Single-Phase Power Distribution Unit Cabling Connections X7 and Earlier

Table 20-4 shows the cable connections from the power distribution units (PDUs) to the rack units in a Recovery Appliance X7, X6, or X5 full rack. The destinations and the cable lengths are the same in racks with fewer storage servers. The cables terminate at PDU-A on the left and are routed to the right to enter the cable management arm (CMA). The cables are bundled in groups of four.

Table 20-4 Single-Phase PDU Cabling for the Recovery Appliance X7, X6, or X5 Full Racks

Rack Unit(1) PDU-A PDU-B Cable Length
U42 G5-5 G0-1 2 meters
U41 G4-5 G1-1 2 meters
U39 G5-6 G0-0 2 meters
U37 G5-3 G0-3 2 meters
U35 G5-1 G0-5 2 meters
U33 G5-0 G0-6 2 meters
U31 G4-4 G1-2 2 meters
U29 G4-3 G1-3 2 meters
U27 G4-2 G1-4 2 meters
U25 G3-5 G2-1 2 meters
U23 G3-3 G2-3 2 meters
U22 G3-1 G2-5 2 meters
U21 G3-0 G2-6 2 meters
U20 G1-5 G4-1 2 meters
U18 G2-2 G3-4 2 meters
U17 G2-1 G3-5 2 meters
U16 G1-6 G4-0 2 meters
U14 G2-0 G3-6 2 meters
U12 G1-4 G4-2 2 meters
U10 G1-2 G4-4 2 meters
U8 G1-0 G4-6 2 meters
U6 G0-6 G5-0 2 meters
U4 G0-4 G5-2 2 meters
U2 G0-2 G5-4 2 meters
U1 G0-0 G5-6 2 meters

Footnote 1 Un is the unit location in the rack, where n is the number.