RDMA Network Fabric Switch-to-Server Cabling Connections

For InfiniBand Network Fabric,Table 17-8 lists the location, ports, and cables for the connections from the gateway leaf switches to the servers in a Recovery Appliance X8, X7, X6 or X5 full rack. The port numbers and cable lengths are the same in racks with fewer storage servers. The switches are located in rack units 20 and 22.

All cables are black quad data rate (QDR) cables.

Table 17-8 RDMA Network FabricSwitch-to-Server Cabling for the Recovery Appliance X8, X7, X6 or X5 Full Racks

From InfiniBand Switch Rack Unit(1) Port To Rack Unit Device Port Cable Length

U22

6B

U41

Storage server

PCIe 7, P1

3 meters

U22

0A

U39

Storage server

PCIe 7, P1

3 meters

U22

0B

U37

Storage server

PCIe 7, P1

3 meters

U22

1A

U35

Storage server

PCIe 7, P1

3 meters

U22

1B

U33

Storage server

PCIe 7, P1

3 meters

U22

2A

U31

Storage server

PCIe 7, P1

3 meters

U22

2B

U29

Storage server

PCIe 7, P1

3 meters

U22

3B

U27

Storage server

PCIe 7, P1

3 meters

U22

4A

U25

Storage server

PCIe 7, P1

2 meters

U22

5A

U23

Storage server

PCIe 7, P1

2 meters

U22

13A

U18

Storage server

PCIe 7, P2

2 meters

U22

13B

U17

Compute server

PCIe 7, P2

2 meters

U22

14B

U16

Compute server

PCIe 7, P2

2 meters

U22

14A

U14

Storage server

PCIe 7, P2

3 meters

U22

15A

U12

Storage server

PCIe 7, P2

3 meters

U22

15B

U10

Storage server

PCIe 7, P2

3 meters

U22

16A

U8

Storage server

PCIe 7, P2

3 meters

U22

16B

U6

Storage server

PCIe 7, P2

3 meters

U22

17A

U4

Storage server

PCIe 7, P2

3 meters

U22

17B

U2

Storage server

PCIe 7, P2

3 meters

U20

6B

U41

Storage server

PCIe 7, P2

3 meters

U20

0A

U39

Storage server

PCIe 7, P2

3 meters

U20

0B

U37

Storage server

PCIe 7, P2

3 meters

U20

1A

U35

Storage server

PCIe 7, P2

3 meters

U20

1B

U33

Storage server

PCIe 7, P2

3 meters

U20

2A

U31

Storage server

PCIe 7, P2

3 meters

U20

2B

U29

Storage server

PCIe 7, P2

3 meters

U20

3B

U27

Storage server

PCIe 7, P2

3 meters

U20

4A

U25

Storage server

PCIe 7, P2

2 meters

U20

5A

U23

Storage server

PCIe 7, P2

2 meters

U20

13A

U18

Storage server

PCIe 7, P1

2 meters

U20

13B

U17

Compute server

PCIe 2, P1

2 meters

U20

14B

U16

Compute server

PCIe 2, P1

2 meters

U20

14A

U14

Storage server

PCIe 7, P1

2 meters

U20

15A

U12

Storage server

PCIe 7, P1

3 meters

U20

15B

U10

Storage server

PCIe 7, P1

3 meters

U20

16A

U8

Storage server

PCIe 7, P1

3 meters

U20

16B

U6

Storage server

PCIe 7, P1

3 meters

U20

17A

U4

Storage server

PCIe 7, P1

3 meters

U20

17B

U2

Storage server

PCIe 7, P1

3 meters

Footnote 1 Un is the unit location in the rack, where n is the number.