17.4.4 Single Phase PDU Cabling for Oracle Exadata Database Machine X7-8 Full Rack
Single phase cabling for the Oracle Exadata Database Machine X7-8 Full Rack routes from each power distribution unit (PDU) to the power supplies.
The cables are terminated to PDU-A on the left, and routed to the right to enter CMA, and are bundled in groups of four.
Table 17-8 Single Phase PDU Cabling for Oracle Exadata Database Machine X7-8 Full Rack
| Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length | 
|---|---|---|---|
| U41 | G5-6 | G0-0 | 2 meters | 
| U39 | G5-4 | G0-2 | 2 meters | 
| U37 | G5-2 | G0-4 | 2 meters | 
| U35 | G5-0 | G0-6 | 2 meters | 
| U33 | G4-6 | G1-0 | 2 meters | 
| U31 | G4-3 | G1-3 | 2 meters | 
| U29 | G3-6 | G2-0 | 2 meters | 
| U24 | G4-7 (C19) (ACO) | G1-7 (C19) (AC1) | 1 meter | 
| U24 | G2-7 (C19) (AC2) | G3-7 (C19) (AC3) | 1 meter | 
| U23 | G3-1 | G2-5 | 2 meters | 
| U22 | G2-6 (PS-2) | G3-0 (PS-1) | 2 meters | 
| U21 | G3-0 | G2-6 | 2 meters | 
| U16 | G3-7 (C19) (AC0) | G2-7 (C19) (AC1) | 1 meter | 
| U16 | G1-7 (C19) (AC2) | G4-7 (C19) (AC3) | 1 meter | 
| U14 | G2-0 | G3-6 | 2 meters | 
| U12 | G1-3 | G4-3 | 2 meters | 
| U10 | G1-0 | G4-6 | 2 meters | 
| U8 | G0-6 | G5-0 | 2 meters | 
| U6 | G0-4 | G5-2 | 2 meters | 
| U4 | G0-3 | G5-3 | 2 meters | 
| U2 | G0-1 | G5-5 | 2 meters | 
| U1 | G0-0 | G5-6 | 2 meters | 
Parent topic: Single Phase Power Distribution Unit Cabling Tables