C H A P T E R  2

Physical Specifications

This chapter provides information about the physical characteristics of the Sun Fire 6800/4810/4800/3800 systems, including dimensions, space needs, cable sizes, and limitations.


2.1 System Components

Sun Fire systems are available in the following enclosures:

TABLE 2-1 Sun Fire System Components

Sun Fire 6800 system

Standard 19-inch x 75-inch cabinet

6 slot CPU/Memory card cage

Sun Fire 4810 system

3 slot CPU/Memory card cage

Sun Fire 4800 system

3 slot CPU/Memory card cage

Sun Fire 3800 system

2 slot CPU/Memory card cage


The same CPU/Memory boards, PCI and CompactPCI boards, UltraSPARCtrademark III and UltraSPARC III 900-MHz CPU modules, and memory modules are used in the Sun Fire systems.

Internal storage devices are not supported.

 FIGURE 2-1 Sun Fire 6800 System

Front and rear views of the sunfire 6800 system.

The maximum configuration for the Sun Fire 6800 system is:

 FIGURE 2-2 Sun Fire 4810 System Mounted in Optional Sun Fire Cabinet

Front and rear views of the sunfire 4810 System Mounted in Optional Sun Fire Cabinet

The maximum configuration for the Sun Fire 4810 system is:

 FIGURE 2-3 Sun Fire 4800 System Mounted in Optional Sun Fire Cabinet

Front and rear views of the Sun Fire 4800 System Mounted in Optional Sun Fire Cabinet

The maximum configuration for the Sun Fire 4800 system is:

 FIGURE 2-4 Sun Fire 3800 System Mounted in Optional Sun Fire Cabinet

Front and rear views of the Sun Fire 3800 System Mounted in Optional Sun Fire Cabinet

The maximum configuration for the Sun Fire 3800 system is:


2.2 General Physical Guidelines

As you plan your space needs for the Sun Fire 6800/4810/4800/3800 systems, keep these conditions in mind:

Consult your specific Sun Fire system installation guide for complete installation details.

Up to three Sun Fire 3800 systems are supported in the Sun Fire Cabinet.

For maximum compute density, the Sun Fire 3800 systems should be mounted in the Sun Fire Cabinet. The Sun Fire 3800 system is also designed to fit in racks which meet the requirements of EIA-310-D.

The Sun Fire 3800 system rack mounting kits are designed to be used in the Sun Fire Cabinet, are not adjustable and may or may not work in other racks. When considering third party rack mounting, the third party thermal guidelines and the third party rack mounting guidelines should be reviewed.

2.2.1 Size and Space Specifications

Sun Fire systems and expansion cabinets can be placed next to each other, without space between them, since there are no side clearance requirements during operation. However, if access is desired, allow approximately 2 feet (60 centimeters) of space on each side to access and remove side panels.

2.2.1.1 Thermal Clearance Specifications

Sun Fire systems not mounted in a Sun Fire cabinet must maintain the minimum thermal distance between the rear of the system and any obstructions or walls. Requirements during operation are listed in the following table.

TABLE 2-2 Thermal Clearance for Sun Fire Standalone Systems

System

Rear Clearance

Sun Fire 3800

36 in. (91.4 cm)

Sun Fire 4800

36 in. (91.4 cm)

Sun Fire 4810

24 in. (60 cm)


 

 FIGURE 2-5 Sun Fire 6800/4810/4800/3800 Systems Access Areas--Top View

Top view of 6800 system or cabinet showing access clearances for front,4 feet, and rear, 3 feet

 FIGURE 2-6 Sun Fire 4800 System (Deskside) Access Areas--Top View

Top view of 4800 system showing access clearances for front,3 feet, and rear, 3 feet

 

To determine space requirements for Sun Fire systems, use the following tables:

 

TABLE 2-4 Physical Specifications for Sun Fire 4810/4800/3800 Systems

Characteristic

Value

Shipping height

Sun Fire 4810 system = 49.7 in. (126 cm)

Sun Fire 4800 system = 45.3 in. (115 cm)

Sun Fire 3800 system = 33.75 in. (85.7 cm)

Shipping width

Sun Fire 4810 system = 26.75 in. (68 cm)

Sun Fire 4800 system = 29.1 in. (74 cm)

Sun Fire 3800 system = 24.75 in. (63 cm)

Shipping depth

Sun Fire 4810 system = 33.75 in. (85 cm)

Sun Fire 4800 system = 40.5 in. (103 cm)

Sun Fire 3800 system = 41.5 in. (105.5 cm)

Shipping weight (package on pallet)

 

Sun Fire 4810 system = 366 lbs (166 kg)

Sun Fire 4800 system = 350 lbs (158.8 kg)

Sun Fire 3800 system = 260 lbs (117.9 kg)

Height

Sun Fire 4810 system = 36.75 in. (93.4 cm)

Sun Fire 4800 system = 30 in. (76.2 cm)

Sun Fire 4800 deskside system = 32.4 in. (82.3 cm)

Sun Fire 3800 system = 15 in. (38 cm)

Width

Sun Fire 4810/4800 systems = 17.5 in. (44.6 cm)

Sun Fire 4800 deskside system = 18.9in. (48.1 cm)

Sun Fire 3800 system = 17.7 in. (45 cm)

