1.2.11 General Environmental Requirements for Oracle Exadata Database Machine X2-8 Full Rack
Table 1-10 shows the general environmental requirements for Oracle Exadata Database Machine X2-8 Full Rack. The other sections in this chapter provide detailed information.
Table 1-10 Environmental Requirements for Oracle Exadata Database Machine X2-8 Full Rack
Environmental Component | Oracle Exadata Database Machine X2-8 Full Rack (Sun Fire X4800 Oracle Database Servers) | Oracle Exadata Database Machine X2-8 Full Rack (Sun Server X2-8 Oracle Database Servers) |
---|---|---|
Weight See Also: "Flooring Requirements" |
943.5 kg (2080 lbs) |
980.7 kg (2162 lbs) |
Acoustic levels |
85 db(A) |
85 db(A) |
Power See Also: "Electrical Power Requirements" |
Maximum: 17.0 kW (17.4 kVA) Typical: 11.9 kW (12.2 kVA) (varies based on application load) |
Maximum: 17.7 kW (18.1 kVA) Typical: 12.4 kW (112.7 kVA) (varies based on application load) |
Cooling See Also: "Temperature and Humidity Requirements", and "Ventilation and Cooling Requirements" |
Maximum: 58,050 BTU/hour (61,200 kJ/hour) Typical: 40,630 BTU/hour (42,840 kJ/hour) |
Maximum: 60,350 BTU/hour (63,630 kJ/hour) Typical: 42,280 BTU/hour (44,580 kJ/hour) |
Air flow front-to-back (subject to actual data center environment) See Also: "Temperature and Humidity Requirements", and "Ventilation and Cooling Requirements" |
Maximum: Approximately 2,690 CFM Typical: Approximately 1,880 CFM |
Maximum: Approximately 2,781CFM Typical: Approximately 1,950 CFM |
See Also: "Network Connection and IP Address Requirements for Oracle Exadata Database Machine" |
45 for Ethernet network, assuming single cluster 22 for InfiniBand network |
45 for Ethernet network, assuming single cluster 22 for InfiniBand network |
Network drops See Also: "Network Connection and IP Address Requirements for Oracle Exadata Database Machine" |
Minimum of 5 network drops |
Minimum of 5 network drops |
External connectivity See Also: "Network Connection and IP Address Requirements for Oracle Exadata Database Machine" |
16 x 1 GbE Ethernet ports 16 x 10 GbE Ethernet SFP+ ports 12 InfiniBand ports |
16 x 1 GbE Ethernet ports 16 x 10 GbE Ethernet SFP+ ports 12 InfiniBand ports |