Seven-Rack Cabling with InfiniBand Network Fabric

Note the following when cabling seven racks together with InfiniBand Network Fabric:

Table 24-21 shows the cable connections for the first spine switch (R1-U1) when cabling seven racks together:

Table 24-21 Leaf Switch Connections for the First Rack in a Seven-Rack System

Leaf Switch Connection Cable Length
R1 IB3 within Rack 1

R1-IB3-P8A to R1-U1-P3A

R1-IB3-P8B to R1-U1-P4A

3 meters
R1 IB3 to Rack 2 R1-IB3-P9A to R2-U1-P5A 5 meters
R1 IB3 to Rack 3 R1-IB3-P9B to R3-U1-P6A 5 meters
R1 IB3 to Rack 4 R1-IB3-P10A to R4-U1-P7A 10 meters
R1 IB3 to Rack 5 R1-IB3-P10B to R5-U1-P8A 10 meters
R1 IB3 to Rack 6 R1-IB3-P11A to R6-U1-P9A 10 meters
R1 IB3 to Rack 7 R1-IB3-P11B to R7-U1-P10A 10 meters
R1 IB2 within Rack 1

R1-IB2-P8A to R1-U1-P3B

R1-IB2-P8B to R1-U1-P4B

3 meters
R1 IB2 to Rack 2 R1-IB2-P9A to R2-U1-P5B 5 meters
R1 IB2 to Rack 3 R1-IB2-P9B to R3-U1-P6B 5 meters
R1 IB2 to Rack 4 R1-IB2-P10A to R4-U1-P7B 10 meters
R1 IB2 to Rack 5 R1-IB2-P10B to R5-U1-P8B 10 meters
R1 IB2 to Rack 6 R1-IB2-P11A to R6-U1-P9B 10 meters
R1 IB2 to Rack 7 R1-IB2-P11B to R7-U1-P10B 10 meters

Table 24-22 shows the cable connections for the second spine switch (R2-U1) when cabling seven full racks together:

Table 24-22 Leaf Switch Connections for the Second Rack in a Seven-Rack System

Leaf Switch Connection Cable Length
R2 IB3 within Rack 2

R2-IB3-P8A to R2-U1-P3A

R2-IB3-P8B to R2-U1-P4A

3 meters
R2 IB3 to Rack 1 R2-IB3-P11B to R1-U1-P10A 5 meters
R2 IB3 to Rack 3 R2-IB3-P9A to R3-U1-P5A 5 meters
R2 IB3 to Rack 4 R2-IB3-P9B to R4-U1-P6A 5 meters
R2 IB3 to Rack 5 R2-IB3-P10A to R5-U1-P7A 10 meters
R2 IB3 to Rack 6 R2-IB3-P10B to R6-U1-P8A 10 meters
R2 IB3 to Rack 7 R2-IB3-P11A to R7-U1-P9A 10 meters
R2 IB2 within Rack 2

R2-IB2-P8A to R2-U1-P3B

R2-IB2-P8B to R2-U1-P4B

3 meters
R2 IB2 to Rack 1 R2-IB2-P11B to R1-U1-P10B 5 meters
R2 IB2 to Rack 3 R2-IB2-P9A to R3-U1-P5B 5 meters
R2 IB2 to Rack 4 R2-IB2-P9B to R4-U1-P6B 5 meters
R2 IB2 to Rack 5 R2-IB2-P10A to R5-U1-P7B 10 meters
R2 IB2 to Rack 6 R2-IB2-P10Bto R6-U1-P8B 10 meters
R2 IB2 to Rack 7 R2-IB2-P11A to R7-U1-P9B 10 meters

Table 24-23 shows the cable connections for the third spine switch (R3-U1) when cabling seven full racks together:

