1.2.13 General Environmental Requirements for Oracle Exadata Storage Expansion Rack X4-2

The environmental requirements for Oracle Exadata Storage Expansion Rack X4-2 depend on the size of the system. Table 1-12 shows the general environmental requirements for each type of Oracle Exadata Storage Expansion Rack X4-2.

Table 1-12 Environmental Requirements for Oracle Exadata Storage Expansion Rack X4-2

Environmental Component Oracle Exadata Storage Expansion X4-2 Full Rack Oracle Exadata Storage Expansion X4-2 Half Rack Oracle Exadata Storage Expansion X4-2 Quarter Rack

Weight

824.2 kg (1817 lbs)

513.0 kg (1131 lbs)

346.5 kg (764 lbs)

Acoustic levels

82 db(A)

79 db(A)

76 db(A)

Power

  • High performance drives

    Maximum: 10.2 kVA

    Typical: 7.1 kVA (varies based on application load)

  • High capacity drives

    Maximum: 9.1 kVA

    Typical: 6.3 kVA (varies based on application load)

  • High performance drives

    Maximum: 5.7 kVA

    Typical: 4.1 kVA (varies based on application load)

  • High capacity drives

    Maximum: 5.2 kVA

    Typical: 3.7 kVA (varies based on application load)

  • High performance drives

    Maximum: 2.9 kVA

    Typical: 2.0 kVA (varies based on application load)

  • High capacity drives

    Maximum: 2.7 kVA

    Typical: 2.0 kVA (varies based on application load)

Cooling

  • High performance drives

    Maximum: 34,100 BTU/hour (36,000 kJ/hour)

    Typical: 23,900 BTU/hour (25,200 kJ/hour)

  • High capacity drives

    Maximum: 30,400 BTU/hour (32,100 kJ/hour)

    Typical: 21,200 BTU/hour (22,400 kJ/hour)

  • High performance drives

    Maximum: 19,100 BTU/hour (20,150 kJ/hour)

    Typical: 13,650 BTU/hour (14,400 kJ/hour)

  • High capacity drives

    Maximum: 17,400 BTU/hour (18,400 kJ/hour)

    Typical: 12,300 BTU/hour (13,000 kJ/hour)

  • High performance drives

    Maximum: 9,500 BTU/hour (10,000 kJ/hour)

    Typical: 6,700 BTU/hour (7,000 kJ/hour)

  • High capacity drives

    Maximum: 8,900 BTU/hour (9,400 kJ/hour)

    Typical: 6,500 BTU/hour (6,900 kJ/hour)

Air flow front-to-back (subject to actual data center environment)

  • High performance drives

    Maximum: Approximately 1,600 CFM

    Typical: Approximately 1,100 CFM

  • High capacity drives

    Maximum: Approximately 1,410 CFM

    Typical: Approximately 980 CFM

  • High performance drives

    Maximum: Approximately 900 CFM

    Typical: Approximately 650 CFM

  • High capacity drives

    Maximum: Approximately 810 CFM

    Typical: Approximately 570 CFM

  • High performance drives

    Maximum: Approximately 440 CFM

    Typical: Approximately 310 CFM

  • High capacity drives

    Maximum: Approximately 410 CFM

    Typical: Approximately 300 CFM

IP Addresses

42 for Ethernet network, assuming single cluster

36 for InfiniBand network

24 for Ethernet network, assuming single cluster

18 for InfiniBand network

13 for Ethernet network, assuming single cluster

8 for InfiniBand network

Network drops

Minimum of 1 network drop

Minimum of 1 network drop

Minimum of 1 network drop

External connectivity

12 InfiniBand ports

12 InfiniBand ports

12 InfiniBand ports