Depth

Sun Fire 4810 system = 23.6 in. (60 cm)

Sun Fire 4800 system = 28.5 in. (72.4 cm)

Sun Fire 4800 deskside system = 34.2 in. (86.9 cm)

Sun Fire 3800 system = 34.8 in. (88.4 cm)

Weight

Sun Fire 4810 system = 305 lbs (138.3 kg)

Sun Fire 4800 system = 289 lbs (131.1 kg)

Sun Fire 4800 deskside system = 289 lbs (131.1 kg)

Sun Fire 3800 system = 200 lbs (90.7 kg)

Power cord length

8.2 ft (2.5 m)

Access requirement for front

36 in. (91 cm)

Access requirement for rear

36 in. (91 cm)


 

FIGURE 2-7 shows the dimensions of the Sun Fire 6800/4810/4800/3800 systems crates.

FIGURE 2-8 shows the dimensions of the Sun Fire 6800 system cabinet.

FIGURE 2-9 shows the footprint dimensions of the Sun Fire 6800 system cabinet, the Sun Fire cabinet with the extension for the Sun Fire 3800 system, and the Sun Fire 4800 deskside system, and the Sun Fire cabinet.

See Electrical Specifications for Sun Fire 6800 Cabinet, Electrical Specifications for Sun Fire Cabinet (Empty), Electrical Specifications for Sun Fire 4810 System Not Mounted in the Sun Fire Cabinet, Electrical Specifications for Sun Fire 4800 System Not Mounted in the Sun Fire Cabinet, and Electrical Specifications for Sun Fire 3800 System Not Mounted in the Sun Fire Cabinet for system electrical specifications and receptacle model numbers.

 FIGURE 2-7 Shipping Crate Dimensions

View showing shipping crate dimensions for 6800 system and cabinet and 4800 deskside system

 FIGURE 2-8 Sun Fire 6800 System Cabinet Dimensions

Sun Fire 6800 system cabinet dimensions


Note - For any peripheral tray in the processor cabinet OVER 20 in (50.8 cm) in length, allow additional space for access to the front or rear doors where the peripheral will be loaded.



 FIGURE 2-9 Sun Fire 6800/4800 and Sun Fire Cabinet--Bottom Views

Sun Fire 6800 system, sunfire cabinet, cabinet with extension, and Sun Fire 4800 deskside system footprint dimensions


Note - The holes in the hold down brackets are large enough to accommodate a
3/8 inch or 10 mm bolt using a flat washer and split washer.



FIGURE 2-10 Sun Fire Cabinet and Sun Fire 6800 System With Hold Down Brackets--Top View

Top view of a Sun Fire 6800 system and cabinet showing the dimensions of the hole locations for the hold down brackets


2.3 Planning Your Access Route

If your existing loading dock meets height or ramp requirements for a standard freight carrier truck, you can use a pallet jack to unload the system. If not, you must provide a standard forklift[1] or other means to unload the system, or request the system be shipped in a truck with a lift gate.

See FIGURE 2-7 for an illustration of the system shipping crate and its dimensions. Each system is shipped in a separate crate. A pallet jack is required to move each shipping crate to the system location.

Leave each system in its shipping crate until it reaches its final destination. If the crate does not fit through the planned access route, partially disassemble it.

All systems not shipped in a cabinet should only be lifted by proper computer lifting equipment to prevent personal injury and/or damage to system equipment.

The entire access route to your computer room should be free of raised patterns that can cause vibration, and the route must meet the following requirements:

TABLE 2-5 Access Route Clearance

With Shipping Pallet

Without Shipping Pallet

Minimum door height

81 in. (205 cm)

75 in. (190.5 cm)

Minimum hallway and door width

44 in. (112 cm)

25 in. (64 cm)

Minimum elevator depth

65.5 in. (166 cm)

61 in. (155 cm)

Maximum incline

10°

10°


 

TABLE 2-6 Weight Requirements

Minimum elevator, pallet jack and floor loading capacity
(maximum weight per system)

1,200 lbs (544 kg)

 


 


2.4 Network Connection Planning

This section provides network setup information for system startup and network connections for the Sun Fire 6800/4810/4800/3800 systems and domains.

2.4.1 Setup and Network Connections

For system setup and continued administrative tasks, one serial cable and one RJ-45 Ethernet cable are required. Once the system has been set up, the Ethernet port can be used for most system administration tasks.

2.4.1.1 Serial Connection

The initial system setup requires an ASCII terminal device connected to the serial port of the main system controller with a null modem cable or a network terminal server (NTS) connection.

2.4.1.2 Ethernet Connection

Once the system is set up, most system administration tasks can be performed through the network via the Ethernet port, using a Category-5 Ethernet cable.

Ethernet Connections provides information on the number of Ethernet connections required for each system and domain.

TABLE 2-7 Ethernet Connections

Sun Fire System

System Controllers

Solaris Domains

 

Min

Max

Min

Max

6800

1

2

1

4

4810/4800/3800

1

2

1

2


2.4.2 Platform and Domain Setup Information

Before installing a Sun Fire 6800/4810/4800/3800 system, determine the following information:


1 (Footnote) A standard forklift has a maximum outside tine dimension of 27 in. (69 cm) and a minimum inside tine dimension of 15 in. (38 cm).