16.4.3 Single Phase PDU Cabling for Oracle Exadata Database Machine X7-2 Full Rack

Single phase cabling for the Exadata Database Machine X7-2 Full Rack routes from each power distribution unit (PDU) to the power supplies.

The cables are terminated to PDU-A on the left, and routed to the right to enter CMA, and are bundled in groups of four.

Table 16-7 Single Phase PDU Cabling for Oracle Exadata Database Machine X7-2 Full Rack

Rack Unit PDU-A/PSU 0 PDU-B/PSU 1 Cable Length

U42

G5-5

G0-1

2 meters

U41

G3-6

G2-0

2 meters

U40

G5-2

G0-4

2 meters

U39

G5-6

G0-0

2 meters

U37

G5-3

G0-3

2 meters

U35

G5-1

G0-5

2 meters

U33

G5-0

G0-6

2 meters

U31

G4-4

G1-2

2 meters

U29

G4-3

G1-3

2 meters

U27

G3-5

G2-1

2 meters

U26

G4-5

G1-1

2 meters

U25

G4-2

G1-4

2 meters

U24

G4-1

G1-5

2 meters

U23

G2-5

G3-1

2 meters

U22

G1-4

G4-2

2 meters

U21

G1-3

G4-3

2 meters

U20

G1-5

G4-1

2 meters

U19

G2-3

G3-3

2 meters

U18

G2-2

G3-4

2 meters

U17

G1-6

G4-0

2 meters

U16

G1-2

G4-4

2 meters

U14

G2-4

G3-2

2 meters

U12

G2-1

G3-5

2 meters

U10

G2-0

G3-6

2 meters

U8

G1-0

G4-6

2 meters

U6

G0-6

G5-0

2 meters

U4

G0-4

G5-2

2 meters

U2

G0-2

G5-4

2 meters

U1

G4-0

G1-6

3 meters