Alarm Type: TPD
Description: The internal temperature within the server is unacceptably high.
Severity: Major
OID: TpdTemperatureErrorNotify 1.3.6.1.4.1.323.5.3.18.3.1.2.15
Alarm ID: TKSPLATMA153000000000004000
Recovery
Table 4-2 Server Environmental Conditions
Ambient Temperature | Operating: 5 degrees C to 40 degrees C Exceptional Operating Limit: 0 degrees C to 50 degrees C Storage: -20 degrees C to 60 degrees C |
Ambient Temperature | Operating: 5° C to 35° C Storage: -20° C to 60° C |
Relative Humidity | Operating: 5% to 85% non-condensing Storage: 5% to 950% non-condensing |
Elevation | Operating: -300m to +300m Storage: -300m to +1200m |
Heating, Ventilation, and Air Conditioning | Capacity must compensate for up to 5100 BTUs/hr for each installed frame. Calculate HVAC capacity as follows: Determine the wattage of the installed equipment. Use the formula: watts x 3.143 = BTUs/hr |
Note:
Be prepared to wait the appropriate period of time before continuing with the next step. Conditions need to be below alarm thresholds consistently for the alarm to clear. The alarm may take up to five minutes to clear after conditions improve. It may take about ten minutes after the room returns to an acceptable temperature before syscheck shows the alarm cleared.Note:
Be prepared to wait the appropriate period of time before continuing with the next step. Conditions need to be below alarm thresholds consistently for the alarm to clear. It may take about ten minutes after the room returns to an acceptable temperature before the alarm cleared.Note:
Be prepared to wait the appropriate period of time before continuing with the next step. Conditions need to be below alarm thresholds consistently for the alarm to clear. The alarm may take up to five minutes to clear after conditions improve. It may take about ten minutes after the filter is replaced before syscheck shows the alarm cleared.