18.5 Three Phase Power Distribution Unit Cabling Tables

This section contains the tables for three phase cabling from each power distribution unit (PDU) to the power supplies configured in each rack. The cables are terminated to PDU-A on the left, and routed to the right to enter CMA, and are bundled in groups of four.

The following tables are in this section:

Table 18-13 shows the cable connections from the PDUs to the rack units in Oracle Exadata Database Machine X4-2 Full Rack.

Table 18-13 Three Phase PDU Cabling for Oracle Exadata Database Machine X4-2 Full Rack

Rack Unit PDU-A/PS-00 PDU-B/PS-01 Cable Length

U39

G5-6

G2-0

2 meters

U37

G5-3

G2-3

2 meters

U35

G5-0

G2-6

2 meters

U33

G4-6

G1-0

2 meters

U31

G4-4

G1-2

2 meters

U29

G4-2

G1-4

2 meters

U27

G3-6

G0-0

2 meters

U26

G4-0

G1-6

2 meters

U25

G3-5

G0-1

2 meters

U24

G3-4

G0-2

2 meters

U23

G3-3

G0-3

2 meters

U22

G3-1

G0-5

2 meter

U21

G3-0

G0-6

2 meters

U20

G2-4

G5-2

2 meters

U19

G2-3

G5-3

2 meters

U18

G2-2

G5-4

2 meters

U17

G2-1

G5-5

2 meters

U16

G1-6

G4-0

2 meters

U14

G2-0

G5-6

2 meters

U12

G1-4

G4-2

2 meters

U10

G1-2

G4-4

2 meters

U8

G1-0

G4-6

2 meters

U6

G0-6

G3-0

2 meters

U4

G0-4

G3-2

2 meters

U2

G0-2

G3-4

2 meters

Table 18-14 shows the cable connections from the PDUs to the rack units in Oracle Exadata Database Machine X4-2 Half Rack.

Table 18-14 Three Phase PDU Cabling for Oracle Exadata Database Machine X4-2 Half Rack

Rack Unit PDU-A/PS-00 PDU-B/PS-01 Cable Length

U22

G3-1

G0-5

2 meter

U21

G3-0

G0-6

2 meters

U20

G2-4

G5-2

2 meters

U19

G2-3

G5-3

2 meters

U18

G2-2

G5-4

2 meters

U17

G2-1

G5-5

2 meters

U16

G1-6

G4-0

2 meters

U14

G2-0

G5-6

2 meters

U12

G1-4

G4-2

2 meters

U10

G1-2

G4-4

2 meters

U8

G1-0

G4-6

2 meters

U6

G0-6

G3-0

2 meters

U4

G0-4

G3-2

2 meters

U2

G0-2

G3-4

2 meters

Table 18-15 shows the cable connections from the PDUs to the rack units in Oracle Exadata Database Machine X4-2 Quarter Rack.

Table 18-15 Three Phase PDU Cabling for Oracle Exadata Database Machine X4-2 Quarter Rack

Rack Unit PDU-A/PS-00 PDU-B/PS-01 Cable Length

U22

G3-1

G0-5

2 meter

U21

G3-0

G0-6

2 meters

U20

G2-4

G5-2

2 meters

U17

G2-1

G5-5

2 meters

U16

G1-6

G4-0

2 meters

U6

G0-6

G3-0

2 meters

U4

G0-4

G3-2

2 meters

U2

G0-2

G3-4

2 meters

Table 18-16 shows the cable connections from the PDUs to the rack units in Oracle Exadata Database Machine X4-8 Full Rack.

Table 18-16 Three Phase PDU Cabling for Oracle Exadata Database Machine X4-8 Full Rack

Rack Unit PDU-A/PS-00 PDU-B/PS-01 Cable Length

U41

G5-5

G2-1

2 meters

U39

G5-4

G2-2

2 meters

U37

G5-2

G2-4

2 meters

U35

G5-1

G2-5

2 meters

U33

G5-0

G2-6

2 meters

U31

G4-6

G1-0

2 meters

U29

G4-4

G1-2

2 meters

U24

AC0 to G4-7 (C19)

AC1 to G1-7 (C19)

1 meter

U24

AC2 to G3-7 (C19)

AC3 to G0-7 (C19)

1 meter

U23

G3-1

G0-5

2 meters

U22

G3-0

G0-6

2 meters

U21

G2-5

G5-1

2 meters

U16

AC0 to G1-7 (C19)

AC1 to G4-7 (C19)

1 meter

U16

AC2 to G2-7 (C19)

AC3 to G5-7 (C19)

1 meter

U14

G1-3

G4-3

2 meters

U12

G1-0

G4-6

2 meters

U10

G0-6

G3-0

2 meters

U8

G0-5

G3-1

2 meters

U6

G0-4

G3-2

2 meters

U4

G0-2

G3-4

2 meters

U2

G0-1

G3-5

2 meters

U1

G0-0

G3-6

2 meters