1.2.10 General Environmental Requirements for Oracle Exadata Database Machine X2-2
The environmental requirements for Oracle Exadata Database Machine X2-2 depend on the size of the system. Table 1-9 shows the general environmental requirements for Oracle Exadata Database Machine X2-2. The other sections in this chapter provide detailed information.
Table 1-9 Environmental Requirements for Oracle Exadata Database Machine X2-2
Environmental Component | Oracle Exadata Database Machine X2-2 Full Rack | Oracle Exadata Database Machine X2-2 Half Rack | Oracle Exadata Database Machine X2-2 Quarter Rack |
---|---|---|---|
Weight See Also: "Flooring Requirements" |
966.6 kg (2131 lbs) |
602.8 kg (1329 lbs) |
409.1kg (902 lbs) |
Acoustic levels |
89 db(A) |
86 db(A) |
83 db(A) |
Power See Also: "Electrical Power Requirements" |
Maximum: 14.0 kW (14.3 kVA) Typical: 9.8 kW (10.0 kVA) (varies based on application load) |
Maximum: 7.2 kW (7.3 kVA) Typical: 5.1 kW (5.2 kVA) (varies based on application load) |
Maximum: 3.6 kW (3.7 kVA) Typical: 2.7 kW (2.75kVA) (varies based on application load) |
Cooling See Also: "Temperature and Humidity Requirements", and "Ventilation and Cooling Requirements" |
Maximum: 47,800 BTU/hour (50,400 kJ/hour) Typical: 33,400 BTU/hour (35,300 kJ/hour) |
Maximum: 26,400 BTU/hour (25,950 kJ/hour) Typical: 17,400 BTU/hour (35,300 kJ/hour) |
Maximum: 12,300 BTU/hour (13,000 kJ/hour) Typical: 9,200 BTU/hour (9,700 kJ/hour) |
Air flow front-to-back (subject to actual data center environment) See Also: "Temperature and Humidity Requirements", and "Ventilation and Cooling Requirements" |
Maximum: Approximately 2,200 CFM Typical: Approximately 1,560 CFM |
Maximum: Approximately 1,130 CFM Typical: Approximately 840 CFM |
Maximum: Approximately 550 CFM Typical: Approximately 410 CFM |
See Also: "Network Connection and IP Address Requirements for Oracle Exadata Database Machine" |
70 for Ethernet network, assuming single cluster 22 for InfiniBand network |
40 for Ethernet network, assuming single cluster (39 IP addresses are needed for Oracle Exadata Database Machine X2-2 (with X4170 and X4275 servers)) 11 for InfiniBand network |
23 for Ethernet network, assuming single cluster 5 for InfiniBand network |
Network drops See Also: "Network Connection and IP Address Requirements for Oracle Exadata Database Machine" |
Minimum of 12 network drops |
Minimum of 8 network drops |
Minimum of 6 network drops |
External connectivity See Also: "Network Connection and IP Address Requirements for Oracle Exadata Database Machine" |
24 x 1 GbE Ethernet ports 16 x 10 GbE Ethernet ports (valid for M2 servers only) At least 12 InfiniBand ports |
12 x 1 GbE Ethernet ports 8 x 10 GbE Ethernet ports (valid for M2 servers only) At least 12 InfiniBand ports |
6 x 1 GbE Ethernet ports 4 x 10 GbE Ethernet ports (valid for M2 servers only) At least 12 InfiniBand ports |
Parent topic: General Environmental Requirements