Replacing an Oracle ZFS Storage ZS7-2 Fan Module
Unpack the replacement fan module and get it ready to insert into the controller chassis as soon as the faulted fan is removed.
You do not have to power off the controller to service fan modules. You should not begin this procedure unless you have a replacement fan module and you are ready to install it immediately.
Caution:
When performing the actual removal and replacement of a fan module in the Oracle ZFS Storage ZS7-2 controller, you must complete the entire procedure within 20 seconds to maintain adequate cooling within the system. Remove and replace only one fan module at a time. Ensure that you have obtained the replacement fan module and that is it is ready for installation before starting the replacement procedure. If the fan module is not replaced within 20 seconds of removal, Oracle ILOM will take the protective action to shut down the system to prevent thermal damage.Fan modules are hot-swappable and can be removed and installed while the controller is running without affecting other hardware capabilities. Use the following procedure to replace an Oracle ZFS Storage ZS7-2 fan module.