Complete the following checklist to ensure that the data center environment requirements are met. For information about environment requirements, see Temperature and Humidity Requirements.
Data Center Environment Considerations | Yes | No | N/A | comment |
---|---|---|---|---|
Does the computer room air handling meet temperature and humidity requirements? |
||||
Does the installation floor layout satisfy the ventilation requirements? |
||||
Will the equipment be positioned so the exhaust air of one rack does not enter the air intake of another rack? |
||||
Are the perforated floor tiles each rated at 400 CFM or greater? |
||||
Do the data center air conditioners provide sufficient front to back airflow? |
||||
Is airflow adequate to prevent hot spots? |
||||
Can the data center continuously satisfy environmental requirements? |
||||
Can more vented floor tiles be obtained if required? |