Table 24-23 Leaf Switch Connections for the Third Rack in a Seven-Rack System

Leaf Switch Connection Cable Length
R3 IB3 within Rack 3

R3-IB3-P8A to R3-U1-P3A

R3-IB3-P8B to R3-U1-P4A

3 meters
R3 IB3 to Rack 1 R3-IB3-P11A to R1-U1-P9A 5 meters
R3 IB3 to Rack 2 R3-IB3-P11B to R2-U1-P10A 5 meters
R3 IB3 to Rack 4 R3-IB3-P9A to R4-U1-P5A 5 meters
R3 IB3 to Rack 5 R3-IB3-P9B to R5-U1-P6A 5 meters
R3 IB3 to Rack 6 R3-IB3-P10A to R6-U1-P7A 10 meters
R3 IB3 to Rack 7 R3-IB3-P10B to R7-U1-P8A 10 meters
R3 IB2 within Rack 3

R3-IB2-P8A to R3-U1-P3B

R3-IB2-P8B to R3-U1-P4B

3 meters
R3 IB2 to Rack 1 R3-IB2-P11A to R1-U1-P9B 5 meters
R3 IB2 to Rack 2 R3-IB2-P11B to R2-U1-P10B 5 meters
R3 IB2 to Rack 4 R3-IB2-P9A to R4-U1-P5B 5 meters
R3 IB2 to Rack 5 R3-IB2-P9B to R5-U1-P6B 5 meters
R3 IB2 to Rack 6 R3-IB2-P10A to R6-U1-P7B 10 meters
R3 IB2 to Rack 7 R3-IB2-P10B to R7-U1-P8B 10 meters

Table 24-24 shows the cable connections for the fourth spine switch (R4-U1) when cabling seven full racks together:

Table 24-24 Leaf Switch Connections for the Fourth Rack in a Seven-Rack System

Leaf Switch Connection Cable Length
R4 IB3 within Rack 4

R4-IB3-P8A to R4-U1-P3A

R4-IB3-P8B to R4-U1-P4A

3 meters
R4 IB3 to Rack 1 R4-IB3-P10B to R1-U1-P8A 10 meters
R4 IB3 to Rack 2 R4-IB3-P11A to R2-U1-P9A 5 meters
R4 IB3 to Rack 3 R4-IB3-P11B to R3-U1-P10A 5 meters
R4 IB3 to Rack 5 R4-IB3-P9A to R5-U1-P5A 5 meters
R4 IB3 to Rack 6 R4-IB3-P9B to R6-U1-P6A 5 meters
R4 IB3 to Rack 7 R4-IB3-P10A to R7-U1-P7A 10 meters
R4 IB2 within Rack 4

R4-IB2-P8A to R4-U1-P3B

R4-IB2-P8B to R4-U1-P4B

3 meters
R4 IB2 to Rack 1 R4-IB2-P10B to R1-U1-P8B 10 meters
R4 IB2 to Rack 2 R4-IB2-P11A to R2-U1-P9B 5 meters
R4 IB2 to Rack 3 R4-IB2-P11B to R3-U1-P10B 5 meters
R4 IB2 to Rack 5 R4-IB2-P9A to R5-U1-P5B 5 meters
R4 IB2 to Rack 6 R4-IB2-P9B to R6-U1-P6B 5 meters
R4 IB2 to Rack 7 R4-IB2-P10A to R7-U1-P7B 10 meters

Table 24-25 shows the cable connections for the fifth spine switch (R5-U1) when cabling seven full racks together:

Table 24-25 Leaf Switch Connections for the Fifth Rack in a Seven-Rack System

Leaf Switch Connection Cable Length
R5 IB3 within Rack 5

R5-IB3-P8A to R5-U1-P3A

R5-IB3-P8B to R5-U1-P4A

3 meters
R5 IB3 to Rack 1 R5-IB3-P10A to R1-U1-P7A 10 meters
R5 IB3 to Rack 2 R5-IB3-P10B to R2-U1-P8A 10 meters
R5 IB3 to Rack 3 R5-IB3-P11A to R3-U1-P9A 5 meters
R5 IB3 to Rack 4 R5-IB3-P11B to R4-U1-P10A 5 meters
R5 IB3 to Rack 6 R5-IB3-P9A to R6-U1-P5A 5 meters
R5 IB3 to Rack 7 R5-IB3-P9B to R7-U1-P6A 5 meters
R5 IB2 within Rack 5

