Verify the Rack Meets the Specifications for Installing a KMA
Verify the rack is compatible before installing the KMA. The rack should be a standard, RETMA 19-inch, four post rack or cabinet.
Note:
Two-post racks are not supported by the T7-1 or T8-1 servers.
Only 9.5 mm square hole and M6 round mounting holes are supported.
The sliding rails are compatible with racks which meet the following standards:
- Horizontal opening and unit vertical pitch conforming to ANSI/EIA 310-D-1992 or IEC 60927 standards.
- Distance between front and rear mounting planes between 610 mm and 915 mm (24 in. to 36 in.).
- Clearance depth to a front cabinet door must be at least 27 mm (1.06 in.).
- Clearance depth to a rear cabinet door at least 900 mm (35.5 in.) to incorporate cable management or 700 mm (27.5 in.) without cable management.
- Clearance width between structural supports and cable troughs and between front and rear mounting planes is at least 456 mm (18 in.).
Provide adequate service clearance for rack components:
- Front service clearance 48.5 in. (1.23 m) minimum
- Rear service clearance 36 in. (914.4 mm) minimum
Consider the total weight when you place equipment into the rack. To prevent an unbalanced situation:
- Load equipment in a rack from the bottom to the top.
- Install the heaviest equipment on the bottom and the lightest on the top.
- Install an anti-tilt bar (if necessary) to provide additional stability.
Verify there is adequate cooling for the servers.
- Ensure that the temperature in the rack does not exceed the maximum ambient rated temperatures for all of the equipment installed in the rack.
- Ensure that there is adequate cooling to support all of the equipment in the rack.
Verify the rack has the proper power connections and ground.
- When removing power from any equipment, make sure it does not effect other equipment in the rack.