Power Requirements
Before installing the library, make sure that the installation site can provide the minimum requirements for power.
The library requires a separate AC power source for each PDU in the library.
- 240 VAC, 50/60 Hz, at 30 amps (range: 200–240 VAC, 47–63 Hz, 24 amps), single phase
See Power Configurations.