R5-IB2-P8A to R5-U1-P3B

R5-IB2-P8B to R5-U1-P4B

3 meters
R5 IB2 to Rack 1 R5-IB2-P10A to R1-U1-P7B 10 meters
R5 IB2 to Rack 2 R5-IB2-P10B to R2-U1-P8B 10 meters
R5 IB2 to Rack 3 R5-IB2-P11A to R3-U1-P9B 5 meters
R5 IB2 to Rack 4 R5-IB2-P11B to R4-U1-P10B 5 meters
R5 IB2 to Rack 6 R5-IB2-P9A to R6-U1-P5B 5 meters
R5 IB2 to Rack 7 R5-IB2-P9B to R7-U1-P6B 5 meters

Table 24-26 shows the cable connections for the sixth spine switch (R6-U1) when cabling seven full racks together:

Table 24-26 Leaf Switch Connections for the Sixth Rack in a Seven-Rack System

Leaf Switch Connection Cable Length
R6 IB3 within Rack 6

R6-IB3-P8A to R6-U1-P3A

R6-IB3-P8B to R6-U1-P4A

3 meters
R6 IB3 to Rack 1 R6-IB3-P9B to R1-U1-P6A 10 meters
R6 IB3 to Rack 2 R6-IB3-P10A to R2-U1-P7A 10 meters
R6 IB3 to Rack 3 R6-IB3-P10B to R3-U1-P8A 10 meters
R6 IB3 to Rack 4 R6-IB3-P11A to R4-U1-P9A 5 meters
R6 IB3 to Rack 5 R6-IB3-P11B to R5-U1-P10A 5 meters
R6 IB3 to Rack 7 R6-IB3-P9A to R7-U1-P5A 5 meters
R6 IB2 within Rack 6

R6-IB2-P8A to R6-U1-P3B

R6-IB2-P8B to R6-U1-P4B

3 meters
R6 IB2 to Rack 1 R6-IB2-P9B to R1-U1-P6B 10 meters
R6 IB2 to Rack 2 R6-IB2-P10A to R2-U1-P7B 10 meters
R6 IB2 to Rack 3 R6-IB2-P10B to R3-U1-P8B 10 meters
R6 IB2 to Rack 4 R6-IB2-P11A to R4-U1-P9B 5 meters
R6 IB2 to Rack 5 R6-IB2-P11B to R5-U1-P10B 5 meters
R6 IB2 to Rack 7 R6-IB2-P9A to R7-U1-P5B 5 meters

Table 24-27 shows the cable connections for the seventh spine switch (R7-U1) when cabling seven full racks together:

Table 24-27 Leaf Switch Connections for the Seventh Rack in a Seven-Rack System

Leaf Switch Connection Cable Length
R7 IB3 within Rack 7

R7-IB3-P8A to R7-U1-P3A

R7-IB3-P8B to R7-U1-P4A

3 meters
R7 IB3 to Rack 1 R7-IB3-P9A to R1-U1-P5A 10 meters
R7 IB3 to Rack 2 R7-IB3-P9B to R2-U1-P6A 10 meters
R7 IB3 to Rack 3 R7-IB3-P10A to R3-U1-P7A 10 meters
R7 IB3 to Rack 4 R7-IB3-P10B to R4-U1-P8A 10 meters
R7 IB3 to Rack 5 R7-IB3-P11A to R5-U1-P9A 5 meters
R7 IB3 to Rack 6 R7-IB3-P11B to R6-U1-P10A 5 meters
R7 IB2 within Rack 7

R7-IB2-P8A to R7-U1-P3B

R7-IB2-P8B to R7-U1-P4B

3 meters
R7 IB2 to Rack 1 R7-IB2-P9A to R1-U1-P5B 10 meters
R7 IB2 to Rack 2 R7-IB2-P9B to R2-U1-P6B 10 meters
R7 IB2 to Rack 3 R7-IB2-P10A to R3-U1-P7B 10 meters
R7 IB2 to Rack 4 R7-IB2-P10B to R4-U1-P8B 10 meters
R7 IB2 to Rack 5 R7-IB2-P11A to R5-U1-P9B 5 meters
R7 IB2 to Rack 6 R7-IB2-P11B to R6-U1-P10B 5 meters