Rackmount Checklist
This section provides a server rackmount checklist.
Complete the following checklist prior to installing the server into a rack or cabinet.
Rackmount Considerations | Yes | No | N/A | Comment |
---|---|---|---|---|
Is the distance between the front and back mounting planes between the minimum of 610 mm and the maximum 915 mm (24 inches to 36 inches)? |
||||
Is the clearance depth in the front of the front mounting plane (distance to the front cabinet door) at least 25.4 mm (1 inch)? |
||||
Does the target rack meet the following minimum load capacity?
|
||||
Is the rack a four-post rack (mounting at both front and back)? Two-post racks are not compatible. |
||||
Does the rack's horizontal opening and unit vertical pitch conform to ANSI/EIA 310-D-1992 or IEC 60297 standards? |
||||
Does the rack have RETMA rail support? |
||||
Does the rack support installation of Oracle vented and solid filler panels? |
||||
Can the rack provide tie-downs for the Ethernet wiring harness? |
||||
Is there sufficient space for the cable harnesses and the power distribution units (PDUs) in the rack? |
||||
Can a label with the serial number be printed and attached to the target rack? |
||||
Does the rack support installation of standard Oracle PDUs? If not, then complete this checklist. |
||||
Can the customer provide an equivalent pair of PDUs? |
||||
Can the customer provide two PDUs with capacity of 110kVA per PDU? |
||||
Can the customer provide a single PDU and its circuits to support the power requirements in case one PDU fails? |
||||
Can the customer ensure power loads are evenly distributed across all circuits of a single PDU? |
||||
Can the customer provide appropriate power drops for the PDUs? |