This section contains the tables for the Power Distribution Units (PDU) cabling for Exalogic Elastic Cloud.
This section contains the following topics for Single Phase PDUs:
This section contains the following topics for Three Phase PDUs:
This section contains the following tables:
Table E-14 lists the location, ports and cables for the Single Phase PDU connections for an Exalogic machine half rack.
Table E-14 Single Phase PDU Power Cabling for Exalogic Machine Half Rack
From Rack Unit | Type of Equipment | PDU-A | PDU-B | Jumper Length |
---|---|---|---|---|
U28 |
Compute node |
G3-3 |
G2-3 |
2M |
U27 |
Compute node |
G3-2 |
G2-4 |
2M |
U25 |
Cisco Switch |
G3-1 |
G2-5 |
2M |
U23 |
NM2-GW-SW |
G2-6 |
G3-0 |
2M |
U22 |
ZS3-ES HN |
G2-5 |
G3-1 |
2M |
U21 |
ZS3-ES HN |
G2-4 |
G3-2 |
2M |
U17 |
DE2-24C DS |
G2-3 |
G3-3 |
1M |
U16 |
NM2-GW-SW |
G1-6 |
G4-0 |
2M |
U15 |
Compute node |
G2-2 |
G3-4 |
2M |
U14 |
Compute node |
G2-1 |
G3-5 |
2M |
U13 |
Compute node |
G2-0 |
G3-6 |
2M |
U12 |
Compute node |
G1-4 |
G4-2 |
2M |
U11 |
Compute node |
G1-3 |
G4-3 |
2M |
U10 |
Compute node |
G1-2 |
G4-4 |
2M |
U09 |
Compute node |
G1-1 |
G4-5 |
2M |
U08 |
Compute node |
G1-0 |
G4-6 |
2M |
U07 |
Compute node |
G0-6 |
G5-0 |
2M |
U06 |
Compute node |
G0-5 |
G5-1 |
2M |
U05 |
Compute node |
G0-4 |
G5-2 |
2M |
U04 |
Compute node |
G0-3 |
G5-3 |
2M |
U03 |
Compute node |
G0-2 |
G5-4 |
2M |
U02 |
Compute node |
G0-1 |
G5-5 |
2M |
This section contains the following tables:
Table E-15 lists the location, ports and cables for the Single Phase PDU connections for an Exalogic machine quarter rack.
Table E-15 Single Phase PDU Power Cabling for Exalogic Machine Quarter Rack
From Rack Unit | Type of Equipment | PDU-A | PDU-B | Jumper Length |
---|---|---|---|---|
U25 |
Cisco Switch |
G3-1 |
G2-5 |
2M |
U23 |
NM2-GW-SW |
G2-6 |
G3-0 |
2M |
U22 |
ZS3-ES HN |
G2-5 |
G3-1 |
2M |
U21 |
ZS3-ES HN |
G2-4 |
G3-2 |
2M |
U17 |
DE2-24C DS |
G2-3 |
G3-3 |
1M |
U16 |
NM2-GW-SW |
G1-6 |
G4-0 |
2M |
U09 |
Compute node |
G1-1 |
G4-5 |
2M |
U08 |
Compute node |
G1-0 |
G4-6 |
2M |
U07 |
Compute node |
G0-6 |
G5-0 |
2M |
U06 |
Compute node |
G0-5 |
G5-1 |
2M |
U05 |
Compute node |
G0-4 |
G5-2 |
2M |
U04 |
Compute node |
G0-3 |
G5-3 |
2M |
U03 |
Compute node |
G0-2 |
G5-4 |
2M |
U02 |
Compute node |
G0-1 |
G5-5 |
2M |
This section contains the following tables:
Table E-16 lists the location, ports and cables for the Single Phase PDU connections for an Exalogic machine eighth rack.
