This Appendix contains the following specifications for the Sun Fire X2270 Server.
A.1	Physical Specifications
TABLE A-1 lists the physical specifications for the Sun Fire X2270 Server.
   TABLE A-1 	   Sun Fire X2270 Server Physical Specifications     
| 
 Specification
 
 | 
 British
 
 | 
 Metric
 
 | 
| 
 Height
 
 | 
 1.7 inches
 
 | 
 43 mm
 
 | 
| 
 Width
 
 | 
 17.2 inches
 
 | 
 436 mm
 
 | 
| 
 Depth
 
 | 
 25.6 inches
 
 | 
 650 mm
 
 | 
| 
 Weight
 
 | 
 27.28 lbs (minimum configuration options)
 
29.04 lbs (maximum configuration options)
 
 | 
 12.4 kg
 
13.2 kg
 
 | 
A.2	Power Specifications
Maximum continuous power is 600 W. Other power specifications are shown in the following tables.
   TABLE A-2 	AC Input Voltage Rating 
| 
 Parameter
 
 | 
 Minimum
 
 | 
 Rated
 
 | 
 Maximum
 
 | 
| 
 Voltage
 
 | 
 90 Vrms
 
 | 
 100-127/200-240 Vrms
 
 | 
 264 Vrms
 
 | 
| 
 Frequency
 
 | 
 47 Hz
 
 | 
 50/60 Hz
 
 | 
 63 Hz
 
 | 
   TABLE A-3 	Input Current 
| 
 Current Type
 
 | 
 Values
 
 | 
| 
 Maximum input current
 
 | 
 8.6 Amps max @ 100 Vac; 4.3 Amps max @ 200 Vac, full load
 
 | 
| 
 Maximum inrush current
 
 | 
 60 Amps
 
 | 
A.3	Environmental Specifications
Environmental specifications for the Sun Fire X2270 Server are shown in TABLE A-4.
   TABLE A-4 	     Sun Fire X2270 Server Environmental Specifications  
| 
 Specification
 
 | 
 State
 
 | 
 British
 
 | 
 Metric
 
 | 
| 
 Humidity 
 
 | 
 Operating 
 
 | 
 7%-93% RH non-condensing, 80.6˚ F max wet bulb
 
 | 
 7%-93% RH non-condensing, 38˚ C max wet bulb
 
 | 
| 
  
 
 | 
 Nonoperating 
 
 | 
 93% RH, non-condensing, 100.4˚ F max wet bulb
 
 | 
 93% RH, non-condensing, 43˚ C max wet bulb
 
 | 
| 
 Vibration 
 
 | 
 Operating 
 
 | 
 0.12 G x-y, 0.17 G z;
 5-500 Hz sine 
 
 | 
  
 
 | 
| 
  
 
 | 
 Nonoperating 
 
 | 
 0.3 G x-y, 0.6 G z;
 5-500 Hz sine 
 
 | 
  
 
 | 
| 
 Shock 
 
 | 
 Operating 
 
 | 
 3.5 G; 11 msec. half-sine 
 
 | 
  
 
 | 
| 
 Temperature 
 
 | 
 Operating 
 
 | 
 36˚ F to 100˚ F
 
 | 
 2˚ C to 35˚ C
 
 | 
| 
  
 
 | 
 Nonoperating 
 
 | 
 -40˚ F to 154˚ F
 
 | 
 -40˚ C to 68˚ C
 
 | 
| 
 Maximum operating temperature derating
 
 | 
  
 
 | 
 -1.8˚ F for every 985 ft. in altitude
 
 | 
 -1˚ C for every 300 m in altitude
 
 | 
| 
 Altitude 
 
 | 
 Operating 
 
 | 
 max 9,843 ft
 
 | 
 max 3,000 m
 
 | 
A.4	Serial Connector Pin Assignments
The serial management port connector is an RS-232-F RJ-45 type connector located on the server back panel.
FIGURE A-1 	Serial Management Port Pin Configuration
   TABLE A-5 	   Serial Management Port Pin Assignments  
| 
 Pin Number
 
 | 
 Pin Name
 
 | 
 Description
 
 | 
| 
 1
 
 | 
 RTS
 
 | 
 Ready to send
 
 | 
| 
 2
 
 | 
 DTR
 
 | 
 Data terminal ready
 
 | 
| 
 3
 
 | 
 TXD
 
 | 
 Transmit data
 
 | 
| 
 4
 
 | 
 GND
 
 | 
 Ground
 
 | 
| 
 5
 
 | 
 GND
 
 | 
 Ground
 
 | 
| 
 6
 
 | 
 RXD
 
 | 
 Receive data
 
 | 
| 
 7
 
 | 
 DSR
 
 | 
 Data send ready
 
 | 
| 
 8
 
 | 
 CTS
 
 | 
 Clear to send
 
 | 
| Sun Fire X2270 Server Service Manual
 | 