16.4.2 Single Phase PDU Cabling for Oracle Exadata Database Machine X8-8 Full Rack

Single phase cabling for the Oracle Exadata Database Machine X8-8 Full Rack routes from each power distribution unit (PDU) to the power supplies.

The cables are terminated to PDU-A on the left (when looking at the rear of the rack), and routed to the right to enter CMA. The cables are bundled in groups of four. The PDU connections in the table below list the group and outlet on the PDU. So, for example, G5-5 refers to group 5 outlet 5.

Table 16-6 Single Phase PDU Cabling for Oracle Exadata Database Machine X8-8 Full Rack

Rack Unit PDU-A/PSU 0 PDU-B/PSU 1 Cable Length

U41

G3-5

G2-1

2 meters

U39

G5-4

G0-2

2 meters

U37

G5-2

G0-4

2 meters

U35

G5-0

G0-6

2 meters

U33

G4-6

G1-0

2 meters

U31

G4-3

G1-3

2 meters

U29

G3-6

G2-0

2 meters

U24

G2-7 (PS2)

G3-7 (PS3)

2 meters

U24

G4-7

G1-7

2 meters

U23

G3-1

G2-5

2 meters

U22

G2-6

G3-0

2 meters

U21

G3-0

G2-6

2 meters

U16

G1-7 (PS2)

G4-7 (PS3)

2 meters

U16

G3-7

G2-7

2 meters

U14 (only 2 DB servers)

G2-0

G3-6

2 meters

U12 (only 2 DB servers)

G1-3

G4-3

2 meters

U10 (only 2 DB servers)

G1-0

G4-6

2 meters

U10 (3 DB servers)

G0-7 (PS2)

G5-7 (PS3)

2 meters

U10 (3 DB servers)

G5-7

G0-7

2 meters

U8

G0-6

G5-0

2 meters

U6

G0-4

G5-2

2 meters

U4

G0-3

G5-3

2 meters

U2

G0-1

G5-5

2 meters

U1

G0-0

G5-6

3 meters