1.2.9 General Environmental Requirements for Oracle Exadata Database Machine X3-8 Full Rack with Exadata Storage Server X3-2 Servers

Table 1-8 shows the general environmental requirements for Oracle Exadata Database Machine X3-8 Full Rack with Exadata Storage Server X3-2 Servers. The other sections in this chapter provide detailed information.

Table 1-8 Environmental Requirements for Oracle Exadata Database Machine X3-8 Full Rack with Exadata Storage Server X3-2 Servers

Environmental Component Oracle Exadata Database Machine X3-8 Full Rack with Exadata Storage Server X3-2 Servers

Weight

See Also: "Flooring Requirements"

929.9 kg (2050 lbs)

Acoustic levels

84 db(A)

Power

See Also: "Electrical Power Requirements"

  • High performance drives

    Maximum: 15.3 kVA

    Typical: 10.7 kVA (varies based on application load)

  • High capacity drives

    Maximum: 14.3 kVA

    Typical: 10.0 kVA (varies based on application load)

Cooling

See Also: "Temperature and Humidity Requirements", and "Ventilation and Cooling Requirements"

  • High performance drives

    Maximum: 51,200 BTU/hour (54,000 kJ/hour)

    Typical: 35,900 BTU/hour (37,900 kJ/hour)

  • High capacity drives

    Maximum: 47,800 BTU/hour (50,400 kJ/hour)

    Typical: 33,500 BTU/hour (35,300 kJ/hour)

Air flow front-to-back (subject to actual data center environment)

See Also: "Temperature and Humidity Requirements", and "Ventilation and Cooling Requirements"

  • High performance drives

    Maximum: Approximately 2,400 CFM

    Typical: Approximately 1,700 CFM

  • High capacity drives

    Maximum: Approximately 2,200 CFM

    Typical: Approximately 1,550 CFM

IP Addresses

See Also: "Network Connection and IP Address Requirements for Oracle Exadata Database Machine"

45 for Ethernet network, assuming single cluster

22 for InfiniBand network

Network drops

See Also: "Network Connection and IP Address Requirements for Oracle Exadata Database Machine"

Minimum of 5 network drops

External connectivity

See Also: "Network Connection and IP Address Requirements for Oracle Exadata Database Machine"

16 x 1 GbE Ethernet ports

16 x 10 GbE Ethernet SFP+ ports

12 InfiniBand ports