Environmental Specifications
The following table lists the temperature, humidity, and altitude specifications, as
well as acoustic noise, vibration, and shock specifications for the storage server.
Table 3 Environmental Specifications
|
|
|
|
Ambient temperature (Does not apply to removable media)
|
The ambient temperature for systems operating in an Exadata cabinet is
41˚F to 90˚F (5˚C to 32˚C) up to 2,953 feet (900
meters).
Note -
Maximum ambient operating temperature is derated by 1 degree C for
every 300 meters elevation beyond 900 meters, up to a maximum altitude of
3,000 meters elevation.
|
–40˚F to 158˚F
(–40˚C to 70˚C)
|
70˚F to 74˚F
(21˚C to 23˚C)
|
Relative humidity
|
-
10% to 90% noncondensing, short term 25˚F to 113˚F
(–5˚C to 55˚C)
-
5% to 90% noncondensing, but not to exceed 0.024 kg of water per kg
of dry air (0.053 lbs water/2.205 lbs dry air)
|
Up to 93% noncondensing 100.4˚F (38˚C) maximum wet bulb
|
45% to 50% relative humidity
|
Altitude
|
Maximum 9,840 feet (3,000 meters) at 95˚F (35˚C)
Note -
In China markets, regulations may limit installations to a maximum
altitude of 6,562 feet (2,000 meters).
|
Maximum 39,370 feet (12,000 meters)
|
|
Acoustic Noise
|
|
Not applicable
|
|
Vibration
|
0.15 G (z-axis),
0.10 G (x-, y-axes), 5-500Hz swept sine
IEC 60068-2-6 Test FC
|
0.5 G (z-axis),
0.25 G (x-, y-axes), 5-500Hz swept sine
IEC 60068-2-6 Test FC
|
|
Shock
|
3 Gs, 11 ms half-sine
IEC 60068-2-27 Test Ea
|
Roll-off: 1.25-inch roll-off free fall, front to back rolling
directions
Threshold: 13 mm threshold height at 0.65 m/s impact velocity
ETE-1010-02 Rev A
|
|
|
Set conditions to the optimal temperature and humidity ranges to minimize the chance of
downtime due to component failure. Operating the storage server for extended periods at or
near the operating range limits, or installing it in an environment where it remains at or
near nonoperating range limits could significantly increase hardware component failure.