1.2.10 General Environmental Requirements for Oracle Exadata Database Machine X2-2

The environmental requirements for Oracle Exadata Database Machine X2-2 depend on the size of the system. Table 1-9 shows the general environmental requirements for Oracle Exadata Database Machine X2-2. The other sections in this chapter provide detailed information.

Table 1-9 Environmental Requirements for Oracle Exadata Database Machine X2-2

Environmental Component Oracle Exadata Database Machine X2-2 Full Rack Oracle Exadata Database Machine X2-2 Half Rack Oracle Exadata Database Machine X2-2 Quarter Rack

Weight

See Also: "Flooring Requirements"

966.6 kg (2131 lbs)

602.8 kg (1329 lbs)

409.1kg (902 lbs)

Acoustic levels

89 db(A)

86 db(A)

83 db(A)

Power

See Also: "Electrical Power Requirements"

Maximum: 14.0 kW (14.3 kVA)

Typical: 9.8 kW (10.0 kVA) (varies based on application load)

Maximum: 7.2 kW (7.3 kVA)

Typical: 5.1 kW (5.2 kVA) (varies based on application load)

Maximum: 3.6 kW (3.7 kVA)

Typical: 2.7 kW (2.75kVA) (varies based on application load)

Cooling

See Also: "Temperature and Humidity Requirements", and "Ventilation and Cooling Requirements"

Maximum: 47,800 BTU/hour (50,400 kJ/hour)

Typical: 33,400 BTU/hour (35,300 kJ/hour)

Maximum: 26,400 BTU/hour (25,950 kJ/hour)

Typical: 17,400 BTU/hour (35,300 kJ/hour)

Maximum: 12,300 BTU/hour (13,000 kJ/hour)

Typical: 9,200 BTU/hour (9,700 kJ/hour)

Air flow front-to-back (subject to actual data center environment)

See Also: "Temperature and Humidity Requirements", and "Ventilation and Cooling Requirements"

Maximum: Approximately 2,200 CFM

Typical: Approximately 1,560 CFM

Maximum: Approximately 1,130 CFM

Typical: Approximately 840 CFM

Maximum: Approximately 550 CFM

Typical: Approximately 410 CFM

IP Addresses

See Also: "Network Connection and IP Address Requirements for Oracle Exadata Database Machine"

70 for Ethernet network, assuming single cluster

22 for InfiniBand network

40 for Ethernet network, assuming single cluster (39 IP addresses are needed for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers))

11 for InfiniBand network

23 for Ethernet network, assuming single cluster

5 for InfiniBand network

Network drops

See Also: "Network Connection and IP Address Requirements for Oracle Exadata Database Machine"

Minimum of 12 network drops

Minimum of 8 network drops

Minimum of 6 network drops

External connectivity

See Also: "Network Connection and IP Address Requirements for Oracle Exadata Database Machine"

24 x 1 GbE Ethernet ports

16 x 10 GbE Ethernet ports (valid for M2 servers only)

At least 12 InfiniBand ports

12 x 1 GbE Ethernet ports

8 x 10 GbE Ethernet ports (valid for M2 servers only)

At least 12 InfiniBand ports

6 x 1 GbE Ethernet ports

4 x 10 GbE Ethernet ports (valid for M2 servers only)

At least 12 InfiniBand ports