Managing DERMS DER Groups
Working with the DERMS DER Group Management Tool
The DERMS DER Group Management tool allows you to create groups of devices to monitor and to (potentially) modify multiple devices at a time.
For VPP - Market groups used in day-ahead wholesale market participation, use the Day Ahead Market tool in Flex Operations. See Working with Day Ahead Market in the Grid DERMS chapter for creating market groups, preparing offers, reviewing awards, and running unit commitment.
Actions
• Create Group: Displays the Create/Edit Group dialog box. This allows you to Add a group name, description, and criteria to define the group.
• Edit: Displays the Create/Edit Group dialog box that allows you to modify the group definition fields.
• View Details: Displays Group Details for the selected group. For VPP - Market groups in Flex Operations, use Day Ahead Market. See Working with Day Ahead Market and Working with VPP - Market Group Details in Chapter 18.
• Delete: Deletes the group.
• Refresh: Refreshes the data from the database.
Working with VPP - Market Group Details
In Flex Operations, open Day Ahead Market from the Grid DERMS workspace group. The tool lists DER groups whose Group Type is VPP - Market. Select a group and choose View Details to open Group Details. VPP - Market groups provide Overview, DERs, Day Ahead Market Bids and Awards, and UC Results tabs.
Day Ahead Market Lifecycle
The lifecycle indicator shows Group Ready, Day Ahead Market Group Submitted, Awards Received, UC Ready, and UC Complete. On the UC Results tab, specify Market Window Start and Market Window End and select Set Group For Day Ahead Market to prepare the group forecasts and offers. In a hosted environment, the earliest market-window start is midnight on the following day. While the group is in the submitted stage, the application periodically checks for matching awards. When matching awards are first received, the lifecycle advances to Awards Received and unit commitment runs automatically. Run Unit Commitment remains available after awards are received so the operator can run it again when needed.
SCADA Points and Realtime Market
The Overview tab displays SCADA Points and Realtime Market side by side. Use Add SCADA Point, Remove SCADA Point, and Refresh to maintain or reload the group's SCADA associations. The supported target measurements are Target MW, Target MVAR, Target Voltage, and Target Frequency.
DAGC Enabled controls real-time automatic generation control for the group and is off by default. It can be changed only when a Target MW SCADA point is associated and the user has the Allow DERMS Update DER Group permission. Select Save after changing the setting. When enabled, an eligible Target MW value change runs unit commitment for the current interval and dispatches the current DER real-power setpoints through a DAGC Dispatch switching sheet. Target MVAR, Target Voltage, and Target Frequency remain available for monitoring but do not trigger unit commitment.
The DAGC Setpoint vs Dispatch graph compares Market Award, Initial UC Dispatch, Latest UC Dispatch, and Target MW SCADA values for the selected market window. Use Plot Horizon Start and Plot Horizon End to limit the displayed range. The graph defaults to the current hour when the entire current hour is within the market window; otherwise it displays the complete market window.
Working with the DERMS Smart Inverters Tool
Groups Tab
Lists the groups created by the DERMS DER Group Management tool that include Smart Inverters
Actions
• Add Smart Inverter Program: Allows you to add a Smart Inverter program, with a set of available Default and Override controls for the group of devices.
• Edit: Allows you to edit the Smart Inverter program.
• View Details: Displays the Group Details page.
• Create/Edit Event: Displays the Create/Edit Smart Inverter Event tool. This allows you to schedule the Default or Override controls.
• Refresh: Refreshes the data from the database.
Controls Tab
Actions
• Refresh: Refreshes the data from the database.
• Create: Displays the Create/Edit Control drawer. This allows you to create a set of Override or Default Controls.
• Clone: Allows you to copy the selected Control
• Edit: Displays the Create/Edit Control drawer.
• Delete: Deletes the selected Control.
Available Controls
The Controls tab supports the following controls. Where a control provides multiple operating modes, select the required operating mode before entering its values.
• Ramp Rate Setting
• Active power output ramp rate
• Active power output soft-start ramp rate
• Low/High Voltage Ride Through
• Low Voltage Ride Through MUST Trip
• Low Voltage Ride Through MAY Trip
• Low Voltage Ride Through Momentary Cessation
• High Voltage Ride Through MUST Trip
• High Voltage Ride Through MAY Trip
• High Voltage Ride Through Momentary Cessation
• Low/High Frequency Ride Through
• Low Frequency Ride Through MUST Trip
• Low Frequency Ride Through MAY Trip
• High Frequency Ride Through MUST Trip
• High Frequency Ride Through MAY Trip
• Connection Status
• DER connection status
• Dynamic Volt-VAr
• Volt-VAr curve
• Power Factor
• Fixed PF setting - Absorb W
• Fixed PF setting - Inject W
• Power Output
• Maximum active power generation level
• Volt-Watt
• Volt-Watt curve
• Frequency-Watt
• Frequency-Watt curve
• Active Power
• Charge or discharge mode setpoint
• Target output power
• Watt-PF Control
• Watt-PF curve
• Watt-VAr Control
• Watt-VAr curve
• Reactive Power
• Delivered or received reactive power setpoint
• Target reactive power
• Frequency Droop
• Frequency-Watt operation
• Enter Service After Trip
• Enter Service Delay
• Enter Service Frequency High
• Enter Service Voltage High
• Enter Service Frequency Low
• Enter Service Voltage Low
• Enter Service Ramp Time
• Enter Service Randomized Delay
Curves Tab
Actions
• Create: Displays the Create/Edit Curve drawer. This allows you to create a set of curves for use in Controls.
• Clone: Allows you to copy the selected curve.
• Edit: Displays the Create/Edit Curve drawer.
• Delete: Deletes the selected curve.
• Refresh: Refreshes the data from the database.