1.2.14 General Environmental Requirements for Oracle Exadata Storage Expansion Rack X3-2

The environmental requirements for Oracle Exadata Storage Expansion Rack X3-2 depend on the size of the system. Table 1-13 shows the general environmental requirements for each type of Oracle Exadata Storage Expansion Rack X3-2.

Table 1-13 Environmental Requirements for Oracle Exadata Storage Expansion Rack X3-2

Environmental Component Oracle Exadata Storage Expansion X3-2 Full Rack Oracle Exadata Storage Expansion X3-2 Half Rack Oracle Exadata Storage Expansion X3-2 Quarter Rack

Weight

827.4 kg (1824 lbs)

516.2 kg (1138 lbs)

349.7 kg (771 lbs)

Acoustic levels

82 db(A)

79 db(A)

76 db(A)

Power

  • High performance drives

    Maximum: 10.2 kVA

    Typical: 7.1 kVA (varies based on application load)

  • High capacity drives

    Maximum: 8.9 kVA

    Typical: 6.2 kVA (varies based on application load)

  • High performance drives

    Maximum: 5.7 kVA

    Typical: 4.1 kVA (varies based on application load)

  • High capacity drives

    Maximum: 5.1 kVA

    Typical: 3.6 kVA (varies based on application load)

  • High performance drives

    Maximum: 2.9 kVA

    Typical: 2.0 kVA (varies based on application load)

  • High capacity drives

    Maximum: 2.6 kVA

    Typical: 1.9 kVA (varies based on application load)

Cooling

  • High performance drives

    Maximum: 34,100 BTU/hour (36,000 kJ/hour)

    Typical: 23,900 BTU/hour (25,200 kJ/hour)

  • High capacity drives

    Maximum: 29,700 BTU/hour (31,300 kJ/hour)

    Typical: 20,800 BTU/hour (21,950 kJ/hour)

  • High performance drives

    Maximum: 19,100 BTU/hour (20,150 kJ/hour)

    Typical: 13,650 BTU/hour (14,400 kJ/hour)

  • High capacity drives

    Maximum: 17,100 BTU/hour (18,000 kJ/hour)

    Typical: 11,950 BTU/hour (12,600 kJ/hour)

  • High performance drives

    Maximum: 9,500 BTU/hour (10,000 kJ/hour)

    Typical: 6,700 BTU/hour (7,000 kJ/hour)

  • High capacity drives

    Maximum: 8,500 BTU/hour (9,000 kJ/hour)

    Typical: 6,150 BTU/hour (6,500 kJ/hour)

Air flow front-to-back (subject to actual data center environment)

  • High performance drives

    Maximum: Approximately 1,600 CFM

    Typical: Approximately 1,100 CFM

  • High capacity drives

    Maximum: Approximately 1,375 CFM

    Typical: Approximately 960 CFM

  • High performance drives

    Maximum: Approximately 900 CFM

    Typical: Approximately 650 CFM

  • High capacity drives

    Maximum: Approximately 790 CFM

    Typical: Approximately 550 CFM

  • High performance drives

    Maximum: Approximately 440 CFM

    Typical: Approximately 310 CFM

  • High capacity drives

    Maximum: Approximately 400 CFM

    Typical: Approximately 285 CFM

IP Addresses

42 for Ethernet network, assuming single cluster

18 for InfiniBand network

24 for Ethernet network, assuming single cluster

9 for InfiniBand network

13 for Ethernet network, assuming single cluster

4 for InfiniBand network

Network drops

Minimum of 1 network drop

Minimum of 1 network drop

Minimum of 1 network drop

External connectivity

12 InfiniBand ports

12 InfiniBand ports

12 InfiniBand ports