when cabling eight full racks together:

Table 6-33 Leaf Switch Connections for the Sixth Rack in a Eight-Rack System

Leaf Switch Connection Cable Length

R6 IB3 within Rack 6

R6-IB3-P8A to R6-U1-P3A

3 meters

R6 IB3 to Rack 1

R6-IB3-P9B to R1-U1-P6A

10 meters

R6 IB3 to Rack 2

R6-IB3-P10A to R2-U1-P7A

10 meters

R6 IB3 to Rack 3

R6-IB3-P10B to R3-U1-P8A

10 meters

R6 IB3 to Rack 4

R6-IB3-P11A to R4-U1-P9A

5 meters

R6 IB3 to Rack 5

R6-IB3-P11B to R5-U1-P10A

5 meters

R6 IB3 to Rack 7

R6-IB3-P8B to R7-U1-P4A

5 meters

R6 IB3 to Rack 8

R6-IB3-P9A to R8-U1-P5A

5 meters

R6 IB2 within Rack 6

R6-IB2-P8A to R6-U1-P3B

3 meters

R6 IB2 to Rack 1

R6-IB2-P9B to R1-U1-P6B

10 meters

R6 IB2 to Rack 2

R6-IB3-P10A to R2-U1-P7B

10 meters

R6 IB2 to Rack 3

R6-IB2-P10B to R3-U1-P8B

10 meters

R6 IB2 to Rack 4

R6-IB2-P11A to R4-U1-P9B

5 meters

R6 IB2 to Rack 5

R6-IB2-P11B to R5-U1-P10B

5 meters

R6 IB2 to Rack 7

R6-IB2-P8B to R7-U1-P4B

5 meters

R6 IB2 to Rack 8

R6-IB2-P9A to R8-U1-P5B

5 meters

Table 6-34 shows the cable connections for the seventh spine switch (R7-U1) when cabling eight full racks together:

Table 6-34 Leaf Switch Connections for the Seventh Rack in a Eight-Rack System

Leaf Switch Connection Cable Length

R7 IB3 within Rack 7

R7-IB3-P8A to R7-U1-P3A

3 meters

R7 IB3 to Rack 1

R7-IB3-P9A to R1-U1-P5A

10 meters

R7 IB3 to Rack 2

R7-IB3-P9B to R2-U1-P6A

10 meters

R7 IB3 to Rack 3

R7-IB3-P10A to R3-U1-P7A

10 meters

R7 IB3 to Rack 4

R7-IB3-P10B to R4-U1-P8A

10 meters

R7 IB3 to Rack 5

R7-IB3-P11A to R5-U1-P9A

5 meters

R7 IB3 to Rack 6

R7-IB3-P11B to R6-U1-P10A

5 meters

R7 IB3 to Rack 8

R7-IB3-P8B to R8-U1-P4A

5 meters

R7 IB2 within Rack 7

R7-IB2-P8A to R7-U1-P3B

3 meters

R7 IB2 to Rack 1

R7-IB2-P9A to R1-U1-P5B

10 meters

R7 IB2 to Rack 2

R7-IB2-P9B to R2-U1-P6B

10 meters

R7 IB2 to Rack 3

R7-IB2-P10A to R3-U1-P7B

10 meters

R7 IB2 to Rack 4

R7-IB2-P10B to R4-U1-P8B

10 meters

R7 IB2 to Rack 5

R7-IB2-P11A to R5-U1-P9B

5 meters

R7 IB2 to Rack 6

R7-IB2-P11B to R6-U1-P10B

5 meters

R7 IB2 to Rack 8

R7-IB2-P8B to R8-U1-P4B

5 meters

Table 6-35 shows the cable connections for the eighth spine switch (R8-U1) when cabling eight full racks together:

Table 6-35 Leaf Switch Connections for the Eighth Rack in a Eight-Rack System

Leaf Switch Connection Cable Length

R8 IB3 within Rack 8

R8-IB3-P8A to R8-U1-P3A

3 meters

R8 IB3 to Rack 1

R8-IB3-P8B to R1-U1-P4A

10 meters

R8 IB3 to Rack 2

R8-IB3-P9A to R2-U1-P5A

10 meters

R8 IB3 to Rack 3

R8-IB3-P9B to R3-U1-P6A

10 meters

R8 IB3 to Rack 4

R8-IB3-P10A to R4-U1-P7A

10 meters

R8 IB3 to Rack 5

R8-IB3-P10B to R5-U1-P8A

10 meters

R8 IB3 to Rack 6

R8-IB3-P11A to R6-U1-P9A

5 meters

R8 IB3 to Rack 7

R8-IB3-P11B to R7-U1-P10A

5 meters

R8 IB2 within Rack 8

R8-IB2-P8A to R8-U1-P3B

3 meters

R8 IB2 to Rack 1

R8-IB2-P8B to R1-U1-P4B

10 meters

R8 IB2 to Rack 2

R8-IB2-P9A to R2-U1-P5B

10 meters

R8 IB2 to Rack 3

R8-IB2-P9B to R3-U1-P6B

10 meters

R8 IB2 to Rack 4

R8-IB2-P10A to R4-U1-P7B

10 meters

R8 IB2 to Rack 5

R8-IB2-P10B to R5-U1-P8B

10 meters

R8 IB2 to Rack 6

R8-IB2-P11A to R6-U1-P9B

5 meters

R8 IB2 to Rack 7

R8-IB2-P11B to R7-U1-P10B

5 meters