1.2.12 General Environmental Requirements for Oracle Exadata Storage Expansion Rack X5-2

The environmental requirements for Oracle Exadata Storage Expansion Rack X5-2 depend on the size of the system. Table 1-11 shows the general environmental requirements for each type of Oracle Exadata Storage Expansion Rack X5-2.

Table 1-11 Environmental Requirements for Oracle Exadata Storage Expansion Rack X5-2

Environmental Component Oracle Exadata Storage Expansion X5-2 Full Rack Oracle Exadata Storage Expansion X5-2 Half Rack Oracle Exadata Storage Expansion X5-2 Quarter Rack

Weight

  • Extreme Flash drives: 821 kg (1810 lbs)

  • High capacity drives: 915.8 kg (2019 lbs)

  • Extreme Flash drives: 546.6 kg (1205 lbs)

  • High capacity drives: 591.5 kg (1304 lbs)

  • Extreme Flash drives: 364.5 kg (804 lbs)

  • High capacity drives: 384.4 kg (848 lbs)

Acoustic levels

82 db(A)

79 db(A)

76 db(A)

Power

  • Extreme Flash drives

    Maximum: 13.1 kVA

    Typical: 9.2 kVA (varies based on application load)

  • High capacity drives

    Maximum: 12.8 kVA

    Typical: 8.9 kVA (varies based on application load)

  • Extreme Flash drives

    Maximum: 5.9 kVA

    Typical: 4.2 kVA (varies based on application load)

  • High capacity drives

    Maximum: 6.9 kVA

    Typical: 4.8 kVA (varies based on application load)

  • Extreme Flash drives

    Maximum: 3.7 kVA

    Typical: 2.6 kVA (varies based on application load)

  • High capacity drives

    Maximum: 3.7 kVA

    Typical: 2.6 kVA (varies based on application load)

Cooling

  • Extreme Flash drives

    Maximum: 43,765 BTU/hour (46,170 kJ/hour)

    Typical: 30,635 BTU/hour (32,320 kJ/hour)

  • High capacity drives

    Maximum: 42,670 BTU/hour (45,020 kJ/hour)

    Typical: 29,870 BTU/hour (31,515 kJ/hour)

  • Extreme Flash drives

    Maximum: 19,880 BTU/hour (20,970 kJ/hour)

    Typical: 13,915 BTU/hour (14,680 kJ/hour)

  • High capacity drives

    Maximum: 22,950 BTU/hour (24,210 kJ/hour)

    Typical: 16,065 BTU/hour (16,950 kJ/hour

  • Extreme Flash drives

    Maximum: 12,362 BTU/hour (13,042 kJ/hour)

    Typical: 8,654 BTU/hour (9,129 kJ/hour)

  • High capacity drives

    Maximum: 12,212 BTU/hour (12,884 kJ/hour)

    Typical: 8,548 BTU/hour (9,019 kJ/hour)

Air flow front-to-back (subject to actual data center environment)

  • Extreme Flash drives

    Maximum: Approximately 2,030 CFM

    Typical: Approximately 1,420 CFM

  • High capacity drives

    Maximum: Approximately 1,975 CFM

    Typical: Approximately 1,385 CFM

  • Extreme Flash drives

    Maximum: Approximately 920 CFM

    Typical: Approximately 645 CFM

  • High capacity drives

    Maximum: Approximately 1,065 CFM

    Typical: Approximately 745 CFM

  • Extreme Flash drives

    Maximum: Approximately 565 CFM

    Typical: Approximately 396 CFM

  • High capacity drives

    Maximum: Approximately 572 CFM

    Typical: Approximately 401 CFM

IP Addresses

44 for Ethernet network, assuming single cluster

38 for InfiniBand network

24 for Ethernet network, assuming single cluster

18 for InfiniBand network

13 for Ethernet network, assuming single cluster

8 for InfiniBand network

Network drops

Minimum of 1 network drop

Minimum of 1 network drop

Minimum of 1 network drop

External connectivity

12 InfiniBand ports

12 InfiniBand ports

12 InfiniBand ports