Table E-16 Single Phase PDU Power Cabling for Exalogic Machine Eighth Rack
From Rack Unit | Type of Equipment | PDU-A | PDU-B | Jumper Length |
---|---|---|---|---|
U25 |
Cisco Switch |
G3-1 |
G2-5 |
2M |
U23 |
NM2-GW-SW |
G2-6 |
G3-0 |
2M |
U22 |
ZS3-ES HN |
G2-5 |
G3-1 |
2M |
U21 |
ZS3-ES HN |
G2-4 |
G3-2 |
2M |
U17 |
DE2-24C DS |
G2-3 |
G3-3 |
1M |
U16 |
NM2-GW-SW |
G1-6 |
G4-0 |
2M |
U05 |
Compute node |
G0-4 |
G5-2 |
2M |
U04 |
Compute node |
G0-3 |
G5-3 |
2M |
U03 |
Compute node |
G0-2 |
G5-4 |
2M |
U02 |
Compute node |
G0-1 |
G5-5 |
2M |
This section contains the following tables:
Table E-17 lists the location, ports and cables for the Three Phase PDU connections for an Exalogic machine full rack.
Table E-17 Three Phase PDU Power Cabling for Exalogic Machine Full Rack
From Rack Unit | Type of Equipment | PDU-A | PDU-B | Jumper Length |
---|---|---|---|---|
U42 |
Compute node |
G5-5 |
G2-1 |
2M |
U41 |
Compute node |
G5-4 |
G2-2 |
2M |
U40 |
Compute node |
G5-3 |
G2-3 |
2M |
U39 |
Compute node |
G5-2 |
G2-4 |
2M |
U38 |
Compute node |
G5-1 |
G2-5 |
2M |
U37 |
Compute node |
G5-0 |
G2-6 |
2M |
U36 |
Compute node |
G4-6 |
G1-0 |
2M |
U35 |
Compute node |
G4-5 |
G1-1 |
2M |
U34 |
Compute node |
G4-4 |
G1-2 |
2M |
U33 |
Compute node |
G4-3 |
G1-3 |
2M |
U32 |
Compute node |
G4-2 |
G1-4 |
2M |
U31 |
Compute node |
G4-1 |
G1-5 |
2M |
U30 |
Compute node |
G3-6 |
G0-0 |
2M |
U29 |
Compute node |
G3-5 |
G0-1 |
2M |
U28 |
Compute node |
G3-4 |
G0-2 |
2M |
U27 |
Compute node |
G3-3 |
G0-3 |
2M |
U26 |
NM2-GW SW |
G3-2 |
G0-4 |
2M |
U25 |
Cisco Switch |
G3-1 |
G0-5 |
2M |
U24 |
NM2-GW SW |
G2-6 |
G5-0 |
2M |
U23 |
NM2-GW-SW |
G2-5 |
G5-1 |
2M |
U22 |
ZS3-ES HN |
G3-0 |
G0-6 |
2M |
U21 |
ZS3-ES HN |
G2-4 |
G5-2 |
2M |
U17 |
DE2-24C DS |
G2-3 |
G5-3 |
1M |
U16 |
NM2-GW-SW |
G1-6 |
G4-0 |
2M |
U15 |
Compute node |
G2-2 |
G5-4 |
2M |
U14 |
Compute node |
G2-1 |
G5-5 |
2M |
U13 |
Compute node |
G2-0 |
G5-6 |
2M |
U12 |
Compute node |
G1-4 |
G4-2 |
2M |
U11 |
Compute node |
G1-3 |
G4-3 |
2M |
U10 |
Compute node |
G1-2 |
G4-4 |
2M |
U09 |
Compute node |
G1-1 |
G4-5 |
2M |
U08 |
Compute node |
G1-0 |
G4-6 |
2M |
U07 |
Compute node |
G0-6 |
G3-0 |
2M |
U06 |
Compute node |
G0-5 |
G3-1 |
2M |
U05 |
Compute node |
G0-4 |
G3-2 |
2M |
U04 |
Compute node |
G0-3 |
G3-3 |
2M |
U03 |
Compute node |
G0-2 |
G3-4 |
2M |
U02 |
Compute node |
G0-1 |
G3-5 |
2M |
This section contains the following tables:
Table E-18 lists the location, ports and cables for the Three Phase PDU connections for an Exalogic machine half rack.
