Four-Rack Cabling with InfiniBand Network Fabric

Note the following when cabling four racks together with InfiniBand Network Fabric:

Table 24-6 shows the cable connections for the first spine switch (R1-U1) when cabling four racks together:

Table 24-6 Leaf Switch Connections for the First Rack in a Four-Rack System

Leaf Switch Connection Cable Length
R1 IB3 within Rack 1

R1-IB3-P8A to R1-U1-P3A

R1-IB3-P8B to R1-U1-P4A

3 meters
R1 IB3 to Rack 2

R1-IB3-P9A to R2-U1-P5A

R1-IB3-P9B to R2-U1-P6A

5 meters
R1 IB3 to Rack 3

R1-IB3-P10A to R3-U1-P7A

R1-IB3-P10B to R3-U1-P8A

5 meters
R1 IB3 to Rack 4

R1-IB3-P11A to R4-U1-P9A

R1-IB3-P11B to R4-U1-P10A

10 meters
R1 IB2 within Rack 1

R1-IB2-P8A to R1-U1-P3B

R1-IB2-P8B to R1-U1-P4B

3 meters
R1 IB2 to Rack 2

R1-IB2-P9A to R2-U1-P5B

R1-IB2-P9B to R2-U1-P6B

5 meters
R1 IB2 to Rack 3

R1-IB2-P10A to R3-U1-P7B

R1-IB2-P10B to R3-U1-P8B

5 meters
R1 IB2 to Rack 4

R1-IB2-P11A to R4-U1-P9B

R1-IB2-P11B to R4-U1-P10B

10 meters

Table 24-7 shows the cable connections for the second spine switch (R2-U1) when cabling four full racks together:

Table 24-7 Leaf Switch Connections for the Second Rack in a Four-Rack System

Leaf Switch Connection Cable Length
R2 IB3 within Rack 2

R2-IB3-P8A to R2-U1-P3A

R2-IB3-P8B to R2-U1-P4A

3 meters
R2 IB3 to Rack 1

R2-IB3-P11A to R1-U1-P9A

R2-IB3-P11B to R1-U1-P10A

5 meters
R2 IB3 to Rack 3

R2-IB3-P9A to R3-U1-P5A

R2-IB3-P9B to R3-U1-P6A

5 meters
R2 IB3 to Rack 4

R2-IB3-P10A to R4-U1-P7A

R2-IB3-P10B to R4-U1-P8A

5 meters
R2 IB2 within Rack 2

R2-IB2-P8A to R2-U1-P3B

R2-IB2-P8B to R2-U1-P4B

3 meters
R2 IB2 to Rack 1

R2-IB2-P11A to R1-U1-P9B

R2-IB2-P11B to R1-U1-P10B

5 meters
R2 IB2 to Rack 3

R2-IB2-P9A to R3-U1-P5B

R2-IB2-P9B to R3-U1-P6B

5 meters
R2 IB2 to Rack 4

R2-IB2-P10A to R4-U1-P7B

R2-IB2-P10B to R4-U1-P8B

5 meters

Table 24-8 shows the cable connections for the third spine switch (R3-U1) when cabling four full racks together:

Table 24-8 Leaf Switch Connections for the Third Rack in a Four-Rack System

Leaf Switch Connection Cable Length
R3 IB3 within Rack 3

R3-IB3-P8A to R3-U1-P3A

R3-IB3-P8B to R3-U1-P4A

3 meters
R3 IB3 to Rack 1

R3-IB3-P10A to R1-U1-P7A

R3-IB3-P10B to R1-U1-P8A

5 meters
R3 IB3 to Rack 2

R3-IB3-P11A to R2-U1-P9A

R3-IB3-P11B to R2-U1-P10A

5 meters
R3 IB3 to Rack 4

R3-IB3-P9A to R4-U1-P5A

R3-IB3-P9B to R4-U1-P6A

5 meters
R3 IB2 within Rack 3

R3-IB2-P8A to R3-U1-P3B

R3-IB2-P8B to R3-U1-P4B

3 meters
R3 IB2 to Rack 1

R3-IB2-P10A to R1-U1-P7B

R3-IB2-P10B to R1-U1-P8B

5 meters
R3 IB2 to Rack 2

R3-IB2-P11A to R2-U1-P9B

R3-IB2-P11B to R2-U1-P10B

5 meters
R3 IB2 to Rack 4

R3-IB2-P9A to R4-U1-P5B

R3-IB2-P9B to R4-U1-P6B

5 meters

Table 24-9 shows the cable connections for the fourth spine switch (R4-U1) when cabling four full racks together:

Table 24-9 Leaf Switch Connections for the Fourth Rack in a Four-Rack System

Leaf Switch Connection Cable Length
R4 IB3 within Rack 4

R4-IB3-P8A to R4-U1-P3A

R4-IB3-P8B to R4-U1-P4A

3 meters
R4 IB3 to Rack 1

R4-IB3-P9A to R1-U1-P5A

R4-IB3-P9B to R1-U1-P6A

10 meters
R4 IB3 to Rack 2

R4-IB3-P10A to R2-U1-P7A

R4-IB3-P10B to R2-U1-P8A

5 meters
R4 IB3 to Rack 3

R4-IB3-P11A to R3-U1-P9A

R4-IB3-P11B to R3-U1-P10A

5 meters
R4 IB2 within Rack 4

R4-IB2-P8A to R4-U1-P3B

R4-IB2-P8B to R4-U1-P4B

3 meters
R4 IB2 to Rack 1

R4-IB2-P9A to R1-U1-P5B

R4-IB2-P9B to R1-U1-P6B

10 meters
R4 IB2 to Rack 2

R4-IB2-P10A to R2-U1-P7B

R4-IB2-P10B to R2-U1-P8B

5 meters
R4 IB2 to Rack 3

R4-IB2-P11A to R3-U1-P9B

R4-IB2-P11B to R3-U1-P10B

5 meters