Table E-18 Three Phase PDU Power Cabling for Exalogic Machine Half Rack
From Rack Unit | Type of Equipment | PDU-A | PDU-B | Jumper Length |
---|---|---|---|---|
U28 |
Compute node |
G3-4 |
G0-2 |
2M |
U27 |
Compute node |
G3-3 |
G0-3 |
2M |
U25 |
Cisco Switch |
G3-1 |
G0-5 |
2M |
U23 |
NM2-GW-SW |
G2-5 |
G5-1 |
2M |
U22 |
ZS3-ES HN |
G3-0 |
G0-6 |
2M |
U21 |
ZS3-ES HN |
G2-4 |
G5-2 |
2M |
U17 |
DE2-24C DS |
G2-3 |
G5-3 |
1M |
U16 |
NM2-GW-SW |
G1-6 |
G4-0 |
2M |
U15 |
Compute node |
G2-2 |
G5-4 |
2M |
U14 |
Compute node |
G2-1 |
G5-5 |
2M |
U13 |
Compute node |
G2-0 |
G5-6 |
2M |
U12 |
Compute node |
G1-4 |
G4-2 |
2M |
U11 |
Compute node |
G1-3 |
G4-3 |
2M |
U10 |
Compute node |
G1-2 |
G4-4 |
2M |
U09 |
Compute node |
G1-1 |
G4-5 |
2M |
U08 |
Compute node |
G1-0 |
G4-6 |
2M |
U07 |
Compute node |
G0-6 |
G3-0 |
2M |
U06 |
Compute node |
G0-5 |
G3-1 |
2M |
U05 |
Compute node |
G0-4 |
G3-2 |
2M |
U04 |
Compute node |
G0-3 |
G3-3 |
2M |
U03 |
Compute node |
G0-2 |
G3-4 |
2M |
U02 |
Compute node |
G0-1 |
G3-5 |
2M |
This section contains the following tables:
Table E-19 lists the location, ports and cables for the Three Phase PDU connections for an Exalogic machine quarter rack.
Table E-19 Three Phase PDU Power Cabling for Exalogic Machine Quarter Rack
From Rack Unit | Type of Equipment | PDU-A | PDU-B | Jumper Length |
---|---|---|---|---|
U25 |
Cisco Switch |
G3-1 |
G0-5 |
2M |
U23 |
NM2-GW-SW |
G2-5 |
G5-1 |
2M |
U22 |
ZS3-ES HN |
G3-0 |
G0-6 |
2M |
U21 |
ZS3-ES HN |
G2-4 |
G5-2 |
2M |
U17 |
DE2-24C DS |
G2-3 |
G5-3 |
1M |
U16 |
NM2-GW-SW |
G1-6 |
G4-0 |
2M |
U09 |
Compute node |
G1-1 |
G4-5 |
2M |
U08 |
Compute node |
G1-0 |
G4-6 |
2M |
U07 |
Compute node |
G0-6 |
G3-0 |
2M |
U06 |
Compute node |
G0-5 |
G3-1 |
2M |
U05 |
Compute node |
G0-4 |
G3-2 |
2M |
U04 |
Compute node |
G0-3 |
G3-3 |
2M |
U03 |
Compute node |
G0-2 |
G3-4 |
2M |
U02 |
Compute node |
G0-1 |
G3-5 |
2M |
This section contains the following tables:
Table E-20 lists the location, ports and cables for the Three Phase PDU connections for an Exalogic machine eighth rack.
Table E-20 Three Phase PDU Power Cabling for Exalogic Machine Eighth Rack
From Rack Unit | Type of Equipment | PDU-A | PDU-B | Jumper Length |
---|---|---|---|---|
U25 |
Cisco Switch |
G3-1 |
G0-5 |
2M |
U23 |
NM2-GW-SW |
G2-5 |
G5-1 |
2M |
U22 |
ZS3-ES HN |
G3-0 |
G0-6 |
2M |
U21 |
ZS3-ES HN |
G2-4 |
G5-2 |
2M |
U17 |
DE2-24C DS |
G2-3 |
G5-3 |
1M |
U16 |
NM2-GW-SW |
G1-6 |
G4-0 |
2M |
U05 |
Compute node |
G0-4 |
G3-2 |
2M |
U04 |
Compute node |
G0-3 |
G3-3 |
2M |
U03 |
Compute node |
G0-2 |
G3-4 |
2M |
U02 |
Compute node |
G0-1 |
G3-5 |
2M |